Toshiba RAV-SM800XT-E Characteristics required for flux, Types of flux Noncorrosive flux, Brazing

Page 22

(2)Characteristics required for flux

Activated temperature of flux coincides with the brazing temperature.

Due to a wide effective temperature range, flux is hard to carbonize.

It is easy to remove slag after brazing.

The corrosive action to the treated metal and brazing filler is minimum.

It excels in coating performance and is harmless to the human body.

As the flux works in a complicated manner as described above, it is necessary to select an adequate type of flux according to the type and shape of treated metal, type of brazing filler and brazing method, etc.

(3)Types of flux

Noncorrosive flux

Generally, it is a compound of borax and boric acid.

It is effective in case where the brazing temperature is higher than 800°C.

Activated flux

Most of fluxes generally used for silver brazing are this type.

It features an increased oxide film removing capability due to the addition of compounds such as potassium fluoride, potassium chloride and sodium fluoride to the borax-boric acid compound.

(4)Piping materials for brazing and used brazing filler/flux

Piping

Used brazing

Used

material

filler

flux

 

 

 

Copper - Copper

Phosphor copper

Do not use

 

 

 

Copper - Iron

Silver

Paste flux

 

 

 

Iron - Iron

Silver

Vapor flux

 

 

 

1Do not enter flux into the refrigeration cycle.

2 When chlorine contained in the flux remains within the pipe, the lubricating oil deteriorates. Therefore, use a flux which does not contain chloring.

3 When adding water to the flux, use water which does not contain chlorine (e.g. distilled water or ion-exchange water).

4 Remove the flux after brazing.

6-5-3. Brazing

As brazing work requires sophisticated techniques, experiences based upon a theoretical knowledge, it must be performed by a person qualified.

In order to prevent the oxide film from occurring in the pipe interior during brazing, it is effective to proceed with brazing while letting dry Nitrogen gas (N2) flow.

Never use gas other than Nitrogen gas.

(1)Brazing method to prevent oxidation

1 Attach a reducing valve and a flow-meter to the Nitrogen gas cylinder.

2Use a copper pipe to direct the piping material, and attach a flow-meter to the cylinder.

3Apply a seal into the clearance between the piping material and inserted copper pipe for

Nitrogen in order to prevent backflow of the Nitrogen gas.

4When the Nitrogen gas is flowing, be sure to keep the piping end open.

5Adjust the flow rate of Nitrogen gas so that it is

lower than 0.05 m3/Hr or 0.02 Mpa (0.2 kgf/ cm2) by means of the reducing valve.

6After performing the steps above, keep the Nitrogen gas flowing until the pipe cools down to a certain extent (temperature at which pipes

are touchable with hands).

7Remove the flux completely after brazing.

MFlow meter

Stop valve

Nitrogen gas

cylinder

From Nitrogen cylinder

Pipe Nitrogen gas

Rubber plug

Fig. 6-5-1 Prevention of oxidation during brazing

– 20 –

Image 22
Contents AIR-CONDITIONER Contents Specifications Indoor UnitOperation characteristic curve Cooling Heating CurrentOutdoor Unit RAV-SM560AT-E RAV-SM800AT-EConstruction Views Outdoor Unit RAV-SM560AT-E Outdoor Unit RAV-SM800AT-E Systematic Refrigerating Cycle Diagram RAV-SM560XT-E / RAV-SM560AT-ERAV-SM800XT-E / RAV-SM800AT-E Indoor unitWiring Diagram Color IdentificationL N Board Specification of Electrical Parts Parts name Type SpecificationsRefrigerant R410A Safety During Installation/ServicingRefrigerant Piping Installation Piping materials and joints usedOuter diameter mm R410A R22 1 Thicknesses of annealed copper pipes Thickness mmProcessing of piping materials Clutch type Wing nut type Width·m kgf·cm ·m kgf·mRequired tools ToolsGeneral tools Conventional tools can be used 1 Configuration of refrigerant charging Recharging of RefrigerantBrazing of Pipes Activated flux Characteristics required for fluxTypes of flux Noncorrosive flux Filler FluxControl Block Diagram OperationAir volume control When power supply is resetOperation mode selection Operation DescriptionCool air discharge preventive control 1 Cold draft preventing controlLouver control Freeze preventive control Low temperature releaseHigh-temp release control Filter sign displayOperation How to set auto restart functionAuto Restart Function MotionsHow to turn off filter check lamp How to cancel auto restart functionPower failure during timer operation Filter Check LampUnder Ceiling Installation Installation ProcedureInstallation Diagram of Indoor and Outdoor Units Console InstallationPrecautions for Safety To Disconnect the Appliance from Main Power SupplyPage Accessory parts Accessory parts and Parts to be procured locallyParts to be procured locally Selection of Installation Place Avoid installing in the following placesRemote controller usage Installation PlaceRemote controller Before Installation Remove the Air inlet grilleCondition for Installation Install the indoor unitInstall the Suspension bolts Piping and Drain Hose InstallationConnect the Flexible pipe 5 to the large pipe Gas side Unit must not decline more than 15 mm in either Cutting a hole and mounting the Installation plateAxis Drain Piping Work DrainageRefrigerant Piping Tightening connection Evacuating Heat insulation For RAV-SM560AT-E model Electrical Work Final Installation Checks LED indication and code checking Environment Before troubleshooting TroubleshootingSummary of Troubleshooting Troubleshooting procedureSelf-Diagnosis by Remote Control Check Code How to use remote control in service modeJudgement and action No display in the setting at shipment Operation Troubleshooting for Each Check Code 1A error YESError 1C error* Except RAV-SM560AT-E 1E error 1D error1F error Connector normal? 20 TE, TO, TS sensor TA sensor TC, TCJ sensor Caracteristics-1 Caracteristics-2Caracteristics-3 TD sensor Caracteristics-4Compressor does not operate Inspection procedurePrimary check Cooling and heating model Are all of compressor cords normal? Detachments How to install the Air inlet grilleRemove the Panel arms from the Front panel Open 3 Cap screws and remove the screws How to remove the Drain pan Assembly Pan assembly Refrigeration How to remove the Refrigeration assemblyHow to remove the Multiblade fan Part name Procedures RemarksFan motor No. Part name Procedure Remarks DetachmentProcedure Remarks Requirement Connection with the power terminal Part name Procedure Remarks ‡ Compressor Perform works of items 1 ‚, ƒ, „, … Fan guard Remove the upper cabinet Discharge port cabinet for the heat ex Requirement Part name… Control P.C Remove the inverter box from P.C. board base Loosen the flange nut by turning clock † Compressor Perform works of items , ‚, ƒ, „, Ø4 x 10L , 2 pcs. per one reactor Product Exploded Views and Parts List Indoor Unit E-Parts AssyAir Inlet Grille Inverter 21,22 16,17 Outdoor Unit Inverter Assy, RAV-SM560AT-E 702 TE Sensor TS Sensor To Sensor TD Sensor 701 705 703 704Inverter BOX Outdoor Unit Inverter Assy, RAV-SM800AT-E