9-6. DRAIN PIPING WORK

9-6-1. Drainage

1. Run the Drain hose sloping downward.

NOTE :

The hole should be made at a slight downward slant on the outdoor side.

Under Ceiling Installation

Console Installation

50 mm or more

50 mm or more

Fig. 9-6-1

NOTICE

In case of upward drainage from the unit, (Under Ceiling Installation), it is necessary to use the Drain pump kit of optional part.

CAUTION

1.Do not raise the Drain hose.

2.Do not put the Drain hose into water.

3.Do not form the Drain hose into a wave shape.

4.Do not put the Drain hose end in the drainage ditch.

2.Open the louver manually and put some water into it. Then check the flow of water from the Drain hose.

Fig. 9-6-2

3.When connecting the Extension drain hose; insulate the connecting part of Extension drain hose with the Pipe shield.

Pipe shield

Drain hose

Inside the room

Extension drain hose

Fig. 9-6-3

CAUTION

Arrange the drain pipe for proper drainage from the unit.

Improper drainage can result in dew-dropping. (Provide by customer)

– 36 –

Image 38
Contents AIR-CONDITIONER Contents Specifications Indoor UnitOperation characteristic curve Cooling Heating CurrentOutdoor Unit RAV-SM560AT-E RAV-SM800AT-EConstruction Views Outdoor Unit RAV-SM560AT-E Outdoor Unit RAV-SM800AT-E Systematic Refrigerating Cycle Diagram RAV-SM560XT-E / RAV-SM560AT-ERAV-SM800XT-E / RAV-SM800AT-E Indoor unitWiring Diagram Color IdentificationL N Board Specification of Electrical Parts Parts name Type SpecificationsRefrigerant R410A Safety During Installation/ServicingRefrigerant Piping Installation Piping materials and joints usedProcessing of piping materials 1 Thicknesses of annealed copper pipes Thickness mmOuter diameter mm R410A R22 Clutch type Wing nut type Width·m kgf·cm ·m kgf·mGeneral tools Conventional tools can be used ToolsRequired tools 1 Configuration of refrigerant charging Recharging of RefrigerantBrazing of Pipes Activated flux Characteristics required for fluxTypes of flux Noncorrosive flux Filler FluxControl Block Diagram OperationAir volume control When power supply is resetOperation mode selection Operation DescriptionCool air discharge preventive control 1 Cold draft preventing controlLouver control Freeze preventive control Low temperature releaseHigh-temp release control Filter sign displayOperation How to set auto restart functionAuto Restart Function MotionsHow to turn off filter check lamp How to cancel auto restart functionPower failure during timer operation Filter Check LampUnder Ceiling Installation Installation ProcedureInstallation Diagram of Indoor and Outdoor Units Console InstallationPrecautions for Safety To Disconnect the Appliance from Main Power SupplyPage Parts to be procured locally Accessory parts and Parts to be procured locallyAccessory parts Selection of Installation Place Avoid installing in the following placesRemote controller usage Installation PlaceRemote controller Before Installation Remove the Air inlet grilleCondition for Installation Install the indoor unitInstall the Suspension bolts Piping and Drain Hose InstallationConnect the Flexible pipe 5 to the large pipe Gas side Axis Cutting a hole and mounting the Installation plateUnit must not decline more than 15 mm in either Drain Piping Work DrainageRefrigerant Piping Tightening connection Evacuating Heat insulation For RAV-SM560AT-E model Electrical Work Final Installation Checks LED indication and code checking Environment Before troubleshooting TroubleshootingSummary of Troubleshooting Troubleshooting procedureSelf-Diagnosis by Remote Control Check Code How to use remote control in service modeJudgement and action No display in the setting at shipment Operation Troubleshooting for Each Check Code 1A error YESError 1C error* Except RAV-SM560AT-E 1F error 1D error1E error Connector normal? 20 TE, TO, TS sensor TA sensor TC, TCJ sensor Caracteristics-1 Caracteristics-2Caracteristics-3 TD sensor Caracteristics-4Primary check Inspection procedureCompressor does not operate Cooling and heating model Are all of compressor cords normal? Remove the Panel arms from the Front panel How to install the Air inlet grilleDetachments Open 3 Cap screws and remove the screws How to remove the Drain pan Assembly Pan assembly Refrigeration How to remove the Refrigeration assemblyFan motor Part name Procedures RemarksHow to remove the Multiblade fan No. Part name Procedure Remarks DetachmentProcedure Remarks Requirement Connection with the power terminal Part name Procedure Remarks ‡ Compressor Perform works of items 1 ‚, ƒ, „, … Fan guard Remove the upper cabinet Discharge port cabinet for the heat ex Requirement Part name… Control P.C Remove the inverter box from P.C. board base Loosen the flange nut by turning clock † Compressor Perform works of items , ‚, ƒ, „, Ø4 x 10L , 2 pcs. per one reactor Product Exploded Views and Parts List Indoor Unit E-Parts AssyAir Inlet Grille Inverter 21,22 16,17 Outdoor Unit Inverter Assy, RAV-SM560AT-E 702 TE Sensor TS Sensor To Sensor TD Sensor 701 705 703 704Inverter BOX Outdoor Unit Inverter Assy, RAV-SM800AT-E