10. TROUBLESHOOTING

10-1. Summary of Troubleshooting

10-1-1. Before troubleshooting

(1)Required tools/instruments

e and d screwdrivers, spanners, radio cutting pliers, nippers, etc.

Tester, thermometer, pressure gauge, etc.

(2)Confirmation points before check

1 The following operations are normal.

a)Compressor does not operate.

Is not 3-minutes delay (3 minutes after compressor OFF)?

Does not thermostat turn off?

Does not timer operate during fan operation?

Is not outside high-temperature operation controlled in heating operation?

b)Indoor fan does not rotate.

Does not cool air discharge preventive control work in heating operation?

c)Outdoor fan does not rotate or air volume changes.

Does not high-temperature release opera- tion control work in heating operation?

Does not outside low-temperature opera- tion control work in cooling operation?

Is not defrost operation performed?

d)ON/OFF operation cannot be performed from remote control.

Is not forced operation performed?

Is not the control operation performed from

outside/remote side?

2Did you return the cabling to the initial positions?

3Are connecting cables between indoor unit and receiving unit correct?

10-1-2. Troubleshooting procedure

When a trouble occurred, check the parts along with the following procedure.

Trouble Confirmation of check code by service mode

Check defective position and parts.

NOTE :

For cause of a trouble, power conditions or malfunc- tion/erroneous diagnosis of microcomputer due to outer noise is considered except the items to be checked. If there is any noise source, change the cables of the signal line to shield cables.

10-1-3. Outline of Judgment

A primary judgment to detect cause of error exists on the indoor unit or outdoor unit is performed in the following procedure.

<Judgment by flashing display on the indoor unit display part>

The indoor unit monitors operating status of the air conditioner, and if a protective circuit works, contents of the self-diagnosis are displayed with a block restricted to the following cases on the indoor unit display part (Sensor).

Table 10-1-1

Remote

Block display

Contents of self-diagnosis

Check code

control code

 

 

 

 

 

 

 

––

Operation lamp display flashes. (1Hz)

Power failure (In power ON)

––

 

 

 

 

00

Operation lamp display flashes. (5Hz)

Indoor P.C. board

0b to 0F, 11, 12, b5, b6

 

 

 

 

01

Operation/timer lamp displays flash. (5Hz)

Inter-unit cables/transmission system

04

 

 

 

 

02

Operation/defrost lamp displays flash. (5Hz)

Outdoor P.C. board

14 to 19, 1A, 1C

 

 

 

 

03

Operation/timer/defrost lamp displays flash. (5Hz)

Cycle system, etc.

1d, 1E, 1F, 21

 

 

 

 

––

––

––

1b, 8b

 

 

 

 

– 46 –

Image 48
Contents AIR-CONDITIONER Contents Specifications Indoor UnitOperation characteristic curve Cooling Heating CurrentOutdoor Unit RAV-SM560AT-E RAV-SM800AT-EConstruction Views Outdoor Unit RAV-SM560AT-E Outdoor Unit RAV-SM800AT-E Systematic Refrigerating Cycle Diagram RAV-SM560XT-E / RAV-SM560AT-ERAV-SM800XT-E / RAV-SM800AT-E Indoor unitWiring Diagram Color IdentificationL N Board Specification of Electrical Parts Parts name Type SpecificationsSafety During Installation/Servicing Refrigerant Piping InstallationRefrigerant R410A Piping materials and joints used1 Thicknesses of annealed copper pipes Thickness mm Outer diameter mm R410A R22Processing of piping materials Clutch type Wing nut type Width·m kgf·cm ·m kgf·mTools Required toolsGeneral tools Conventional tools can be used 1 Configuration of refrigerant charging Recharging of RefrigerantBrazing of Pipes Characteristics required for flux Types of flux Noncorrosive fluxActivated flux Filler FluxControl Block Diagram OperationWhen power supply is reset Operation mode selectionAir volume control Operation DescriptionCool air discharge preventive control 1 Cold draft preventing controlFreeze preventive control Low temperature release High-temp release controlLouver control Filter sign displayHow to set auto restart function Auto Restart FunctionOperation MotionsHow to cancel auto restart function Power failure during timer operationHow to turn off filter check lamp Filter Check LampInstallation Procedure Installation Diagram of Indoor and Outdoor UnitsUnder Ceiling Installation Console InstallationPrecautions for Safety To Disconnect the Appliance from Main Power SupplyPage Accessory parts and Parts to be procured locally Accessory partsParts to be procured locally Selection of Installation Place Avoid installing in the following placesInstallation Place Remote controllerRemote controller usage Before Installation Remove the Air inlet grilleInstall the indoor unit Install the Suspension boltsCondition for Installation Piping and Drain Hose InstallationConnect the Flexible pipe 5 to the large pipe Gas side Cutting a hole and mounting the Installation plate Unit must not decline more than 15 mm in eitherAxis Drain Piping Work DrainageRefrigerant Piping Tightening connection Evacuating Heat insulation For RAV-SM560AT-E model Electrical Work Final Installation Checks LED indication and code checking Environment Troubleshooting Summary of TroubleshootingBefore troubleshooting Troubleshooting procedureSelf-Diagnosis by Remote Control Check Code How to use remote control in service modeJudgement and action No display in the setting at shipment Operation Troubleshooting for Each Check Code 1A error YESError 1C error* Except RAV-SM560AT-E 1D error 1E error1F error Connector normal? TA sensor TC, TCJ sensor Caracteristics-1 Caracteristics-2 Caracteristics-320 TE, TO, TS sensor TD sensor Caracteristics-4Inspection procedure Compressor does not operatePrimary check Cooling and heating model Are all of compressor cords normal? How to install the Air inlet grille DetachmentsRemove the Panel arms from the Front panel Open 3 Cap screws and remove the screws How to remove the Drain pan Assembly Pan assembly Refrigeration How to remove the Refrigeration assemblyPart name Procedures Remarks How to remove the Multiblade fanFan motor No. Part name Procedure Remarks DetachmentProcedure Remarks Requirement Connection with the power terminal Part name Procedure Remarks ‡ Compressor Perform works of items 1 ‚, ƒ, „, … Fan guard Remove the upper cabinet Discharge port cabinet for the heat ex Requirement Part name… Control P.C Remove the inverter box from P.C. board base Loosen the flange nut by turning clock † Compressor Perform works of items , ‚, ƒ, „, Ø4 x 10L , 2 pcs. per one reactor Product Exploded Views and Parts List Indoor Unit E-Parts AssyAir Inlet Grille Inverter 21,22 16,17 Outdoor Unit Inverter Assy, RAV-SM560AT-E 702 TE Sensor TS Sensor To Sensor TD Sensor 701 705 703 704Inverter BOX Outdoor Unit Inverter Assy, RAV-SM800AT-E