Toshiba RAV-SM560XT-E, RAV-SM800XT-E service manual No display in the setting at shipment

Page 51

Table 10-2-2

 

 

Operation of diagnostic function

 

 

 

 

 

 

 

 

 

 

 

Judgement and action

Block

Check

 

Symptom

Unit

Condition

 

code

 

status

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

[MODE]

 

 

The serial signal is not output

Operation

Displayed when

1.

Outdoor unit does not completely

[TIMER] lamp

 

 

from outdoor unit to indoor unit.

continues.

error is detected

 

operate.

5Hz flash

 

 

Miscabling of inter-unit cables

 

 

 

Inter-unit cable check, correction of

 

 

 

Defective serial sending circuit

 

 

 

miscabling

 

 

 

on outdoor P.C. board

 

 

 

Outdoor P.C. board check, P.C. board

 

 

 

Defective serial receiving circuit

 

 

 

cables check

 

 

 

on outdoor P.C. board

 

 

 

Compressor case thermo check

 

 

 

Compressor case thermo

 

 

2.

In normal operation

 

 

 

operation

 

 

 

When outdoor sending serial LED

 

 

 

 

 

 

 

(Green) flashes, the receiving serial

 

 

 

 

 

 

 

LED (Orange) also flashes. : Indoor

 

 

 

 

 

 

 

P.C. board (Main P.C. board) check

 

 

 

 

 

 

 

When the receiving serial LED (Orange)

 

 

 

 

 

 

 

does not flash: Outdoor P.C. board

 

 

 

 

 

 

 

check

 

 

 

 

 

 

 

 

 

 

 

BUS communication circuit error

Operation

Displayed when

1.

Communication line check, miscabling

 

 

 

* BUS communication was

continues

error is detected

 

check

 

 

 

interrupted over the specified

(According

 

 

Power supply check for central control

 

 

 

time.

to remote

 

 

(Central control remote control, etc.)

 

 

 

 

control of

 

 

and indoor unit

 

 

 

 

indoor

 

2.

Communication check (XY terminal)

 

 

 

 

unit)

 

3.

Indoor P.C. board check

 

 

 

 

 

 

4.

Central control check

 

 

 

 

 

 

 

(Communication P.C. board)

 

 

 

 

 

 

 

 

 

 

 

Error in 4-way valve system

Operation

Displayed when

1.

Check 4-way valve.

 

 

 

Indoor heat exchanger

continues.

error is detected

2.

Check 2-way valve and non-return

 

 

 

temperature rise after start of

 

 

 

valve.

 

 

 

cooling operation.

 

 

3.

Check indoor heat exchanger sensor

 

 

 

Indoor heat exchanger

 

 

 

(TC).

 

 

 

temperature fall after start of

 

 

4.

Check indoor P.C. board

 

 

 

heating operation.

 

 

 

(Main P.C. board).

 

 

 

 

 

 

 

 

 

 

 

Error in other cycles

Operation

Displayed when

1.

Compressor case thermo operation.

 

 

 

Indoor heat exchanger temp

continues.

error is detected

2.

Coming-off of detection part of indoor

 

 

 

(TC) does not vary after start of

 

 

 

heat exchanger sensor.

 

*

 

cooling/ heating operation.

 

 

3.

Check indoor heat exchanger sensor

 

 

 

 

 

4.

(TC).

 

 

 

 

 

 

Check indoor P.C. board

 

 

 

 

 

 

 

(Main P.C. board).

 

 

 

 

 

 

 

 

[MODE] lamp

 

 

Coming-off, disconnection or

Operation

Displayed when

1.

Check indoor temp sensor (TA).

5Hz flash

 

 

short of indoor temp sensor (TA)

continues.

error is detected

2.

Check indoor P.C. board

 

 

 

 

 

 

 

(Main P.C. board).

 

 

 

 

 

 

 

 

 

 

 

Coming-off, disconnection or

Operation

Displayed when

1.

Check indoor temp sensor (TC).

 

 

 

short of indoor temp sensor (TC)

continues.

error is detected

2.

Check indoor P.C. board

 

 

 

 

 

 

 

(Main P.C. board).

 

 

 

 

 

 

 

 

 

 

 

Coming-off, disconnection or

Operation

Displayed when

1.

Check indoor temp sensor (TCJ).

 

 

 

short of indoor temp sensor

continues.

error is detected

2.

Check indoor P.C. board (Main P.C.

 

 

 

(TCJ)

 

 

 

board).

 

 

 

 

 

 

 

 

[MODE] lamp

 

 

Error in indoor fan system

All stop

Displayed when

1.

Check indoor fan motor connector

5Hz flash

 

 

Revolutions frequency error of fan

 

error is detected

 

circuit (CN210).

 

 

 

 

 

 

2.

Check indoor fan.

 

 

 

 

 

 

3.

Check indoor P.C. board

 

 

 

 

 

 

 

(Main P.C. board).

 

 

 

 

 

 

 

 

 

 

 

Error in indoor unit or other

Operation

Displayed when

1.

Check indoor P.C. board

 

 

 

positions

continues.

error is detected

 

(EEPROM and peripheral circuits)

 

 

 

1. EEPROM access error

 

 

 

(Main P.C. board).

 

 

 

 

 

 

 

 

 

 

 

Outside error input

Operation

Displayed when

1.

Check outside devices.

 

 

 

Detected by input voltage level

continues.

error is detected

2.

Check indoor P.C. board

 

 

 

from outside devices

 

 

 

(Main P.C. board).

 

 

 

 

 

 

 

 

 

 

 

Outside interlock input

All stop

Displayed when

 

 

 

 

 

Detected by input voltage level

 

error is detected

 

 

 

 

 

from outside devices

 

 

 

 

 

 

 

 

 

 

 

 

*: No display in the setting at shipment

– 49 –

Image 51
Contents AIR-CONDITIONER Contents Indoor Unit SpecificationsCurrent Operation characteristic curve Cooling HeatingRAV-SM560AT-E RAV-SM800AT-E Outdoor UnitConstruction Views Outdoor Unit RAV-SM560AT-E Outdoor Unit RAV-SM800AT-E RAV-SM560XT-E / RAV-SM560AT-E Systematic Refrigerating Cycle DiagramIndoor unit RAV-SM800XT-E / RAV-SM800AT-EColor Identification Wiring DiagramL N Board Parts name Type Specifications Specification of Electrical PartsPiping materials and joints used Safety During Installation/ServicingRefrigerant Piping Installation Refrigerant R410A1 Thicknesses of annealed copper pipes Thickness mm Outer diameter mm R410A R22Processing of piping materials Width Clutch type Wing nut type·m kgf·m ·m kgf·cmTools Required toolsGeneral tools Conventional tools can be used Recharging of Refrigerant 1 Configuration of refrigerant chargingBrazing of Pipes Filler Flux Characteristics required for fluxTypes of flux Noncorrosive flux Activated fluxOperation Control Block DiagramOperation Description When power supply is resetOperation mode selection Air volume control1 Cold draft preventing control Cool air discharge preventive controlFilter sign display Freeze preventive control Low temperature releaseHigh-temp release control Louver controlMotions How to set auto restart functionAuto Restart Function OperationFilter Check Lamp How to cancel auto restart functionPower failure during timer operation How to turn off filter check lampConsole Installation Installation ProcedureInstallation Diagram of Indoor and Outdoor Units Under Ceiling InstallationTo Disconnect the Appliance from Main Power Supply Precautions for SafetyPage Accessory parts and Parts to be procured locally Accessory partsParts to be procured locally Avoid installing in the following places Selection of Installation PlaceBefore Installation Remove the Air inlet grille Installation PlaceRemote controller Remote controller usagePiping and Drain Hose Installation Install the indoor unitInstall the Suspension bolts Condition for InstallationConnect the Flexible pipe 5 to the large pipe Gas side Cutting a hole and mounting the Installation plate Unit must not decline more than 15 mm in eitherAxis Drainage Drain Piping WorkRefrigerant Piping Tightening connection Evacuating Heat insulation For RAV-SM560AT-E model Electrical Work Final Installation Checks LED indication and code checking Environment Troubleshooting procedure TroubleshootingSummary of Troubleshooting Before troubleshootingHow to use remote control in service mode Self-Diagnosis by Remote Control Check CodeJudgement and action No display in the setting at shipment Operation YES Troubleshooting for Each Check Code 1A errorError 1C error* Except RAV-SM560AT-E 1D error 1E error1F error Connector normal? TD sensor Caracteristics-4 TA sensor TC, TCJ sensor Caracteristics-1 Caracteristics-2Caracteristics-3 20 TE, TO, TS sensorInspection procedure Compressor does not operatePrimary check Cooling and heating model Are all of compressor cords normal? How to install the Air inlet grille DetachmentsRemove the Panel arms from the Front panel Open 3 Cap screws and remove the screws How to remove the Drain pan Refrigeration How to remove the Refrigeration assembly Assembly Pan assemblyPart name Procedures Remarks How to remove the Multiblade fanFan motor Detachment No. Part name Procedure RemarksProcedure Remarks Requirement Connection with the power terminal Part name Procedure Remarks ‡ Compressor Perform works of items 1 ‚, ƒ, „, … Fan guard Remove the upper cabinet Discharge port cabinet for the heat ex Part name Requirement… Control P.C Remove the inverter box from P.C. board base Loosen the flange nut by turning clock † Compressor Perform works of items , ‚, ƒ, „, Ø4 x 10L , 2 pcs. per one reactor Product Indoor Unit E-Parts Assy Exploded Views and Parts ListAir Inlet Grille Inverter 21,22 16,17 702 TE Sensor TS Sensor To Sensor TD Sensor 701 705 703 704 Outdoor Unit Inverter Assy, RAV-SM560AT-EOutdoor Unit Inverter Assy, RAV-SM800AT-E Inverter BOX