Toshiba RAV-SM560XT-E Cool air discharge preventive control, Cold draft preventing control

Page 25

<HEAT>

Preset

°C

 

 

0

L

temp.

0.5

 

temp.)

1

*1

1.5

*2

2

 

8-4. Cool air discharge preventive control

In heating operation, the indoor heat exchanger restricts revolving speed of the fan motor to prevent a cold draft. The upper limit of the revolving speed is shown in Fig. 8-4-1 and Table 8-4-1.

(Preset

 

M+

 

 

temp.)

5.0

 

5.5

 

(Room

H

[FAN AUTO]

 

 

 

NOTE :

*1, *2 : The values marked with *1 and *2 are calculated and controlled by the difference in motor speed between M+ and L.

 

46

34

 

45

33

 

33

21

 

32

20

*2

A+4

A+4

 

A8

A8

 

 

 

 

*6

*5

 

 

 

Manual

(One of AUTO 5 steps)

*4 LH (Up to setting

SUL*3 speed)

SUL*1

Stop

Fig. 8-3-2

Table 8-3-1

 

 

RAV-SM560XT-E

RAV-SM800XT-E

MODEL

 

 

 

 

Motor speed

Air flow level

Motor speed

Air flow level

 

 

(rpm)

 

(m3/h)

(rpm)

(m3/h)

Cooling

HIGH

1060

 

800

1190

900

 

 

 

 

 

 

 

and

MED

950

 

690

1010

750

 

 

 

 

 

 

 

Fan only

LOW

800

 

580

850

650

 

HIGH

1120

 

830

1300

980

Heating

MED

970

 

730

1070

800

 

LOW

820

 

600

860

650

 

 

 

 

 

 

 

 

 

LOW+

=

LOW+MED

 

 

 

 

 

2

 

 

 

 

MED+

= MED+HIGH

 

 

 

 

 

2

 

 

NOTES :

*1: The fan stops for 2 minutes after thermostat-OFF.

*2: A is 24°C when the preset temperature is 24°C or more and A is the preset temperature when it is under 24°C.

*3: SUL means Super Ultra Low.

*4: Calculated from difference in motor speed between SUL and HIGH.

Fig. 8-4-1 Cold draft preventing control

*5 and *6:

Table 8-4-1

Fan

*5

 

*6

 

speed

 

Starting period

 

Stabilized period

 

 

 

 

 

AUTO

Up until 12 minutes

From 12 to 25 minutes

 

 

passed after starting

 

passed after starting

 

the unit

 

the unit and room

 

From 12 to 25 minutes

 

temperature is

 

 

passed after starting

 

between preset

 

 

the unit and room

 

temperature and 3°C

 

 

temperature is 3°C

 

lower than preset

 

 

lower than preset

 

temperature

 

 

temperature

25 minutes or more

 

 

 

 

passed after starting

 

 

 

 

the unit

Manual

Room temperature

Room temperature

(L – H)

 

< Preset temperature

 

Preset temperature

 

 

–4°C

 

–3.5°C

– 23 –

Image 25
Contents AIR-CONDITIONER Contents Indoor Unit SpecificationsCurrent Operation characteristic curve Cooling HeatingRAV-SM560AT-E RAV-SM800AT-E Outdoor UnitConstruction Views Outdoor Unit RAV-SM560AT-E Outdoor Unit RAV-SM800AT-E RAV-SM560XT-E / RAV-SM560AT-E Systematic Refrigerating Cycle DiagramIndoor unit RAV-SM800XT-E / RAV-SM800AT-EColor Identification Wiring DiagramL N Board Parts name Type Specifications Specification of Electrical PartsRefrigerant Piping Installation Safety During Installation/ServicingRefrigerant R410A Piping materials and joints usedOuter diameter mm R410A R22 1 Thicknesses of annealed copper pipes Thickness mmProcessing of piping materials Width Clutch type Wing nut type·m kgf·m ·m kgf·cmRequired tools ToolsGeneral tools Conventional tools can be used Recharging of Refrigerant 1 Configuration of refrigerant chargingBrazing of Pipes Types of flux Noncorrosive flux Characteristics required for fluxActivated flux Filler FluxOperation Control Block DiagramOperation mode selection When power supply is resetAir volume control Operation Description1 Cold draft preventing control Cool air discharge preventive controlHigh-temp release control Freeze preventive control Low temperature releaseLouver control Filter sign displayAuto Restart Function How to set auto restart functionOperation MotionsPower failure during timer operation How to cancel auto restart functionHow to turn off filter check lamp Filter Check LampInstallation Diagram of Indoor and Outdoor Units Installation ProcedureUnder Ceiling Installation Console InstallationTo Disconnect the Appliance from Main Power Supply Precautions for SafetyPage Accessory parts Accessory parts and Parts to be procured locallyParts to be procured locally Avoid installing in the following places Selection of Installation PlaceRemote controller Installation PlaceRemote controller usage Before Installation Remove the Air inlet grilleInstall the Suspension bolts Install the indoor unitCondition for Installation Piping and Drain Hose InstallationConnect the Flexible pipe 5 to the large pipe Gas side Unit must not decline more than 15 mm in either Cutting a hole and mounting the Installation plateAxis Drainage Drain Piping WorkRefrigerant Piping Tightening connection Evacuating Heat insulation For RAV-SM560AT-E model Electrical Work Final Installation Checks LED indication and code checking Environment Summary of Troubleshooting TroubleshootingBefore troubleshooting Troubleshooting procedureHow to use remote control in service mode Self-Diagnosis by Remote Control Check CodeJudgement and action No display in the setting at shipment Operation YES Troubleshooting for Each Check Code 1A errorError 1C error* Except RAV-SM560AT-E 1E error 1D error1F error Connector normal? Caracteristics-3 TA sensor TC, TCJ sensor Caracteristics-1 Caracteristics-220 TE, TO, TS sensor TD sensor Caracteristics-4Compressor does not operate Inspection procedurePrimary check Cooling and heating model Are all of compressor cords normal? Detachments How to install the Air inlet grilleRemove the Panel arms from the Front panel Open 3 Cap screws and remove the screws How to remove the Drain pan Refrigeration How to remove the Refrigeration assembly Assembly Pan assemblyHow to remove the Multiblade fan Part name Procedures RemarksFan motor Detachment No. Part name Procedure RemarksProcedure Remarks Requirement Connection with the power terminal Part name Procedure Remarks ‡ Compressor Perform works of items 1 ‚, ƒ, „, … Fan guard Remove the upper cabinet Discharge port cabinet for the heat ex Part name Requirement… Control P.C Remove the inverter box from P.C. board base Loosen the flange nut by turning clock † Compressor Perform works of items , ‚, ƒ, „, Ø4 x 10L , 2 pcs. per one reactor Product Indoor Unit E-Parts Assy Exploded Views and Parts ListAir Inlet Grille Inverter 21,22 16,17 702 TE Sensor TS Sensor To Sensor TD Sensor 701 705 703 704 Outdoor Unit Inverter Assy, RAV-SM560AT-EOutdoor Unit Inverter Assy, RAV-SM800AT-E Inverter BOX