Toshiba RAV-SM560XT-E, RAV-SM800XT-E Troubleshooting for Each Check Code 1A error, Yes

Page 53

10-3. Troubleshooting for Each Check Code

[1A error]

Are connections of CN301 and

 

CN300 of CDB correct?

 

YES

 

Does the fan rotate without trouble

NO

when handling the fan with hands under condition

 

of removing CN301 and CN300 from CDB?

 

YES

 

The status that the resistance values

 

between leads below are 50 to 80

 

for 40 W motor (ICF-140-43) and 25 to 55

NO

for 60 W motor (ICF-140-63-1) is normal.

 

Between 1 (Red lead) and 2 (White lead)

 

Between 2 (White lead) and 3 (Black lead)

 

Between 3 (Black lead) and 1 (Red lead)

 

of motor winding of connector (CN301)

 

YES

 

The status that there is

 

5k to 20kresistance values between

NO

1 (Yellow lead) and 4 (Pink lead)

 

of motor position detection of connector

 

(CN300, CN302) is normal.

 

YES

 

CN301

CN300

For RAV-SM560AT-E, CN300 changes to CN301, and CN301 to CN300, respectively.

Normal fan motor

(CDB error)

Defective fan motor

NOTE :

However, GND circuit error inside of the motor is rarely detected even if the above check is carried out. When the circuit does not become normal even if P.C. board has been replaced, replace outdoor fan motor.

 

RAV-SM560AT-E

RAV-SM800AT-E

 

 

 

Objective P.C. board

Control P.C. board

CDB P.C. board

 

 

 

Fan motor winding

CN300

CN301

 

 

 

Motor position detection

CN301

CN300

 

 

 

– 51 –

Image 53
Contents AIR-CONDITIONER Contents Indoor Unit SpecificationsCurrent Operation characteristic curve Cooling HeatingRAV-SM560AT-E RAV-SM800AT-E Outdoor UnitConstruction Views Outdoor Unit RAV-SM560AT-E Outdoor Unit RAV-SM800AT-E RAV-SM560XT-E / RAV-SM560AT-E Systematic Refrigerating Cycle DiagramIndoor unit RAV-SM800XT-E / RAV-SM800AT-EColor Identification Wiring DiagramL N Board Parts name Type Specifications Specification of Electrical PartsRefrigerant Piping Installation Safety During Installation/ServicingRefrigerant R410A Piping materials and joints usedProcessing of piping materials 1 Thicknesses of annealed copper pipes Thickness mmOuter diameter mm R410A R22 Width Clutch type Wing nut type·m kgf·m ·m kgf·cmGeneral tools Conventional tools can be used ToolsRequired tools Recharging of Refrigerant 1 Configuration of refrigerant chargingBrazing of Pipes Types of flux Noncorrosive flux Characteristics required for fluxActivated flux Filler FluxOperation Control Block DiagramOperation mode selection When power supply is resetAir volume control Operation Description1 Cold draft preventing control Cool air discharge preventive controlHigh-temp release control Freeze preventive control Low temperature releaseLouver control Filter sign displayAuto Restart Function How to set auto restart functionOperation MotionsPower failure during timer operation How to cancel auto restart functionHow to turn off filter check lamp Filter Check LampInstallation Diagram of Indoor and Outdoor Units Installation ProcedureUnder Ceiling Installation Console InstallationTo Disconnect the Appliance from Main Power Supply Precautions for SafetyPage Parts to be procured locally Accessory parts and Parts to be procured locallyAccessory parts Avoid installing in the following places Selection of Installation PlaceRemote controller Installation PlaceRemote controller usage Before Installation Remove the Air inlet grilleInstall the Suspension bolts Install the indoor unitCondition for Installation Piping and Drain Hose InstallationConnect the Flexible pipe 5 to the large pipe Gas side Axis Cutting a hole and mounting the Installation plateUnit must not decline more than 15 mm in either Drainage Drain Piping WorkRefrigerant Piping Tightening connection Evacuating Heat insulation For RAV-SM560AT-E model Electrical Work Final Installation Checks LED indication and code checking Environment Summary of Troubleshooting TroubleshootingBefore troubleshooting Troubleshooting procedureHow to use remote control in service mode Self-Diagnosis by Remote Control Check CodeJudgement and action No display in the setting at shipment Operation YES Troubleshooting for Each Check Code 1A errorError 1C error* Except RAV-SM560AT-E 1F error 1D error1E error Connector normal? Caracteristics-3 TA sensor TC, TCJ sensor Caracteristics-1 Caracteristics-220 TE, TO, TS sensor TD sensor Caracteristics-4Primary check Inspection procedureCompressor does not operate Cooling and heating model Are all of compressor cords normal? Remove the Panel arms from the Front panel How to install the Air inlet grilleDetachments Open 3 Cap screws and remove the screws How to remove the Drain pan Refrigeration How to remove the Refrigeration assembly Assembly Pan assemblyFan motor Part name Procedures RemarksHow to remove the Multiblade fan Detachment No. Part name Procedure RemarksProcedure Remarks Requirement Connection with the power terminal Part name Procedure Remarks ‡ Compressor Perform works of items 1 ‚, ƒ, „, … Fan guard Remove the upper cabinet Discharge port cabinet for the heat ex Part name Requirement… Control P.C Remove the inverter box from P.C. board base Loosen the flange nut by turning clock † Compressor Perform works of items , ‚, ƒ, „, Ø4 x 10L , 2 pcs. per one reactor Product Indoor Unit E-Parts Assy Exploded Views and Parts ListAir Inlet Grille Inverter 21,22 16,17 702 TE Sensor TS Sensor To Sensor TD Sensor 701 705 703 704 Outdoor Unit Inverter Assy, RAV-SM560AT-EOutdoor Unit Inverter Assy, RAV-SM800AT-E Inverter BOX