Toshiba RAV-SM800XT-E, RAV-SM560XT-E service manual Electrical Work

Page 44

9-9. ELECTRICAL WORK

For the air conditioner that has no power cord.

NOTE :

For selection and connection method of the power supply cords, refer to the details in the Installation Manual of the outdoor unit.

CAUTION

If incorrect/incomplete wiring is carried out, it may cause an electrical fire or smoke.

Prepare the power supply for exclusive use with the air conditioner.

Be sure to use the cord clamps specified posi- tions with attached to the product.

Do not damage or scratch the conductive core and inner insulator of power and inter-connecting cables when peeling them.

Be sure to comply with local cords on running the wire from outdoor unit to indoor unit (size of wire and wiring method etc.)

Use the power cord and Inter-connecting cable with specified thickness, specified type, and protective devices specified.

Fig. 9-9-2

NOTE :

Connect the earth line to the metallic part (i mark) located at the side of 3P terminal.

9-9-3. Wiring between units

1.Connect the wires between the units correctly. Errors made in the connections can result in the unit malfunctioning.

2.Connect the control wires between the outdoor unit and indoor unit as shown in the figure below:

9-9-4. Wiring Connections

9-9-1. How to wire

Terminal cover

1. Connect the connecting cable to the terminal as

Screws

identified with their respective matched numbers on

Cord clamp

the terminal block of indoor and outdoor unit.

H07RN-F or 245IEC66 (1.5 mm2 or more)

 

2. Insulate the unsheathed redundant cords

 

(conductors) with electrical insulation tape. Process

Earth terminal

them so that they do not touch any electrical or

 

metal parts.

 

3. For inter-unit wiring, do not use a cut wire jointed to another on the way.

9-9-2. Stripping length of connecting cable

10

10

50

40

Earth line

Fig. 9-9-1

NOTE :

Use stranded wire only.

Wire type : More than 1.5 mm2 (H07RN-F or 245IEC66) or 1.3 mm2 (AWG-16)

Fig. 9-9-3

1.Remove the Terminal cover and the Cord clamp.

2.Insert the connecting cable into the pipe hole on the wall.

3.Insert the connecting cable fully into the terminal block and secure it tightly with the screw. Tightening Torque: 1.2 N•m (0.12 kgf•m)

4.Fix the connecting cable by the Cord clamp with two screws.

5.Fix the Terminal cover.

42 –

Image 44
Contents AIR-CONDITIONER Contents Specifications Indoor UnitOperation characteristic curve Cooling Heating CurrentOutdoor Unit RAV-SM560AT-E RAV-SM800AT-EConstruction Views Outdoor Unit RAV-SM560AT-E Outdoor Unit RAV-SM800AT-E Systematic Refrigerating Cycle Diagram RAV-SM560XT-E / RAV-SM560AT-ERAV-SM800XT-E / RAV-SM800AT-E Indoor unitWiring Diagram Color IdentificationL N Board Specification of Electrical Parts Parts name Type SpecificationsSafety During Installation/Servicing Refrigerant Piping InstallationRefrigerant R410A Piping materials and joints usedProcessing of piping materials 1 Thicknesses of annealed copper pipes Thickness mmOuter diameter mm R410A R22 Clutch type Wing nut type Width·m kgf·cm ·m kgf·mGeneral tools Conventional tools can be used ToolsRequired tools 1 Configuration of refrigerant charging Recharging of RefrigerantBrazing of Pipes Characteristics required for flux Types of flux Noncorrosive fluxActivated flux Filler FluxControl Block Diagram OperationWhen power supply is reset Operation mode selectionAir volume control Operation DescriptionCool air discharge preventive control 1 Cold draft preventing controlFreeze preventive control Low temperature release High-temp release controlLouver control Filter sign displayHow to set auto restart function Auto Restart FunctionOperation MotionsHow to cancel auto restart function Power failure during timer operationHow to turn off filter check lamp Filter Check LampInstallation Procedure Installation Diagram of Indoor and Outdoor UnitsUnder Ceiling Installation Console InstallationPrecautions for Safety To Disconnect the Appliance from Main Power SupplyPage Parts to be procured locally Accessory parts and Parts to be procured locallyAccessory parts Selection of Installation Place Avoid installing in the following placesInstallation Place Remote controllerRemote controller usage Before Installation Remove the Air inlet grilleInstall the indoor unit Install the Suspension boltsCondition for Installation Piping and Drain Hose InstallationConnect the Flexible pipe 5 to the large pipe Gas side Axis Cutting a hole and mounting the Installation plateUnit must not decline more than 15 mm in either Drain Piping Work DrainageRefrigerant Piping Tightening connection Evacuating Heat insulation For RAV-SM560AT-E model Electrical Work Final Installation Checks LED indication and code checking Environment Troubleshooting Summary of TroubleshootingBefore troubleshooting Troubleshooting procedureSelf-Diagnosis by Remote Control Check Code How to use remote control in service modeJudgement and action No display in the setting at shipment Operation Troubleshooting for Each Check Code 1A error YESError 1C error* Except RAV-SM560AT-E 1F error 1D error1E error Connector normal? TA sensor TC, TCJ sensor Caracteristics-1 Caracteristics-2 Caracteristics-320 TE, TO, TS sensor TD sensor Caracteristics-4Primary check Inspection procedureCompressor does not operate Cooling and heating model Are all of compressor cords normal? Remove the Panel arms from the Front panel How to install the Air inlet grilleDetachments Open 3 Cap screws and remove the screws How to remove the Drain pan Assembly Pan assembly Refrigeration How to remove the Refrigeration assemblyFan motor Part name Procedures RemarksHow to remove the Multiblade fan No. Part name Procedure Remarks DetachmentProcedure Remarks Requirement Connection with the power terminal Part name Procedure Remarks ‡ Compressor Perform works of items 1 ‚, ƒ, „, … Fan guard Remove the upper cabinet Discharge port cabinet for the heat ex Requirement Part name… Control P.C Remove the inverter box from P.C. board base Loosen the flange nut by turning clock † Compressor Perform works of items , ‚, ƒ, „, Ø4 x 10L , 2 pcs. per one reactor Product Exploded Views and Parts List Indoor Unit E-Parts AssyAir Inlet Grille Inverter 21,22 16,17 Outdoor Unit Inverter Assy, RAV-SM560AT-E 702 TE Sensor TS Sensor To Sensor TD Sensor 701 705 703 704Inverter BOX Outdoor Unit Inverter Assy, RAV-SM800AT-E