Table
|
| Operation of diagnostic function |
|
|
|
| |
|
|
|
|
|
|
| Judgement and action |
Check | Block | Check | Symptom | Unit | Condition |
| |
code | code | status |
|
| |||
|
|
|
|
| |||
|
|
|
|
|
|
|
|
| Indoor |
| The indoor thermo sensor (TA) is | Operation | The lamp on the | 1. | Check the indoor thermo sensor (TA). |
| P.C. board |
| defective. | continues. | indoor unit blinks | 2. | Check the indoor P.C. board. |
|
|
| Disconnection or |
| when error is |
|
|
|
|
|
|
| defected. |
|
|
|
|
|
|
|
|
|
|
|
|
| The indoor heat exchanger | Operation | The lamp on the | 1. | Check the indoor heat exchanger |
|
|
| sensor (TC) is defective. | continues. | indoor unit blinks |
| sensor (TC). |
|
|
| Disconnection or |
| when error is | 2. | Check the indoor P.C. board. |
|
|
|
|
| defected. |
|
|
|
|
|
|
|
|
|
|
|
|
| The indoor fan motor or its circuit | All off | The lamp on the | 1. | Check the connector circuit of the |
|
|
| is defective. |
| indoor unit blinks |
| indoor fan motor (CN10). |
|
|
|
|
| when error is | 2. | Check the indoor fan motor. |
|
|
|
|
| defected. | 3. Check the indoor P.C. board. | |
|
|
| The part other than the above | Operation | The lamp on the | 1. | Check the indoor P.C. board. |
|
|
| parts on the indoor P.C. board is | continues. | indoor unit blinks |
| (EEPROM and peripheral circuits) |
|
|
| defective. |
| when error is |
|
|
|
|
| EEPROM access error |
| defected. |
|
|
|
|
| IOL operation | All off | The lamp on the | Overload operation of refrigerating cycle | |
|
|
|
|
| indoor unit blinks |
|
|
|
|
|
|
| when error is |
|
|
|
|
|
|
| defected. |
|
|
| The block is |
| The variation of TC, 5 minutes | Operation | The lamp on the | 1. | Check whether or not the TC sensor |
| unidentifi- |
| after starting the compressor, | continues. | indoor unit blinks |
| comes off. |
| able |
| is 2K or less. |
| when error is | 2. | Check whether or not it is possible to |
|
|
|
|
| defected. |
| operate the compressor and the |
|
|
|
|
|
|
| outdoor fan motor. |
|
|
|
|
|
| 3. | Check gas leak. |
| Cable |
| The serial signals can not be | Operation | The lamp on the | 1. | In the case of the outdoor unit not |
| connection |
| transmitted and received between | continues. | indoor unit blinks |
| operating at all; |
|
|
| indoor and outdoor units. |
| when error is |
| • Check the crossover cable and |
|
|
| • The crossover wire is |
| defected. |
| connect it properly. |
|
|
| connected wrongly. |
|
|
| • Check the outdoor P.C. board. |
|
|
| • The serial signal transmitting |
|
| 2. | In the case of the outdoor unit operating |
|
|
| circuit on the outdoor P.C. board |
|
|
| normally; |
|
|
| is defective. |
|
|
| • Check whether or not both of serial |
|
|
| • The serial signal receiving |
|
|
| LED (Green) and serial LED (Orange) |
|
|
| circuit on the indoor P.C. board |
|
|
| is blinking. |
|
|
| is defective. |
|
|
| If the serial LED (Green) is not |
|
|
|
|
|
|
| blinking, check the outdoor P.C. board. |
|
|
|
|
|
|
| If the serial LED (Orange) is not |
|
|
|
|
|
|
| blinking, check the indoor P.C. board. |
|
|
|
|
|
|
| |
|
|
| The operation command signals | Operation | The lamp on the | If the operation command signals continue | |
|
|
| are not transmitted from the | continues. | indoor unit blinks | to be transmitted between 2 and 3 of the | |
|
|
| indoor unit to the outdoor unit. |
| when error is | indoor terminal block, replace the outdoor | |
|
|
|
|
| defected. And it | P.C. board. | |
|
|
|
|
| returns to the |
|
|
|
|
|
|
| normal condition |
|
|
|
|
|
|
| when recovering |
|
|
|
|
|
|
| from errors. |
|
|
| Outdoor |
| The outdoor thermo sensor (TE) | All off | The lamp on the | 1. | Check the outdoor thermo sensor (TE). |
| P.C. board |
| is defective. |
| indoor unit blinks | 2. | Check the outdoor P.C. board. |
|
|
| Disconnection or |
| when error is |
|
|
|
|
|
|
| defected. |
|
|
|
|
| The outdoor heat exchanger (TD) | All off | The lamp on the | 1. | Check the outdoor heat exchanger |
|
|
| sensor is defective. |
| indoor unit blinks |
| sensor (TD). |
|
|
| Disconnection or |
| when error is | 2. | Check the outdoor P.C. board. |
|
|
|
|
| defected. |
|
|
|
|
|
|
|
|
|
|
| Other parts |
| The reply serial signal has been | Operation | The lamp on the | 1. | Repeatedly turn the indoor unit on and |
| (including |
| transmitted when starting the | continues. | indoor unit blinks |
| off with the interval of approx. 10 to 40 |
| compressor) |
| unit, but stops being transmitted |
| when error is |
| minutes. (The check code is not |
|
|
| shortly after. |
| defected. And it |
| indicated during operation.) And supply |
|
|
| 1. Compressor thermo operation |
| returns to the |
| gas. (Check gas leak.) |
|
|
| • Gas shortage |
| normal condition | 2. | The indoor unit operates normally |
|
|
| • Gas leak |
| when recovering |
| during the check. |
|
|
| 2. Instantaneous power failure |
| from errors. |
| If the reply serial signal continues to be |
|
|
|
|
|
|
| transmitted between 2 and 3 of the |
|
|
|
|
|
|
| indoor terminal block, replace the |
|
|
|
|
|
|
| outdoor P.C. board. |
|
|
|
|
|
|
| If the signal stops between them, |
|
|
|
|
|
|
| replace the indoor P.C. board. |
|
|
| The discharge temperature is | All off | The lamp on the | 1. | Check the heat exchanger sensor (TD). |
|
|
| over 120°C. |
| indoor unit blinks | 2. | Gas purging |
|
|
|
|
| when error is |
|
|
|
|
|
|
| defected. |
|
|
|
|
|
|
|
|
| |
|
|
| The IOL operation is defective. | All off | The lamp on the | When turning on the unit, the normal | |
|
|
|
|
| indoor unit blinks | phase (RST) is detected but | |
|
|
|
|
| when error is | has not been detected for 120 seconds or | |
|
|
|
|
| detected. | more. | |
|
|
|
|
|
|
|
|
– 48 –