GE 4100, 6100 Up-Front Air Filters, Concealed Manual Vent Control, Corrosion Protection Optional

Page 11

Features and Benefits

Up-Front Air Filters

Two interchangeable up-front filters, easy to remove and reinstall, may be cleaned without opening or removing the room front.

Clean filters by brushing, vacuuming or back- flushing under faucet or shower head.

Concealed Manual

Vent Control

Open ventilation doors on GE Zoneline® Packaged Terminal Air Conditioners and Heat Pumps allow

outside air to enter the room through a screen-covered opening in the weather barrier that separates the indoor and outdoor sections of the unit.

A concealed lever is located along the left side of the unit under the front cover is used to open and close the vent door.

The 3-position manual vent door control may be closed, partially open or fully open. Positive vent door closure prevents accidental opening and unwanted air infiltration.

Vent CFM High Speed

Unit

Full Open

Partial Open

  7000

50

40

  9000

70

45

12000

75

45

15000

75

45

CFM ratings at 230 and 265 volts.

For each CFM of air to enter the room, an equal amount of air must be removed through exhaust fans in the bathroom or roof tops. Greater amounts of air will be introduced (from chart shown above) depending on the size of the exhaust fan.

Outside ambient air entering the room through this screened vent opening is not conditioned. This unconditioned air becomes mixed with the conditioned air that is circulated by the indoor fan. This air mixture generates an additional heat load/heat loss that causes the unit to run longer and may translate into higher operating costs.

Zoneline vent openings are not intended to be the source of make-up air for building ventilation systems due to the additional heating or cooling loads generated.

geappliances.com

Corrosion Protection (Optional)

4100 and 6100 Series units may be ordered with special protection to better withstand damage from salt air and salt water in seacoast areas.

Corrosion protection is standard on the Dry Air 25 models.

Heat pump units with ICR are not available with corrosion protection and should not be installed in seacoast or corrosive environments.

Units installed in corrosive areas should use the RAB77 wall sleeve and be examined/cleaned more frequently than normal installations.

Internal Condensate Removal (ICR)

See page 34 for a discussion of the Internal Condensate Removal system available on 6100 Series heat pumps.

Enhanced Dehumidification

Moisture removal is an important function of an air conditioner. People are more comfortable at higher temperatures when the humidity level is relatively low. Air conditioners operate with less energy consumption when the room temperatures are set higher.

The GE Zoneline 4100 Series with the Dry Air 25 heat pipe application removes 25% more moisture than the base 4100 Series unit.

The GE Zoneline Dry Air 25 chassis is the only PTAC available with the application of the patented Dinh® Dehumidifier Heat Pipe under license from Heat Pipe Technology, Inc.

Customers who are using the Dry Air 25 report a fresher- smelling room as a result of the lower humidity levels, as well as lower operating costs.

Locking Door Kit

RAK8023 — A door with a lock that replaces the standard control cover door to prevent unauthorized changing of control setting is offered as an accessory.

11

Image 11
Contents GE Zoneline packaged terminal air conditioners 6100 Series Control Panel Quick ReferenceVolt Sub-Base and Direct Connected Units Power Connection KitsZoneline Chassis Nomenclature 230/208-Volt Line Cord Connection UnitsCooling With Resistance Heat Deluxe Dry Air 25 ModelsTable of Contents Advantages of the GE Zoneline System Deluxe Line Standard FeaturesDeluxe Line Optional Features IntroductionZoneline System Optional Accessories of the Zoneline SystemResistance heat Zoneline FeaturesFeatures and Benefits Electronic Temperature Limiting Fan-Only Setting HIGH/LOWFan-Cycle Switch SmartFan Compressor Restart DelayInternal Condensate Removal ICR Up-Front Air FiltersConcealed Manual Vent Control Corrosion Protection OptionalPress AUX SET AU appears on the display Auxiliary Control SettingsAuxiliary Control-Aux Set Button To change modesTemperature limits-Cool Important CDC Comments all series applicable CDC Terminal Location and Typical WiringCentral Desk Control RAK806 Universal Control Cover Label Field Wiring TerminalRemote Thermostat Control Resistance Heat ModelsRAK148D1 RAK148P1 Feature Heat Pump Electric HeatHeat Pump Models For remote thermostat operation follow the steps below Zoneline SeriesType Function Low-Voltage ConductorsBalance Point Heat Pumps and Energy SavingsHeat pump condensate Heat Pump Operation Zoneline 6100 SeriesZoneline Heat Pump Heat Source Logic Heat pump defrost Zoneline 6100 SeriesHigh Wall Mount For units Application CommentsAir Distribution 16-1/2 MIN. x 42-3/8 MIN DimensionsAdditional 16-1/4 MIN. x 42-1/4 MINChoice of wall cases is available for Zoneline units RAK204U No receptacle, no wiring will accept anyWall Case Sub-BaseSub-bases for the 265-volt units Wall Case Installation DataGeneral Brick, Frame, Stucco Shingle Construction Architectural Window Louver InstallationWindow, Curtain and Panel Wall Construction Masonry Wall ConstructionCase Angles Installation of Wall Case in Wall OpeningPreparation of the Wall Case for All Types of Construction Brick Veneer and Frame Construction Framing for Wall CaseWall Section Detailed Side View Frame and Brick Veneer Installation Cord set connectedWall Case Receptacle Wall Case Installation Cord SET Connected AS Reqd Geappliances.com TOP View RAB71A/77 Wall Case RAK204 Series SUB-BASE Installation and Electrical DataCondensate Disposal Systems External Drain. See page 36 for internal drain Wall Case with RAD10 Drain KITInternal Drain. See page 35 for external drain Ducted Application Considerations Ducted InstallationsNew Ducted Installations Replacements of Existing Ducted UnitsDuct Adapter Extension has 1/2 Insulation Com RAG63 Bittersweet Chocolate Exterior GrillesOutdoor Grille Exterior Architectural Treatments Special Outdoor Grilles 230/208 Volt Sub-Base and Direct-Connected Units Or 277-Volt Unit Installation Permanently Connected Units230/208-Volt Line-Cord Connected Units 230/208-Volt Permanently Connected UnitsEssential Elements Ordering Overview Electrical Wiring Information 4100/6100 SeriesReplacement of Existing Chassis Volt Units Maximum Connected LoadLatent System Capacity Normal Yearly Operating Data Formula for Calculating Operating Costs Using Above DataTypical 4100 Series, 230/208-Volt Wiring Diagram Typical 4100 Series, 230/208-Volt Schematic Diagram Typical 6100 Series, 230/208-Volt Wiring Diagram Typical 6100 Series, 230/208-Volt Schematic Diagram Each shall consist of the following sections and components Suggested Bid Form SpecificationsAlternate specification for molded wall case 6 1 H 1 2 D a D Receptacles/Sub-BasesCapacity Preliminary SpecificationsKit Number Description Complete Accessory ListGeneral Installation Suggestions New Installations Zoneline WarrantyDucted Installation Comments Replacement InstallationsGeappliances.com Page Beige Maple Bittersweet Alphabetical IndexExterior Grille Color Samples CategoryYears of innovation and we’re just getting started