GE 6100, 4100 manual AS Reqd

Page 30

30

METAL CASE EXTENSION FOR WALLS DEEPER THAN 13-1/8" (11-1/8" WITH SUB-BASE)

Field fabricated – ge recommends the use of one of the deeper RAB71 wall cases offered as special order items.

Zoneline units can be installed in walls of greater depth than the wall case. Where the case recession is less than 3" and where it is possible to waterproof the exposed sides and top of the opening, the suggested procedure is to apply a flashing to the bottom of the wall case as shown on page 31. Where waterproofing is questionable or not possible, or for installations in walls of greater depth, the following is a suggested application procedure. It involves the field fabrication of a case extension. Since the wall case is a water-bearing container, the extension likewise must also be water- bearing and the connection between the two must be watertight. The case extension must contain splitters to prevent recirculation of the outdoor air circuit.

1.The case extension is field fabricated. The extension depth “D” should allow for a minimum outdoor projection of 1/4". This allows for room cabinet clearance to the finished wall and ample surfaces to apply sealant or caulking for a tight weather seal between the completed wall case/extension assembly and the wall opening. It is recommended that the extension be painted and corner and lap joints be additionally sealed with a quality-grade sealant.

2.The wall case and extension should be connected prior to installation in the wall opening. A quality- grade sealant should be applied to all four (4) butting flanges. Use bolts and nuts or oversized self-tapping screws (driven from the wall case to the extension) to attach the two assemblies. Clean all drain holes of excess sealant. The assembly must be free draining.

3.Install flashing, using a quality-grade sealant between the flashing and wall as shown in section A-A below.

4.Install the wall case/extension assembly following procedures described for a standard installation. See diagrams below. The assembly should be sealed or caulked to the wall around all four sides both outdoors and indoors.

NOTE: The wall case/extension assembly should be level.

6-1/4" ± 1/4"

AS REQ'D.

SEALANT - ALL

 

 

D

 

 

 

 

 

 

 

 

 

FOUR (4) FLANGES

 

 

 

 

 

5.Suggested materials for case extension and flashing should be non-ferrous metals. Minimal acceptable material: Galvanized G-90 painted.

 

WALL -

 

ANY

CAULK*

CONSTRUCTION

ROOM

 

RAB71A/77

CASE

CABINET

 

 

EXT.

 

 

 

 

 

 

 

 

1/4" MIN.

CAULK*

CAULK*

SPLITTER BETWEEN

AIR INTAKE AND

DISCHARGE

 

 

CUT DRAIN SLOTS

 

1-1/2"

IN BOTH FLANGES

 

(FOUR REQUIRED)

RAB71A/77

(4 SIDES)

TO MATCH DRAIN

WALL CASE

EXTENSION

HOLES IN RAB71A/77

 

(FIELD

 

 

SUPPLIED)

 

CAULK*

SEE DETAIL

SECTION A-A

*Caulk around perimeter of wall case all four sides where it joins the building - Interior and Exterior.

SECTION A-A

BASEPAN/FLANGE DESIGN

SHOWING SEALANT LOCATIONS.

ALL 4 FLANGES

EXTENSION

 

WALL CASE

 

2" MIN.

FLASHING (FIELD SUPPLIED)

13-3/4" + D"

ALL 4

SIDES

FLANGES AND

DRAIN HOLE

LOCATIONS

SAME AS ON

WALL CASE

1" WIDE

45° DRIP LIP

FLASHING

ALL 4

SIDES

 

WALL

 

Image 30
Contents GE Zoneline packaged terminal air conditioners Quick Reference 6100 Series Control Panel230/208-Volt Line Cord Connection Units Power Connection KitsZoneline Chassis Nomenclature Volt Sub-Base and Direct Connected UnitsDeluxe Dry Air 25 Models Cooling With Resistance HeatTable of Contents Introduction Deluxe Line Standard FeaturesDeluxe Line Optional Features Advantages of the GE Zoneline SystemOptional Accessories of the Zoneline System Zoneline SystemZoneline Features Resistance heatFeatures and Benefits Compressor Restart Delay Fan-Only Setting HIGH/LOWFan-Cycle Switch SmartFan Electronic Temperature LimitingCorrosion Protection Optional Up-Front Air FiltersConcealed Manual Vent Control Internal Condensate Removal ICRTo change modes Auxiliary Control SettingsAuxiliary Control-Aux Set Button Press AUX SET AU appears on the displayTemperature limits-Cool CDC Terminal Location and Typical Wiring Central Desk ControlImportant CDC Comments all series applicable Resistance Heat Models Field Wiring TerminalRemote Thermostat Control RAK806 Universal Control Cover LabelFeature Heat Pump Electric Heat Heat Pump ModelsRAK148D1 RAK148P1 Low-Voltage Conductors Zoneline SeriesType Function For remote thermostat operation follow the steps belowHeat Pumps and Energy Savings Balance PointHeat pump defrost Zoneline 6100 Series Heat Pump Operation Zoneline 6100 SeriesZoneline Heat Pump Heat Source Logic Heat pump condensateApplication Comments Air DistributionHigh Wall Mount For units 16-1/4 MIN. x 42-1/4 MIN DimensionsAdditional 16-1/2 MIN. x 42-3/8 MINSub-Base RAK204U No receptacle, no wiring will accept anyWall Case Choice of wall cases is available for Zoneline unitsWall Case Installation Data GeneralSub-bases for the 265-volt units Masonry Wall Construction Architectural Window Louver InstallationWindow, Curtain and Panel Wall Construction Brick, Frame, Stucco Shingle ConstructionInstallation of Wall Case in Wall Opening Preparation of the Wall Case for All Types of ConstructionCase Angles Framing for Wall Case Brick Veneer and Frame ConstructionFrame and Brick Veneer Installation Cord set connected Wall Section Detailed Side ViewWall Case Receptacle Wall Case Installation Cord SET Connected AS Reqd Geappliances.com TOP View RAK204 Series SUB-BASE Installation and Electrical Data RAB71A/77 Wall CaseCondensate Disposal Systems Wall Case with RAD10 Drain KIT External Drain. See page 36 for internal drainInternal Drain. See page 35 for external drain Replacements of Existing Ducted Units Ducted InstallationsNew Ducted Installations Ducted Application ConsiderationsDuct Adapter Extension has 1/2 Insulation Com Exterior Grilles Outdoor GrilleRAG63 Bittersweet Chocolate Exterior Architectural Treatments Special Outdoor Grilles 230/208-Volt Permanently Connected Units Or 277-Volt Unit Installation Permanently Connected Units230/208-Volt Line-Cord Connected Units 230/208 Volt Sub-Base and Direct-Connected UnitsElectrical Wiring Information 4100/6100 Series Replacement of Existing ChassisEssential Elements Ordering Overview Maximum Connected Load Latent System CapacityVolt Units Formula for Calculating Operating Costs Using Above Data Normal Yearly Operating DataTypical 4100 Series, 230/208-Volt Wiring Diagram Typical 4100 Series, 230/208-Volt Schematic Diagram Typical 6100 Series, 230/208-Volt Wiring Diagram Typical 6100 Series, 230/208-Volt Schematic Diagram Suggested Bid Form Specifications Each shall consist of the following sections and componentsAlternate specification for molded wall case Receptacles/Sub-Bases 6 1 H 1 2 D a DPreliminary Specifications CapacityComplete Accessory List Kit Number DescriptionGeneral Installation Suggestions Replacement Installations Zoneline WarrantyDucted Installation Comments New InstallationsGeappliances.com Page Category Alphabetical IndexExterior Grille Color Samples Beige Maple BittersweetYears of innovation and we’re just getting started