GE 6100, 4100 manual Heat Pumps and Energy Savings, Balance Point

Page 18

Heat Pumps and Energy Savings

GE Zoneline® heat pumps are designed to provide cost-efficient heat pump operation while monitoring room conditions to maintain comfort.

The units employ a logic system monitoring both outdoor and indoor temperatures to determine the heat source, thus increasing energy savings by operating longer in the heat pump mode.

Heat pumps save energy and cost less to operate than units with electric resistance heaters as the only heat source. Just as the EER of an air conditioner is an indication of the efficiency of the unit, COP (Coefficient of Performance) is the indication of the efficiency of the heat pump. This relative efficiency of a heat pump compares the unit to electric resistance heat. If a unit has a COP of 3.0, it means the

unit will produce three times as much heat at rating conditions for the same electrical input wattage used for electric resistance heat.

The compressor is used in heat pump operation just as in air conditioning operation. In heat pump operation, the hot refrigerant gas is directed to the indoor coil rather than to the outdoor coil. Room air that circulates over the indoor coil gains heat from the coil rather than losing heat to the coil as during cooling operation.

As the outdoor temperature falls, the heat pump is able to extract less heat from the outdoor air to raise the temperature of the indoor air. For this reason, all packaged terminal heat pumps also have electric resistance heaters as backup to heat pump operation. At some point, the heat pump is unable to provide sufficient heat to adequately warm the room. Many Packaged Terminal Heat Pumps cease heat pump operation and change to more expensive resistance heat at some pre-determined outdoor temperature to compensate for

the inability of the heat pump to maintain room temperature. This point, called the “switchover point,” is usually at an outdoor temperature where savings from heat pump operation may still be realized if the unit is designed to maintain room comfort at the lower outdoor temperatures.

Balance Point

An important consideration in the selection of a heat pump unit is the “balance point” of the installation. Virtually every room is unique—with different insulation, different sizes and types of windows, different types of construction, different directional exposures. All these variables, as well as geographical location, must be considered in order to determine the balance point, the point at which the heat pump is unable to produce enough heat to compensate for the heat loss of the room or area being heated. For these reasons a consulting engineer should be engaged to calculate the heat loss and specify the heat pump unit required.

GE offers the 6100 series of Zoneline heat pump units—with highly featured microprocessor controls—react to the indoor temperature as well as the outdoor temperature in determining the heat source to provide comfortable room conditions and energy savings. This determination of the heat source based on the indoor temperature helps provide a more comfortable room.

18

Image 18
Contents GE Zoneline packaged terminal air conditioners Quick Reference 6100 Series Control Panel230/208-Volt Line Cord Connection Units Power Connection KitsZoneline Chassis Nomenclature Volt Sub-Base and Direct Connected UnitsDeluxe Dry Air 25 Models Cooling With Resistance HeatTable of Contents Introduction Deluxe Line Standard FeaturesDeluxe Line Optional Features Advantages of the GE Zoneline SystemOptional Accessories of the Zoneline System Zoneline SystemZoneline Features Resistance heatFeatures and Benefits Compressor Restart Delay Fan-Only Setting HIGH/LOWFan-Cycle Switch SmartFan Electronic Temperature LimitingCorrosion Protection Optional Up-Front Air FiltersConcealed Manual Vent Control Internal Condensate Removal ICRTo change modes Auxiliary Control SettingsAuxiliary Control-Aux Set Button Press AUX SET AU appears on the displayTemperature limits-Cool CDC Terminal Location and Typical Wiring Central Desk ControlImportant CDC Comments all series applicable Resistance Heat Models Field Wiring TerminalRemote Thermostat Control RAK806 Universal Control Cover LabelFeature Heat Pump Electric Heat Heat Pump ModelsRAK148D1 RAK148P1 Low-Voltage Conductors Zoneline SeriesType Function For remote thermostat operation follow the steps belowHeat Pumps and Energy Savings Balance PointHeat pump defrost Zoneline 6100 Series Heat Pump Operation Zoneline 6100 SeriesZoneline Heat Pump Heat Source Logic Heat pump condensateApplication Comments Air DistributionHigh Wall Mount For units 16-1/4 MIN. x 42-1/4 MIN DimensionsAdditional 16-1/2 MIN. x 42-3/8 MINSub-Base RAK204U No receptacle, no wiring will accept anyWall Case Choice of wall cases is available for Zoneline unitsWall Case Installation Data GeneralSub-bases for the 265-volt units Masonry Wall Construction Architectural Window Louver InstallationWindow, Curtain and Panel Wall Construction Brick, Frame, Stucco Shingle ConstructionInstallation of Wall Case in Wall Opening Preparation of the Wall Case for All Types of ConstructionCase Angles Framing for Wall Case Brick Veneer and Frame ConstructionFrame and Brick Veneer Installation Cord set connected Wall Section Detailed Side ViewWall Case Receptacle Wall Case Installation Cord SET Connected AS Reqd Geappliances.com TOP View RAK204 Series SUB-BASE Installation and Electrical Data RAB71A/77 Wall CaseCondensate Disposal Systems Wall Case with RAD10 Drain KIT External Drain. See page 36 for internal drainInternal Drain. See page 35 for external drain Replacements of Existing Ducted Units Ducted InstallationsNew Ducted Installations Ducted Application ConsiderationsDuct Adapter Extension has 1/2 Insulation Com Exterior Grilles Outdoor GrilleRAG63 Bittersweet Chocolate Exterior Architectural Treatments Special Outdoor Grilles 230/208-Volt Permanently Connected Units Or 277-Volt Unit Installation Permanently Connected Units230/208-Volt Line-Cord Connected Units 230/208 Volt Sub-Base and Direct-Connected UnitsElectrical Wiring Information 4100/6100 Series Replacement of Existing ChassisEssential Elements Ordering Overview Maximum Connected Load Latent System CapacityVolt Units Formula for Calculating Operating Costs Using Above Data Normal Yearly Operating DataTypical 4100 Series, 230/208-Volt Wiring Diagram Typical 4100 Series, 230/208-Volt Schematic Diagram Typical 6100 Series, 230/208-Volt Wiring Diagram Typical 6100 Series, 230/208-Volt Schematic Diagram Suggested Bid Form Specifications Each shall consist of the following sections and componentsAlternate specification for molded wall case Receptacles/Sub-Bases 6 1 H 1 2 D a DPreliminary Specifications CapacityComplete Accessory List Kit Number DescriptionGeneral Installation Suggestions Replacement Installations Zoneline WarrantyDucted Installation Comments New InstallationsGeappliances.com Page Category Alphabetical IndexExterior Grille Color Samples Beige Maple BittersweetYears of innovation and we’re just getting started