GE 4100, 6100 manual New Ducted Installations, Ducted Application Considerations, Components

Page 37

Ducted Installations

4100 and 6100 Series Zoneline® units may be used in ducted installations.

With a ducted installation it is possible to condition the air in two areas that have a common wall separating them. A special adapter mounts on the wall case and a transition piece directs the air from the unit into the adapter. Instructions for mounting the adapter to the wall case are included with the duct adapter. The adapter contains a grille that allows air from the unit to be discharged into the primary room and the adapter connects to a duct extension that allows the air to flow to the adjoining room. Ducting

a unit may allow a single unit to be used rather than a separate unit in each room, providing a means of reducing initial equipment cost. The duct may extend a total of 15 feet (with a field-fabricated insulated duct extension) in one direction, either to the right or to the left of the unit. A baffle in the adapter allows up to 50% of the discharge air to be delivered to the secondary room.

The installation of the wall case and sub-base, if used, is the same for units being ducted as for free-standing units. The duct adapter support bracket overlaps the wall case by 1" and the bracket and mounting screws add approximately 3/8" (3/16" on each side) to the width of the wall case. If less than 1" of the wall case projects into the room it will be necessary to allow for the additional width in the opening for the wall case. The duct adapter mounting brackets should be mounted prior to installing the case in the wall.

Refer to pages 38 and 39 for drawings of ducted installations.

Prior to the installation of the transition from the room cabinet to the adapter, it will be necessary to remove the discharge grille from the room cabinet. Instructions for this modification are included with the duct adapter.

New Ducted Installations

Components

Duct Adapter RAK6052

Duct Adapter RAK6052 — The duct adapter is secured to each side of the wall case and requires the drilling of mounting holes in the wall case during installation. A template for the hole location is in the installation instructions. By securing the duct adapter to the wall case, the chassis retains the slide-out feature for servicing after the transition piece is removed.

Duct Extension RAK601 — This kit contains a 44"-long insulated duct, a register mounting collar, and an air supply register. It can be secured to the duct adapter at either end of the adapter. This duct may be cut at any dimension and used in two applications providing the sum of the two duct lengths necessary does not exceed the 44" length. Even in single applications the mounting flange must be cut off one end of the duct to accept the collar and supply register.

geappliances.com

RAK601 Duct Extension, Mounting Collar and Register

Mounting Collar and Supply Register RAK602 —These components are included in the Duct Extension Kit RAK601. They may be ordered separately for installations where two duct extensions are made from one RAK601.

Ducted Application Considerations

When designing a ducted application, some application considerations to be made include:

1.Do not exceed the 15-foot-length maximum for the duct extension. Field-supplied duct extension must be completely insulated with minimum of 1/2" insulation

2.The duct must be a straight run. Turns or bends in the duct extension create air pressure drops that the unit is not designed to overcome.

3.Turn the “Duct Mode” on in the auxiliary control settings (Mode 7). This increases the fan speed to ensure proper circulation.

4.Minimum recommended clearance between the unit and the adjacent wall is 2”.

5.Provisions for return air must be made to allow air circulation from secondary room. Doors in both secondary and primary rooms may be undercut or a return grille may be installed through a common wall.

6.When calculating the heat gain/heat loss take both areas into consideration.

Replacements of Existing Ducted Units

Since the design of the Zoneline chassis has changed over the years to provide better performance and appearance, some of the components used in ducted applications have changed. Select the proper components from the information below. The best procedure in determining the correct kit is to measure duct extension cross section.

Flat-Top Discharge Units (Zoneline Units Built Prior to 1988)

Existing Duct Extension Cross Section Measurements: 8-3/8" height x 6-1/2" width

Duct Adapter RAK7012 — This duct adapter will allow the replacement of a new chassis (4100 or 6100 Series unit) into an existing ducted application. This adapter will align properly with the duct extension and will eliminate the need to modify the wall opening. In order to minimize replacement costs, some of the components of the old duct adapter must be removed and used in the new installation. Consult the Installation Instructions of the RAK7012 before removing and discarding the old duct adapter. See additional notes page 56.

Slope-Front Discharge Units

(Models With AZC, AZR, AZW, or AZ21 or AZ31 Prefix)

Existing Duct Extension Cross Section Measurements: 7-3/32" height x 6-1/2" width

Duct Transition RAK7022 — This duct transition will allow the replacement of a new slope-front discharge Zoneline chassis

(4100 or 6100 Series unit) into a previous-design slope-front

37

ducted installation. See additional notes page 56.

Image 37
Contents GE Zoneline packaged terminal air conditioners 6100 Series Control Panel Quick ReferenceZoneline Chassis Nomenclature Power Connection Kits230/208-Volt Line Cord Connection Units Volt Sub-Base and Direct Connected UnitsCooling With Resistance Heat Deluxe Dry Air 25 ModelsTable of Contents Deluxe Line Optional Features Deluxe Line Standard FeaturesIntroduction Advantages of the GE Zoneline SystemZoneline System Optional Accessories of the Zoneline SystemResistance heat Zoneline FeaturesFeatures and Benefits Fan-Cycle Switch SmartFan Fan-Only Setting HIGH/LOWCompressor Restart Delay Electronic Temperature LimitingConcealed Manual Vent Control Up-Front Air FiltersCorrosion Protection Optional Internal Condensate Removal ICRAuxiliary Control-Aux Set Button Auxiliary Control SettingsTo change modes Press AUX SET AU appears on the displayTemperature limits-Cool Central Desk Control CDC Terminal Location and Typical WiringImportant CDC Comments all series applicable Remote Thermostat Control Field Wiring TerminalResistance Heat Models RAK806 Universal Control Cover LabelHeat Pump Models Feature Heat Pump Electric HeatRAK148D1 RAK148P1 Type Function Zoneline SeriesLow-Voltage Conductors For remote thermostat operation follow the steps belowBalance Point Heat Pumps and Energy SavingsZoneline Heat Pump Heat Source Logic Heat Pump Operation Zoneline 6100 SeriesHeat pump defrost Zoneline 6100 Series Heat pump condensateAir Distribution Application CommentsHigh Wall Mount For units Additional Dimensions16-1/4 MIN. x 42-1/4 MIN 16-1/2 MIN. x 42-3/8 MINWall Case RAK204U No receptacle, no wiring will accept anySub-Base Choice of wall cases is available for Zoneline unitsGeneral Wall Case Installation DataSub-bases for the 265-volt units Window, Curtain and Panel Wall Construction Architectural Window Louver InstallationMasonry Wall Construction Brick, Frame, Stucco Shingle ConstructionPreparation of the Wall Case for All Types of Construction Installation of Wall Case in Wall OpeningCase Angles Brick Veneer and Frame Construction Framing for Wall CaseWall Section Detailed Side View Frame and Brick Veneer Installation Cord set connectedWall Case Receptacle Wall Case Installation Cord SET Connected AS Reqd Geappliances.com TOP View RAB71A/77 Wall Case RAK204 Series SUB-BASE Installation and Electrical DataCondensate Disposal Systems External Drain. See page 36 for internal drain Wall Case with RAD10 Drain KITInternal Drain. See page 35 for external drain New Ducted Installations Ducted InstallationsReplacements of Existing Ducted Units Ducted Application ConsiderationsDuct Adapter Extension has 1/2 Insulation Com Outdoor Grille Exterior GrillesRAG63 Bittersweet Chocolate Exterior Architectural Treatments Special Outdoor Grilles 230/208-Volt Line-Cord Connected Units Or 277-Volt Unit Installation Permanently Connected Units230/208-Volt Permanently Connected Units 230/208 Volt Sub-Base and Direct-Connected UnitsReplacement of Existing Chassis Electrical Wiring Information 4100/6100 SeriesEssential Elements Ordering Overview Latent System Capacity Maximum Connected LoadVolt Units Normal Yearly Operating Data Formula for Calculating Operating Costs Using Above DataTypical 4100 Series, 230/208-Volt Wiring Diagram Typical 4100 Series, 230/208-Volt Schematic Diagram Typical 6100 Series, 230/208-Volt Wiring Diagram Typical 6100 Series, 230/208-Volt Schematic Diagram Each shall consist of the following sections and components Suggested Bid Form SpecificationsAlternate specification for molded wall case 6 1 H 1 2 D a D Receptacles/Sub-BasesCapacity Preliminary SpecificationsKit Number Description Complete Accessory ListGeneral Installation Suggestions Ducted Installation Comments Zoneline WarrantyReplacement Installations New InstallationsGeappliances.com Page Exterior Grille Color Samples Alphabetical IndexCategory Beige Maple BittersweetYears of innovation and we’re just getting started