GE 4100 manual Heat Pump Operation Zoneline 6100 Series, Zoneline Heat Pump Heat Source Logic

Page 19

Heat Pumps and Energy Savings

Heat Pump Operation — Zoneline 6100 Series

Heat sources: Heat pump, heat pump and simultaneous electric resistance heat or electric resistance heat.

Zoneline heat pumps employ a highly featured microprocessor control system interfaced with thermistors to accurately measure indoor air temperature, outdoor air temperature, indoor coil temperature and outdoor coil temperature. This system allows the microprocessor to precisely and predictably react to changing conditions in order to provide a very advanced packaged terminal heat pump operating system.

The Zoneline heat pumps are designed to help ensure a comfortable room. When “HEAT” is selected, the unit will determine if the room air is warm enough to satisfy the thermostat setting. If the temperature at the unit sensor is below the desired temperature, the electric resistance heater will be utilized to warm the room to the point where the thermostat is satisfied. This feature is designed to allow the temperature of an unoccupied room to be maintained at an energy-saving level without inconveniencing the room occupant. Once the thermostat has been satisfied, the resistance heater will turn off and the heat pump will operate as shown in the Heat Source Logic chart until the thermostat calls for heat again. The unit will operate in this manner even if connected to a Central Desk Control.

Zoneline Heat Pump Heat Source Logic

ROOM

 

 

Below

TEMPERATURE

Above

Between 46°F

25°F

VS. THERMOSTAT

46°F

and 25°F

 

SET POINT

 

 

 

 

 

 

 

Less Than

Heat Pump

Heat Pump*

Full Resistance

1.8°F Below

Heat

 

 

 

 

 

 

1.8°F to 2.7°F

 

Heat Pump +

Full Resistance

Heat Pump

Supplemental

Below

Heat

 

Heater

 

 

 

 

 

 

 

More than 2.7°F

Heat Pump

Full Resistance

Full Resistance

Below

Heat

Heat

 

 

 

 

 

The Boost Heat option utilizes the supplemental simultaneous heater at the same time as heat pump operation when the outdoor temperature is below 46°F regardless of the indoor air temperature**. The chart above indicates the heat source of the heat pump under various indoor and outdoor conditions. The unit is designed to provide heat pump savings without sacrificing room comfort.

The Quick Heat Recovery feature is not affected by the Heat Source Logic shown in the chart below. For more information about the Quick Heat Recovery Feature, see page 9. The full heat output of the resistance heater is dependent upon circuit amperage and the power connection kit used. See pages 3 and 42–43 for information on power connection kits and available heater capacities.

geappliances.com

An option is provided in the auxiliary controls (Mode 8) to allow the unit to operate only in resistance heat. The use of this option significantly increases the cost for heating.

Heat pump defrost — Zoneline 6100 Series

Zoneline heat pumps utilize a reverse-cycle demand defrost system to extend heat pump operation and increase savings from extended operation. The microprocessor

determines the need for defrosting by criteria based on continuous compressor running time, outdoor air temperature, outdoor coil temperature and the rate of temperature change of the outdoor coil. When defrosting

is required, the unit reverses the flow of refrigerant to direct the hot gas into the outdoor coil to melt the frost buildup. Before and after the reverse-cycle defrosting, the unit shuts off the compressor to allow the refrigerant pressures

to equalize throughout the system. This eliminates the possibility of a loud reversing noise. During these periods of pressure equalization, the full resistance heat capacity of the unit is activated to help ensure room comfort conditions during the defrost cycle. The unit remains in the defrost cycle for a minimum of two minutes up to a maximum of nine minutes. The defrost cycle terminates when the outdoor coil reaches a temperature of 68°F or the maximum time has been reached.

Heat pump condensate

See page 34 for information on heat pump condensate. The Zoneline 6100 Series heat pumps may be ordered with a factory-installed Internal Condensate Removal (ICR) system to minimize the amount of condensate water draining from the unit during heat pump operation. The ICR system has proven to be an effective means of minimizing the amount of heat pump condensate dripping from the unit. However, if the requirements of a particular installation will allow no dripping of condensate water from the wall case, the installation of an internal or external drain system is recommended.

Units with ICR may not be installed in seacoast or corrosive environment applications.

*If the Boost Heat switch (auxiliary setting #9) is “ON”, the supplemental simultaneous heater will be used with heat pump operation. Simultaneous supplemental heater: 1.0 KW @ 230 V; 0.8 KW @ 208V; 1.0 KW @ 265V.

**Boost Heat option only applies to systems controlled at the unit. Boost Heat option should NOT be used with remote thermostat operation since this will cause the unit to switch to resistance heat when outdoor temperatures are below 46°F.

19

Image 19
Contents GE Zoneline packaged terminal air conditioners 6100 Series Control Panel Quick ReferenceVolt Sub-Base and Direct Connected Units Power Connection KitsZoneline Chassis Nomenclature 230/208-Volt Line Cord Connection UnitsCooling With Resistance Heat Deluxe Dry Air 25 ModelsTable of Contents Advantages of the GE Zoneline System Deluxe Line Standard FeaturesDeluxe Line Optional Features IntroductionZoneline System Optional Accessories of the Zoneline SystemResistance heat Zoneline FeaturesFeatures and Benefits Electronic Temperature Limiting Fan-Only Setting HIGH/LOWFan-Cycle Switch SmartFan Compressor Restart DelayInternal Condensate Removal ICR Up-Front Air FiltersConcealed Manual Vent Control Corrosion Protection OptionalPress AUX SET AU appears on the display Auxiliary Control SettingsAuxiliary Control-Aux Set Button To change modesTemperature limits-Cool Central Desk Control CDC Terminal Location and Typical WiringImportant CDC Comments all series applicable RAK806 Universal Control Cover Label Field Wiring TerminalRemote Thermostat Control Resistance Heat ModelsHeat Pump Models Feature Heat Pump Electric HeatRAK148D1 RAK148P1 For remote thermostat operation follow the steps below Zoneline SeriesType Function Low-Voltage ConductorsBalance Point Heat Pumps and Energy SavingsHeat pump condensate Heat Pump Operation Zoneline 6100 SeriesZoneline Heat Pump Heat Source Logic Heat pump defrost Zoneline 6100 SeriesAir Distribution Application CommentsHigh Wall Mount For units 16-1/2 MIN. x 42-3/8 MIN DimensionsAdditional 16-1/4 MIN. x 42-1/4 MINChoice of wall cases is available for Zoneline units RAK204U No receptacle, no wiring will accept anyWall Case Sub-BaseGeneral Wall Case Installation DataSub-bases for the 265-volt units Brick, Frame, Stucco Shingle Construction Architectural Window Louver InstallationWindow, Curtain and Panel Wall Construction Masonry Wall ConstructionPreparation of the Wall Case for All Types of Construction Installation of Wall Case in Wall OpeningCase Angles Brick Veneer and Frame Construction Framing for Wall CaseWall Section Detailed Side View Frame and Brick Veneer Installation Cord set connectedWall Case Receptacle Wall Case Installation Cord SET Connected AS Reqd Geappliances.com TOP View RAB71A/77 Wall Case RAK204 Series SUB-BASE Installation and Electrical DataCondensate Disposal Systems External Drain. See page 36 for internal drain Wall Case with RAD10 Drain KITInternal Drain. See page 35 for external drain Ducted Application Considerations Ducted InstallationsNew Ducted Installations Replacements of Existing Ducted UnitsDuct Adapter Extension has 1/2 Insulation Com Outdoor Grille Exterior GrillesRAG63 Bittersweet Chocolate Exterior Architectural Treatments Special Outdoor Grilles 230/208 Volt Sub-Base and Direct-Connected Units Or 277-Volt Unit Installation Permanently Connected Units230/208-Volt Line-Cord Connected Units 230/208-Volt Permanently Connected UnitsReplacement of Existing Chassis Electrical Wiring Information 4100/6100 SeriesEssential Elements Ordering Overview Latent System Capacity Maximum Connected LoadVolt Units Normal Yearly Operating Data Formula for Calculating Operating Costs Using Above DataTypical 4100 Series, 230/208-Volt Wiring Diagram Typical 4100 Series, 230/208-Volt Schematic Diagram Typical 6100 Series, 230/208-Volt Wiring Diagram Typical 6100 Series, 230/208-Volt Schematic Diagram Each shall consist of the following sections and components Suggested Bid Form SpecificationsAlternate specification for molded wall case 6 1 H 1 2 D a D Receptacles/Sub-BasesCapacity Preliminary SpecificationsKit Number Description Complete Accessory ListGeneral Installation Suggestions New Installations Zoneline WarrantyDucted Installation Comments Replacement InstallationsGeappliances.com Page Beige Maple Bittersweet Alphabetical IndexExterior Grille Color Samples CategoryYears of innovation and we’re just getting started