Page 31

ALTERNATE – CASE RECESSION LESS THAN 3" WITH SIDES AND TOP OF WALL OPENING WATERPROOF, FLASHING ON BOTTOM ONLY

For an installation that will provide better protection against water infiltration, GE recommends the use of one of the deeper RAB71 Series wall cases offered as special-order items. See page 21.

D

A

A

B

C

B

OUTDOOR

GRILLE

CASEFLASHING

1" WIDE 45° DRIP LIP

31

DIMENSIONS:

A. DISTANCE FROM GRILLE OR CASE TO OUTSIDE SURFACE OF WALL PLUS 2" TO 4" (TO INSERT UNDER CASE).

B. 1" DRIP LIP (MINIMUM)

C. 42" PLUS - SUFFICIENT TO FIT SNUGGLY UNDER AND UP AROUND THE CASE. D. 2" MINIMUM

(CAUTION: WHEN CAULKING DO NOT BLOCK DRAIN HOLES IN CASE OR GRILLE.)

IF GRILLE IS TO BE MOUNTED TO WALL SURFACE A SPLITTERS MUST BE USED, SEE PAGE 30.

*Caulk around perimeter of wall case all four sides where it joins the building - Interior and Exterior.

geappliances.com

Image 31
Contents GE Zoneline packaged terminal air conditioners 6100 Series Control Panel Quick ReferenceVolt Sub-Base and Direct Connected Units Power Connection KitsZoneline Chassis Nomenclature 230/208-Volt Line Cord Connection UnitsCooling With Resistance Heat Deluxe Dry Air 25 ModelsTable of Contents Advantages of the GE Zoneline System Deluxe Line Standard FeaturesDeluxe Line Optional Features IntroductionZoneline System Optional Accessories of the Zoneline SystemResistance heat Zoneline FeaturesFeatures and Benefits Electronic Temperature Limiting Fan-Only Setting HIGH/LOWFan-Cycle Switch SmartFan Compressor Restart DelayInternal Condensate Removal ICR Up-Front Air FiltersConcealed Manual Vent Control Corrosion Protection OptionalPress AUX SET AU appears on the display Auxiliary Control SettingsAuxiliary Control-Aux Set Button To change modesTemperature limits-Cool Central Desk Control CDC Terminal Location and Typical WiringImportant CDC Comments all series applicable RAK806 Universal Control Cover Label Field Wiring TerminalRemote Thermostat Control Resistance Heat ModelsHeat Pump Models Feature Heat Pump Electric HeatRAK148D1 RAK148P1 For remote thermostat operation follow the steps below Zoneline SeriesType Function Low-Voltage ConductorsBalance Point Heat Pumps and Energy SavingsHeat pump condensate Heat Pump Operation Zoneline 6100 SeriesZoneline Heat Pump Heat Source Logic Heat pump defrost Zoneline 6100 SeriesAir Distribution Application CommentsHigh Wall Mount For units 16-1/2 MIN. x 42-3/8 MIN DimensionsAdditional 16-1/4 MIN. x 42-1/4 MINChoice of wall cases is available for Zoneline units RAK204U No receptacle, no wiring will accept anyWall Case Sub-BaseGeneral Wall Case Installation DataSub-bases for the 265-volt units Brick, Frame, Stucco Shingle Construction Architectural Window Louver InstallationWindow, Curtain and Panel Wall Construction Masonry Wall ConstructionPreparation of the Wall Case for All Types of Construction Installation of Wall Case in Wall OpeningCase Angles Brick Veneer and Frame Construction Framing for Wall CaseWall Section Detailed Side View Frame and Brick Veneer Installation Cord set connectedWall Case Receptacle Wall Case Installation Cord SET Connected AS Reqd Geappliances.com TOP View RAB71A/77 Wall Case RAK204 Series SUB-BASE Installation and Electrical DataCondensate Disposal Systems External Drain. See page 36 for internal drain Wall Case with RAD10 Drain KITInternal Drain. See page 35 for external drain Ducted Application Considerations Ducted InstallationsNew Ducted Installations Replacements of Existing Ducted UnitsDuct Adapter Extension has 1/2 Insulation Com Outdoor Grille Exterior GrillesRAG63 Bittersweet Chocolate Exterior Architectural Treatments Special Outdoor Grilles 230/208 Volt Sub-Base and Direct-Connected Units Or 277-Volt Unit Installation Permanently Connected Units230/208-Volt Line-Cord Connected Units 230/208-Volt Permanently Connected UnitsReplacement of Existing Chassis Electrical Wiring Information 4100/6100 SeriesEssential Elements Ordering Overview Latent System Capacity Maximum Connected LoadVolt Units Normal Yearly Operating Data Formula for Calculating Operating Costs Using Above DataTypical 4100 Series, 230/208-Volt Wiring Diagram Typical 4100 Series, 230/208-Volt Schematic Diagram Typical 6100 Series, 230/208-Volt Wiring Diagram Typical 6100 Series, 230/208-Volt Schematic Diagram Each shall consist of the following sections and components Suggested Bid Form SpecificationsAlternate specification for molded wall case 6 1 H 1 2 D a D Receptacles/Sub-BasesCapacity Preliminary SpecificationsKit Number Description Complete Accessory ListGeneral Installation Suggestions New Installations Zoneline WarrantyDucted Installation Comments Replacement InstallationsGeappliances.com Page Beige Maple Bittersweet Alphabetical IndexExterior Grille Color Samples CategoryYears of innovation and we’re just getting started