GE 6100, 4100 manual Internal Drain. See page 35 for external drain

Page 36

36

WALL CASE WITH RAD10 DRAIN KIT

Internal Drain. See page 35 for external drain.

NOTE: SHADED PARTS AND SCREWS

INCLUDED WITH RAD10 DRAIN

KIT.THE 90° ELBOWTUBE IS

RECOMMENDED FOR INTERNAL

DRAIN INSTALLATION.

SCREWS

SEE DETAIL

 

BELOW

“A” “B”

METAL PLASTIC

OVERFLOW RELIEF DRAIN

SEE NOTE 6

SQUARE DRAIN HOLES

NEOPRENE SPONGE GASKET

STEEL MOUNTING PLATE

NUT

(MOLDED CASE (RAB77) ONLY)

DETAIL

USE TYPE “A” SCREW FOR METAL CASE (RAB71)

AND TYPE “B” SCREW FOR MOLDED CASE (RAB77)

GASKET

CABINET BOTTOM

TUBE

1/2" OD

COVER

PLATE

1.The RAD10 drain kit is installed in the bottom of the wall case when it is desired to drain condensate to an internal drain system in the building.

2.The drain kit is mounted on the bottom of the wall case prior to installation of the case in the wall. It may be located anywhere on the room-side portion except for sub-base installations. For these the drain should be at least 3" from the indoor edge of the case so as to adequately clear the sub-base.

3.A template is furnished with the kit for locating the necessary three holes in the case bottom —two to provide a securing means and one to provide a drain hole for the 1/2" OD tubing (see details at left).

4.A tube or hose 1/2" I.D. (obtained locally) must be installed on the drain tube and connected to the internal drain system in the building.

5.With the RAD10 the two square drain holes in the bottom outer flange of the wall case are sealed by the gaskets and mounting plates shown above.

6.Three (3) 1/2" diameter holes located 1/4" above the case bottom in the bottom outer flange provide overflow drainage to the outdoors when wind-driven rain enters the chassis.

USE TYPE “A” SCREWS FOR BOTH RAB71A AND RAB77

Image 36
Contents GE Zoneline packaged terminal air conditioners Quick Reference 6100 Series Control PanelPower Connection Kits Zoneline Chassis Nomenclature230/208-Volt Line Cord Connection Units Volt Sub-Base and Direct Connected UnitsDeluxe Dry Air 25 Models Cooling With Resistance HeatTable of Contents Deluxe Line Standard Features Deluxe Line Optional FeaturesIntroduction Advantages of the GE Zoneline SystemOptional Accessories of the Zoneline System Zoneline SystemZoneline Features Resistance heatFeatures and Benefits Fan-Only Setting HIGH/LOW Fan-Cycle Switch SmartFanCompressor Restart Delay Electronic Temperature LimitingUp-Front Air Filters Concealed Manual Vent ControlCorrosion Protection Optional Internal Condensate Removal ICRAuxiliary Control Settings Auxiliary Control-Aux Set ButtonTo change modes Press AUX SET AU appears on the displayTemperature limits-Cool CDC Terminal Location and Typical Wiring Central Desk ControlImportant CDC Comments all series applicable Field Wiring Terminal Remote Thermostat ControlResistance Heat Models RAK806 Universal Control Cover LabelFeature Heat Pump Electric Heat Heat Pump ModelsRAK148D1 RAK148P1 Zoneline Series Type FunctionLow-Voltage Conductors For remote thermostat operation follow the steps belowHeat Pumps and Energy Savings Balance PointHeat Pump Operation Zoneline 6100 Series Zoneline Heat Pump Heat Source LogicHeat pump defrost Zoneline 6100 Series Heat pump condensateApplication Comments Air DistributionHigh Wall Mount For units Dimensions Additional16-1/4 MIN. x 42-1/4 MIN 16-1/2 MIN. x 42-3/8 MINRAK204U No receptacle, no wiring will accept any Wall CaseSub-Base Choice of wall cases is available for Zoneline unitsWall Case Installation Data GeneralSub-bases for the 265-volt units Architectural Window Louver Installation Window, Curtain and Panel Wall ConstructionMasonry Wall Construction Brick, Frame, Stucco Shingle ConstructionInstallation of Wall Case in Wall Opening Preparation of the Wall Case for All Types of ConstructionCase Angles Framing for Wall Case Brick Veneer and Frame ConstructionFrame and Brick Veneer Installation Cord set connected Wall Section Detailed Side ViewWall Case Receptacle Wall Case Installation Cord SET Connected AS Reqd Geappliances.com TOP View RAK204 Series SUB-BASE Installation and Electrical Data RAB71A/77 Wall CaseCondensate Disposal Systems Wall Case with RAD10 Drain KIT External Drain. See page 36 for internal drainInternal Drain. See page 35 for external drain Ducted Installations New Ducted InstallationsReplacements of Existing Ducted Units Ducted Application ConsiderationsDuct Adapter Extension has 1/2 Insulation Com Exterior Grilles Outdoor GrilleRAG63 Bittersweet Chocolate Exterior Architectural Treatments Special Outdoor Grilles Or 277-Volt Unit Installation Permanently Connected Units 230/208-Volt Line-Cord Connected Units230/208-Volt Permanently Connected Units 230/208 Volt Sub-Base and Direct-Connected UnitsElectrical Wiring Information 4100/6100 Series Replacement of Existing ChassisEssential Elements Ordering Overview Maximum Connected Load Latent System CapacityVolt Units Formula for Calculating Operating Costs Using Above Data Normal Yearly Operating DataTypical 4100 Series, 230/208-Volt Wiring Diagram Typical 4100 Series, 230/208-Volt Schematic Diagram Typical 6100 Series, 230/208-Volt Wiring Diagram Typical 6100 Series, 230/208-Volt Schematic Diagram Suggested Bid Form Specifications Each shall consist of the following sections and componentsAlternate specification for molded wall case Receptacles/Sub-Bases 6 1 H 1 2 D a DPreliminary Specifications CapacityComplete Accessory List Kit Number DescriptionGeneral Installation Suggestions Zoneline Warranty Ducted Installation CommentsReplacement Installations New InstallationsGeappliances.com Page Alphabetical Index Exterior Grille Color SamplesCategory Beige Maple BittersweetYears of innovation and we’re just getting started