Remote Thermostat Control
Heat Pump Models
The Zoneline® 6100 Series heat pump units may be connected to a
6100 series units:
RAK148D1 — | RAK148P1 — |
thermostat | programmable |
requiring six | thermostat |
connection wires. | requiring six |
| connection wires. |
Please see page 55 for installation recommendations for the remote thermostat wiring. Compatibility of other thermostats considered for use with the GE Zoneline unit is the responsibility of the customer.
The control voltage on the remote control conductors is 24 VAC.
The remote
The fan speed for the 6100 Series in remote thermostat operation is selected by the connection of the fan wire from the thermostat to either the HIGH or LOW terminal on the unit. See the sketch of the unit terminals for the location of the HIGH and LOW fan speed terminals. Operating the unit in low fan speed reduces the operating sound level of the unit.
Field Wiring Terminal
R | — 24V AC | GL | — |
GH | — | B | — Reversing Valve |
Y | — Compressor | W | — Heater |
C | — Common |
|
|
Feature | Heat Pump | Electric Heat |
Indoor Frost Control | Yes | Yes |
Freeze Sentinel™ | Yes | Yes |
Heat Sentinel | Yes | Yes |
Auto Fan Speed | No | No |
Electronic |
|
|
Temperature Limiting | No | No |
Switch to Resistance |
|
|
Heat Based on Indoor | Determined by |
|
Temperature | Remote Thermostat | N/A |
Switch to Resistance |
|
|
Heat Based on |
|
|
Outdoor Temperature | Yes | N/A |
Reverse Cycle Defrost | Yes | N/A |
Simultaneous |
|
|
Resistance Heat |
|
|
with Heat Pump | No | N/A |
Resistance Heat |
|
|
Lockout | Yes | N/A |
“Smart Fan” | Fan ON/AUTO Set On | Fan ON/AUTO Set On |
Fan Cycle | Remote Thermostat | Remote Thermostat |
Central Desk Control | Yes | Yes |
When connected to a remote thermostat, the
Boost heat option should not be used with remote thermostat operation since this will cause the unit to switch to resistance heat when outdoor temperatures are below 46ºF.
CDC | R GL GH B Y W C |
Common
White — Heater
Yellow — Compressor
Black — Reversing Valve
Green —
Green —
Red — 24V AC
CDC Terminal