Remote Thermostat Control

Heat Pump Models

The Zoneline® 6100 Series heat pump units may be connected to a single-stage cooling/two-stage heating thermostat designed for use with heat pump systems. GE offers two thermostats compatible with the

6100 series units:

RAK148D1

RAK148P1

solid-state digital

solid-state digital

thermostat

programmable

requiring six

thermostat

connection wires.

requiring six

 

connection wires.

Please see page 55 for installation recommendations for the remote thermostat wiring. Compatibility of other thermostats considered for use with the GE Zoneline unit is the responsibility of the customer.

The control voltage on the remote control conductors is 24 VAC.

The remote thermostat-Class 2 option (Mode 6 in the auxiliary control setting) must be turned ON to enable remote thermostat control. Refer to installation instructions packaged with the chassis.

The fan speed for the 6100 Series in remote thermostat operation is selected by the connection of the fan wire from the thermostat to either the HIGH or LOW terminal on the unit. See the sketch of the unit terminals for the location of the HIGH and LOW fan speed terminals. Operating the unit in low fan speed reduces the operating sound level of the unit.

Field Wiring Terminal

R

— 24V AC

GL

Low-Speed Fan

GH

High-Speed Fan

B

— Reversing Valve

Y

— Compressor

W

— Heater

C

— Common

 

 

Feature

Heat Pump

Electric Heat

Indoor Frost Control

Yes

Yes

Freeze Sentinel

Yes

Yes

Heat Sentinel

Yes

Yes

Auto Fan Speed

No

No

Electronic

 

 

Temperature Limiting

No

No

Switch to Resistance

 

 

Heat Based on Indoor

Determined by

 

Temperature

Remote Thermostat

N/A

Switch to Resistance

 

 

Heat Based on

 

 

Outdoor Temperature

Yes

N/A

Reverse Cycle Defrost

Yes

N/A

Simultaneous

 

 

Resistance Heat

 

 

with Heat Pump

No

N/A

Resistance Heat

 

 

Lockout

Yes

N/A

“Smart Fan”

Fan ON/AUTO Set On

Fan ON/AUTO Set On

Fan Cycle

Remote Thermostat

Remote Thermostat

Central Desk Control

Yes

Yes

When connected to a remote thermostat, the indoor-air- temperature sensing is shifted from the unit to the remote thermostat. For this reason, the units will operate slightly differently when connected to a remote thermostat. The above chart shows the unit operation when connected to a remote thermostat.

Boost heat option should not be used with remote thermostat operation since this will cause the unit to switch to resistance heat when outdoor temperatures are below 46ºF.

CDC

R GL GH B Y W C

Common

White — Heater

Yellow — Compressor

Black — Reversing Valve

Green — High-Speed Fan

Green — Low-Speed Fan

Red — 24V AC

CDC Terminal

16

Image 16
Contents GE Zoneline packaged terminal air conditioners Quick Reference 6100 Series Control PanelPower Connection Kits Zoneline Chassis Nomenclature230/208-Volt Line Cord Connection Units Volt Sub-Base and Direct Connected UnitsDeluxe Dry Air 25 Models Cooling With Resistance HeatTable of Contents Deluxe Line Standard Features Deluxe Line Optional FeaturesIntroduction Advantages of the GE Zoneline SystemOptional Accessories of the Zoneline System Zoneline SystemZoneline Features Resistance heatFeatures and Benefits Fan-Only Setting HIGH/LOW Fan-Cycle Switch SmartFanCompressor Restart Delay Electronic Temperature LimitingUp-Front Air Filters Concealed Manual Vent ControlCorrosion Protection Optional Internal Condensate Removal ICRAuxiliary Control Settings Auxiliary Control-Aux Set ButtonTo change modes Press AUX SET AU appears on the displayTemperature limits-Cool Central Desk Control CDC Terminal Location and Typical WiringImportant CDC Comments all series applicable Field Wiring Terminal Remote Thermostat ControlResistance Heat Models RAK806 Universal Control Cover LabelHeat Pump Models Feature Heat Pump Electric HeatRAK148D1 RAK148P1 Zoneline Series Type FunctionLow-Voltage Conductors For remote thermostat operation follow the steps belowHeat Pumps and Energy Savings Balance PointHeat Pump Operation Zoneline 6100 Series Zoneline Heat Pump Heat Source LogicHeat pump defrost Zoneline 6100 Series Heat pump condensateAir Distribution Application CommentsHigh Wall Mount For units Dimensions Additional16-1/4 MIN. x 42-1/4 MIN 16-1/2 MIN. x 42-3/8 MINRAK204U No receptacle, no wiring will accept any Wall CaseSub-Base Choice of wall cases is available for Zoneline unitsGeneral Wall Case Installation DataSub-bases for the 265-volt units Architectural Window Louver Installation Window, Curtain and Panel Wall ConstructionMasonry Wall Construction Brick, Frame, Stucco Shingle ConstructionPreparation of the Wall Case for All Types of Construction Installation of Wall Case in Wall OpeningCase Angles Framing for Wall Case Brick Veneer and Frame ConstructionFrame and Brick Veneer Installation Cord set connected Wall Section Detailed Side ViewWall Case Receptacle Wall Case Installation Cord SET Connected AS Reqd Geappliances.com TOP View RAK204 Series SUB-BASE Installation and Electrical Data RAB71A/77 Wall CaseCondensate Disposal Systems Wall Case with RAD10 Drain KIT External Drain. See page 36 for internal drainInternal Drain. See page 35 for external drain Ducted Installations New Ducted InstallationsReplacements of Existing Ducted Units Ducted Application ConsiderationsDuct Adapter Extension has 1/2 Insulation Com Outdoor Grille Exterior GrillesRAG63 Bittersweet Chocolate Exterior Architectural Treatments Special Outdoor Grilles Or 277-Volt Unit Installation Permanently Connected Units 230/208-Volt Line-Cord Connected Units230/208-Volt Permanently Connected Units 230/208 Volt Sub-Base and Direct-Connected UnitsReplacement of Existing Chassis Electrical Wiring Information 4100/6100 SeriesEssential Elements Ordering Overview Latent System Capacity Maximum Connected LoadVolt Units Formula for Calculating Operating Costs Using Above Data Normal Yearly Operating DataTypical 4100 Series, 230/208-Volt Wiring Diagram Typical 4100 Series, 230/208-Volt Schematic Diagram Typical 6100 Series, 230/208-Volt Wiring Diagram Typical 6100 Series, 230/208-Volt Schematic Diagram Suggested Bid Form Specifications Each shall consist of the following sections and componentsAlternate specification for molded wall case Receptacles/Sub-Bases 6 1 H 1 2 D a DPreliminary Specifications CapacityComplete Accessory List Kit Number DescriptionGeneral Installation Suggestions Zoneline Warranty Ducted Installation CommentsReplacement Installations New InstallationsGeappliances.com Page Alphabetical Index Exterior Grille Color SamplesCategory Beige Maple BittersweetYears of innovation and we’re just getting started