Exterior Architectural Treatments

and Special Outdoor Grilles

The architectural design of a building may dictate the use of special or oversized louvers for aesthetic reasons. Louvers other than standard Zoneline exterior grilles may be used on the Zoneline unit, however, these special louvers, or any special exterior architectural treatments of the building facade that may restrict the free circulation of condenser airflow, should be referred to GE Application Engineering for evaluation and approval. The following guidelines should be followed in selecting a louver:

1.The louver must have a minimum of 65% free area. ASHRAE defines free area as the minimum area of the opening in an air inlet or outlet through which air can pass. Percent (%) free area equals the X dimension divided by the Y dimension.

2.The louver should be attached to the wall case in a manner that will prevent recirculation of condenser discharge air into the air inlet. If the louver is not attached directly to the wall case, a field-supplied splitter or gasket is required between the chassis and the louver to prevent recirculation.

It is important that the above criteria be followed since a louver that is too restrictive or allows recirculation will reduce the unit’s capacity and efficiency, increase the electrical current draw, cause intermittent operation due to the compressor overload protector shutting the compressor off, and cause failure of the compressor overload and shorten compressor life. Using the unit with a grille that

is too restrictive or allows recirculation may constitute improper installation and will void the unit's warranty. A scale drawing of the louver section should be sent to GE Application Engineering. To assure the proper performance of the Zoneline unit and comply with Underwriters Laboratories requirements, it may be necessary to send a sample louver section (at least 16" x 42") to an independent lab to be tested with the Zoneline unit.

Sample Calculations

 

x

Free Area (%) =

y x 100 x = 1" y = 1.5"

1

F.A. % = 1.5 x 100 = 66.7%

41

Image 41
Contents GE Zoneline packaged terminal air conditioners 6100 Series Control Panel Quick ReferenceZoneline Chassis Nomenclature Power Connection Kits230/208-Volt Line Cord Connection Units Volt Sub-Base and Direct Connected UnitsCooling With Resistance Heat Deluxe Dry Air 25 ModelsTable of Contents Deluxe Line Optional Features Deluxe Line Standard FeaturesIntroduction Advantages of the GE Zoneline SystemZoneline System Optional Accessories of the Zoneline SystemResistance heat Zoneline FeaturesFeatures and Benefits Fan-Cycle Switch SmartFan Fan-Only Setting HIGH/LOWCompressor Restart Delay Electronic Temperature LimitingConcealed Manual Vent Control Up-Front Air FiltersCorrosion Protection Optional Internal Condensate Removal ICRAuxiliary Control-Aux Set Button Auxiliary Control SettingsTo change modes Press AUX SET AU appears on the displayTemperature limits-Cool Important CDC Comments all series applicable CDC Terminal Location and Typical WiringCentral Desk Control Remote Thermostat Control Field Wiring TerminalResistance Heat Models RAK806 Universal Control Cover LabelRAK148D1 RAK148P1 Feature Heat Pump Electric HeatHeat Pump Models Type Function Zoneline SeriesLow-Voltage Conductors For remote thermostat operation follow the steps belowBalance Point Heat Pumps and Energy SavingsZoneline Heat Pump Heat Source Logic Heat Pump Operation Zoneline 6100 SeriesHeat pump defrost Zoneline 6100 Series Heat pump condensateHigh Wall Mount For units Application CommentsAir Distribution Additional Dimensions16-1/4 MIN. x 42-1/4 MIN 16-1/2 MIN. x 42-3/8 MINWall Case RAK204U No receptacle, no wiring will accept anySub-Base Choice of wall cases is available for Zoneline unitsSub-bases for the 265-volt units Wall Case Installation DataGeneral Window, Curtain and Panel Wall Construction Architectural Window Louver InstallationMasonry Wall Construction Brick, Frame, Stucco Shingle ConstructionCase Angles Installation of Wall Case in Wall OpeningPreparation of the Wall Case for All Types of Construction Brick Veneer and Frame Construction Framing for Wall CaseWall Section Detailed Side View Frame and Brick Veneer Installation Cord set connectedWall Case Receptacle Wall Case Installation Cord SET Connected AS Reqd Geappliances.com TOP View RAB71A/77 Wall Case RAK204 Series SUB-BASE Installation and Electrical DataCondensate Disposal Systems External Drain. See page 36 for internal drain Wall Case with RAD10 Drain KITInternal Drain. See page 35 for external drain New Ducted Installations Ducted InstallationsReplacements of Existing Ducted Units Ducted Application ConsiderationsDuct Adapter Extension has 1/2 Insulation Com RAG63 Bittersweet Chocolate Exterior GrillesOutdoor Grille Exterior Architectural Treatments Special Outdoor Grilles 230/208-Volt Line-Cord Connected Units Or 277-Volt Unit Installation Permanently Connected Units230/208-Volt Permanently Connected Units 230/208 Volt Sub-Base and Direct-Connected UnitsEssential Elements Ordering Overview Electrical Wiring Information 4100/6100 SeriesReplacement of Existing Chassis Volt Units Maximum Connected LoadLatent System Capacity Normal Yearly Operating Data Formula for Calculating Operating Costs Using Above DataTypical 4100 Series, 230/208-Volt Wiring Diagram Typical 4100 Series, 230/208-Volt Schematic Diagram Typical 6100 Series, 230/208-Volt Wiring Diagram Typical 6100 Series, 230/208-Volt Schematic Diagram Each shall consist of the following sections and components Suggested Bid Form SpecificationsAlternate specification for molded wall case 6 1 H 1 2 D a D Receptacles/Sub-BasesCapacity Preliminary SpecificationsKit Number Description Complete Accessory ListGeneral Installation Suggestions Ducted Installation Comments Zoneline WarrantyReplacement Installations New InstallationsGeappliances.com Page Exterior Grille Color Samples Alphabetical IndexCategory Beige Maple BittersweetYears of innovation and we’re just getting started