GE 4100, 6100 manual Wall Case with RAD10 Drain KIT, External Drain. See page 36 for internal drain

Page 35
Alternate 6" long, 1/2" O.D. straight copper tube.

WALL CASE WITH RAD10 DRAIN KIT

External Drain. See page 36 for internal drain.

SCREWS

“A” “B”

METAL PLASTIC

SEE PAGE 36 NOTE #6

SQUARE DRAIN HOLES

1/2" O.D. 90° ELBOW DRAIN TUBE

NEOPRENE SPONGE GASKET

NOTE: SHADED PARTS AND SCREWS ARE INCLUDED WITH RAD10 DRAIN KIT. USE EITHERTHE 90° ELBOWTUBE OR THE STRAIGHTTUBE DEPENDING UPON THE REQUIREMENTS OFTHE PARTICULAR INSTALLATION.

TYPICAL INSTALLATION

35

STEEL MOUNTING PLATE

USE TYPE “A” SCREW FOR METAL CASE (RAB71A)

AND TYPE “B” SCREW FOR MOLDED CASE (RAB77)

WATER DRAINAGE - Precipitation entering the unit through the outdoor louver may not be removed entirely by the condensate removal system. The base pan flange is designed to allow excess water, either condensate water or precipitation, to flow into the wall case and drain through two drain holes in the rear of the wall case. If there is more water in the wall case than can be drained through these holes it will drain through the three overflow drain holes. These drain holes must not be blocked when mounting or caulking the wall case.

For those installations where water draining from the drain holes is objectionable or where positive drainage is desired, the RAD10 drain kit is available with either a 90° elbow or a 6" straight tube to be used either to connect to a field- supplied drain line or to allow the water to drip free rather than drain down the surface of the building.

NOTE: Drain kit using either the 90° elbow tube or the straight tube may be installed without modification when using RAG60 exterior grille. Drain kit using the 90° elbow tube may be installed without modification when using RAG61 through RAG63 exterior grilles. Modification must be made to the RAG61 through RAG63 exterior grilles when using the straight tube. Modification must be made to the RAG67 grille if using either the 90° elbow tube or the straight tube (see installation instructions with the RAG67 grille).

Caulk around perimeter of wall case all four sides where it joins the building.

REAR

GRILLE

90° ELBOW DRAIN TUBE

PROJECTION 3"

BEYOND WALL 4"

CASE

CASE ANGLES (FIELD SUPPLIED)

WALL CASE

ROOM

CABINET

MIN. 2 SUPPORTS

FLOOR

FIELD SUPPLIED

 

geappliances.com

Image 35
Contents GE Zoneline packaged terminal air conditioners 6100 Series Control Panel Quick ReferenceVolt Sub-Base and Direct Connected Units Power Connection KitsZoneline Chassis Nomenclature 230/208-Volt Line Cord Connection UnitsCooling With Resistance Heat Deluxe Dry Air 25 ModelsTable of Contents Advantages of the GE Zoneline System Deluxe Line Standard FeaturesDeluxe Line Optional Features IntroductionZoneline System Optional Accessories of the Zoneline SystemResistance heat Zoneline FeaturesFeatures and Benefits Electronic Temperature Limiting Fan-Only Setting HIGH/LOWFan-Cycle Switch SmartFan Compressor Restart DelayInternal Condensate Removal ICR Up-Front Air FiltersConcealed Manual Vent Control Corrosion Protection OptionalPress AUX SET AU appears on the display Auxiliary Control SettingsAuxiliary Control-Aux Set Button To change modesTemperature limits-Cool Important CDC Comments all series applicable CDC Terminal Location and Typical WiringCentral Desk Control RAK806 Universal Control Cover Label Field Wiring TerminalRemote Thermostat Control Resistance Heat ModelsRAK148D1 RAK148P1 Feature Heat Pump Electric HeatHeat Pump Models For remote thermostat operation follow the steps below Zoneline SeriesType Function Low-Voltage ConductorsBalance Point Heat Pumps and Energy SavingsHeat pump condensate Heat Pump Operation Zoneline 6100 SeriesZoneline Heat Pump Heat Source Logic Heat pump defrost Zoneline 6100 SeriesHigh Wall Mount For units Application CommentsAir Distribution 16-1/2 MIN. x 42-3/8 MIN DimensionsAdditional 16-1/4 MIN. x 42-1/4 MINChoice of wall cases is available for Zoneline units RAK204U No receptacle, no wiring will accept anyWall Case Sub-BaseSub-bases for the 265-volt units Wall Case Installation DataGeneral Brick, Frame, Stucco Shingle Construction Architectural Window Louver InstallationWindow, Curtain and Panel Wall Construction Masonry Wall ConstructionCase Angles Installation of Wall Case in Wall OpeningPreparation of the Wall Case for All Types of Construction Brick Veneer and Frame Construction Framing for Wall CaseWall Section Detailed Side View Frame and Brick Veneer Installation Cord set connectedWall Case Receptacle Wall Case Installation Cord SET Connected AS Reqd Geappliances.com TOP View RAB71A/77 Wall Case RAK204 Series SUB-BASE Installation and Electrical DataCondensate Disposal Systems External Drain. See page 36 for internal drain Wall Case with RAD10 Drain KITInternal Drain. See page 35 for external drain Ducted Application Considerations Ducted InstallationsNew Ducted Installations Replacements of Existing Ducted UnitsDuct Adapter Extension has 1/2 Insulation Com RAG63 Bittersweet Chocolate Exterior GrillesOutdoor Grille Exterior Architectural Treatments Special Outdoor Grilles 230/208 Volt Sub-Base and Direct-Connected Units Or 277-Volt Unit Installation Permanently Connected Units230/208-Volt Line-Cord Connected Units 230/208-Volt Permanently Connected UnitsEssential Elements Ordering Overview Electrical Wiring Information 4100/6100 SeriesReplacement of Existing Chassis Volt Units Maximum Connected LoadLatent System Capacity Normal Yearly Operating Data Formula for Calculating Operating Costs Using Above DataTypical 4100 Series, 230/208-Volt Wiring Diagram Typical 4100 Series, 230/208-Volt Schematic Diagram Typical 6100 Series, 230/208-Volt Wiring Diagram Typical 6100 Series, 230/208-Volt Schematic Diagram Each shall consist of the following sections and components Suggested Bid Form SpecificationsAlternate specification for molded wall case 6 1 H 1 2 D a D Receptacles/Sub-BasesCapacity Preliminary SpecificationsKit Number Description Complete Accessory ListGeneral Installation Suggestions New Installations Zoneline WarrantyDucted Installation Comments Replacement InstallationsGeappliances.com Page Beige Maple Bittersweet Alphabetical IndexExterior Grille Color Samples CategoryYears of innovation and we’re just getting started