Suggested Bid Form Specifications
The following are suggested specifications for the Zoneline® 4100 Series Packaged Terminal Air Conditioner and the 6100 Series Packaged Terminal Heat Pump.
The contractor will furnish Packaged Terminal Air Conditioners of the sizes and capacities shown on the schedule and in the specifications. The units shall be located as shown on the drawings and each shall consist of a chassis, room cabinet, wall case,
Units shall be listed by UL, and ARI and cUL certified as to capacity and efficiency and shall be GE Zoneline models or equal. Unit dimensions shall not exceed
Units shall be designed to operate on (208) (230) (265) volts, 60 Hz.,
Chassis. The air conditioner chassis shall be the standard product of the manufacturer and shall be shipped in protective cartons to prevent damage. Cartons shall be appropriately marked at the factory with wording sufficient to warn handlers against improper stacking,
The chassis shall be the
Each shall consist of the following sections and components:
•Each unit shall have a matching, easily removable, textured finish,
•Hermetically sealed refrigerant system with external vibration isolated
•
•A
•
•A positive cooling condensate disposal system which meets the test requirements of applicable A.R.I. Standard 310 (for Packaged Terminal Air Conditioners) and 380 (for Packaged Terminal Heat Pumps) (80°F dry bulb, 75°F wet bulb, 80% relative humidity);
•Condenser and evaporator coils to be constructed of copper tubing and aluminum plate fins designed to achieve EER and COP rating of the unit;
•Indoor and outdoor airflows that match the capacity of the coils for efficient heat transfer. Water
•Adjustable indoor discharge air louvers that provide a 50° off vertical air pattern with an alternate position to provide a 40° off vertical air pattern;
•Easily accessible controls for selection of unit operation and thermostat setting. Controls shall be covered by a hinged door;
•
•
•Electronic temperature limiting with seven independent heating and cooling settings to limit maximum and minimum temperatures without restricting movement of thermostat control knob;
•Freeze Sentinel™ to automatically activate the electric resistance heater and fan motor to warm and circulate indoor air to help prevent damage due to freezing temperatures. Freeze Sentinel shall operate as long as unit is connected
to powered electrical circuit and unit shall provide ability for owner to defeat the Freeze Sentinel operation;
•Heat Sentinel to automatically activate air conditioner operation when the unit is in the STOP setting when the room temperature warms to 85ºF and turns air conditioner operation off when the room temperature cools to 80°F, if selected by owner;
•Compatible with
•Remote Thermostat compatibility with Class 2 remote thermostat;
•Connections to interface with a transfer fan to move air into another room;
Unit shall have means of electrical connection listed by Underwriters Laboratories and compatible with the unit’s required voltage and ampacity in conformance with National Electrical Code and local codes.
Additional specifications for GE Zoneline 6100 Series Packaged Terminal Heat Pumps
Heat pump units shall provide operation that will either: A) automatically phase in electric resistance heat, if outdoor temperature is below 46°F, if heat pump alone is unable to maintain room temperature; or B) use partial electric resistance heat simultaneous with heat pump operation any time the outdoor temperature is below 46;°F. Selection of A or B operation is made by means of a selector switch concealed from room occupant. In either A or B operation, the unit will switch to full resistance heat if room temperature continues to decline or the outdoor temperature falls below 25°F. If the outdoor temperature is above 46°F, unit will lock out electric resistance heat and operate on heat pump only.