Page 14

Central Desk Control

Some installations may want to govern the ability of the unit to operate from a control device remote to the unit or even remote to the room in which the unit is located. The general term given to systems such as this is Central Desk Control. The most common installation of this type of system is a switch mounted at the registration desk and, upon guest check-in, a button is pushed or a switch is moved to allow the air conditioner to operate. Likewise, when the guest checks out the device is put into the “OFF” position so the unit will not operate while the room is vacant.

It is not necessary that the controlling device be located at a central desk to employ a device that will control the unit operation. For instance, in some resort areas devices are connected to sliding glass doors and opening the door causes a contact to close, turning the air conditioner off. This prevents energy being wasted by operating the air conditioner when warm, humid air is entering the room. Some systems operate by motion sensors or heat-sensing detectors mounted in the room. These types of systems determine occupant presence in the room and allow the unit to operate; if no one is in the room the device signals the air conditioner to turn off.

Zoneline® models offer load-shedding capabilities on units connected to Central Desk Control systems. For more information on the models’ load-shedding feature, see page 10.

There is a wide variety of devices available, each with its own benefits and constraints. While GE does not offer components that are external to the unit for a Central Desk Control (CDC) system, GE Zoneline units are compatible with most CDC and energy management systems. Zoneline units provide a 24 VAC circuit that powers the Central Desk Control system and no external power is needed.

All Zoneline 4100 and 6100 Series units are compatible with simple on/off 2-wire Central Desk Control systems. Consult with the provider of the energy management system to be sure it is compatible with GE Zoneline units. Zoneline units have standard connectors factory-installed to provide a CDC interface that permits the unit to be connected to most of the energy management systems. The devices connected to the Zoneline units require no power supply or transformers external to the unit.

Important CDC Comments (all series applicable)

1.When the switching device closes the circuit of the CDC conductors, the unit operation stops.

2.Do not use a common bus (at the unit or at the switch panel) in the wiring. Both wires comprising the circuit must connect to the unit connectors and to the controlling switch. Running one wire from one unit to another unit is common busing and may damage internal components or cause erratic operation of the system.

3.A 24-volt transformer is contained within the Zoneline unit. No external voltage may be applied to the unit through the CDC terminals. (Voltage on the CDC conductors is

24 volts AC.)

4.Recommended wire size must be followed as a minimum requirement.

Wire Size #AWG

Maximum Allowable Length

#22

600

Ft.

#20

900

Ft.

#18

1500

Ft.

#16

2000

Ft.

Freeze Sentineland Heat Sentinel remains operational when the unit is connected to a CDC system. Even if the unit is turned “OFF” at the central location, if the sensor at the unit detects the low or high limit temperature, the unit will automatically turn on until it reaches the preset shutdown temperature (46°F heating, 80°F cooling).

Connecting the Zoneline unit to a CDC system does not eliminate the ability to connect the unit to a remote thermostat. Once the circuit is “opened,” and control of the unit removed from the CDC system, the selected controls—either the unit— mounted control or the remote thermostat—govern the operation of the unit.

Please see page 55 for installation recommendations for the Central Desk Control wiring.

CDC Terminal Location and Typical Wiring

See page 15 for location of CDC terminals on unit.

Example of Common Busing

 

NOT PERMITTED

Unit #1

Unit #2

Unit #3

INCORRECT Common Busing

 

Normally Open

 

Switch -

 

Unit Operational

 

CDC Terminals

 

 

on Zoneline unit

 

 

Typical Wiring

 

(All Wiring Shown Is Field Supplied)

14

Image 14
Contents GE Zoneline packaged terminal air conditioners Quick Reference 6100 Series Control Panel230/208-Volt Line Cord Connection Units Power Connection KitsZoneline Chassis Nomenclature Volt Sub-Base and Direct Connected UnitsDeluxe Dry Air 25 Models Cooling With Resistance HeatTable of Contents Introduction Deluxe Line Standard FeaturesDeluxe Line Optional Features Advantages of the GE Zoneline SystemOptional Accessories of the Zoneline System Zoneline SystemZoneline Features Resistance heatFeatures and Benefits Compressor Restart Delay Fan-Only Setting HIGH/LOWFan-Cycle Switch SmartFan Electronic Temperature LimitingCorrosion Protection Optional Up-Front Air FiltersConcealed Manual Vent Control Internal Condensate Removal ICRTo change modes Auxiliary Control SettingsAuxiliary Control-Aux Set Button Press AUX SET AU appears on the displayTemperature limits-Cool Important CDC Comments all series applicable CDC Terminal Location and Typical WiringCentral Desk Control Resistance Heat Models Field Wiring TerminalRemote Thermostat Control RAK806 Universal Control Cover LabelRAK148D1 RAK148P1 Feature Heat Pump Electric HeatHeat Pump Models Low-Voltage Conductors Zoneline SeriesType Function For remote thermostat operation follow the steps belowHeat Pumps and Energy Savings Balance PointHeat pump defrost Zoneline 6100 Series Heat Pump Operation Zoneline 6100 SeriesZoneline Heat Pump Heat Source Logic Heat pump condensateHigh Wall Mount For units Application CommentsAir Distribution 16-1/4 MIN. x 42-1/4 MIN DimensionsAdditional 16-1/2 MIN. x 42-3/8 MINSub-Base RAK204U No receptacle, no wiring will accept anyWall Case Choice of wall cases is available for Zoneline unitsSub-bases for the 265-volt units Wall Case Installation DataGeneral Masonry Wall Construction Architectural Window Louver InstallationWindow, Curtain and Panel Wall Construction Brick, Frame, Stucco Shingle ConstructionCase Angles Installation of Wall Case in Wall OpeningPreparation of the Wall Case for All Types of Construction Framing for Wall Case Brick Veneer and Frame ConstructionFrame and Brick Veneer Installation Cord set connected Wall Section Detailed Side ViewWall Case Receptacle Wall Case Installation Cord SET Connected AS Reqd Geappliances.com TOP View RAK204 Series SUB-BASE Installation and Electrical Data RAB71A/77 Wall CaseCondensate Disposal Systems Wall Case with RAD10 Drain KIT External Drain. See page 36 for internal drainInternal Drain. See page 35 for external drain Replacements of Existing Ducted Units Ducted InstallationsNew Ducted Installations Ducted Application ConsiderationsDuct Adapter Extension has 1/2 Insulation Com RAG63 Bittersweet Chocolate Exterior GrillesOutdoor Grille Exterior Architectural Treatments Special Outdoor Grilles 230/208-Volt Permanently Connected Units Or 277-Volt Unit Installation Permanently Connected Units230/208-Volt Line-Cord Connected Units 230/208 Volt Sub-Base and Direct-Connected UnitsEssential Elements Ordering Overview Electrical Wiring Information 4100/6100 SeriesReplacement of Existing Chassis Volt Units Maximum Connected LoadLatent System Capacity Formula for Calculating Operating Costs Using Above Data Normal Yearly Operating DataTypical 4100 Series, 230/208-Volt Wiring Diagram Typical 4100 Series, 230/208-Volt Schematic Diagram Typical 6100 Series, 230/208-Volt Wiring Diagram Typical 6100 Series, 230/208-Volt Schematic Diagram Suggested Bid Form Specifications Each shall consist of the following sections and componentsAlternate specification for molded wall case Receptacles/Sub-Bases 6 1 H 1 2 D a DPreliminary Specifications CapacityComplete Accessory List Kit Number DescriptionGeneral Installation Suggestions Replacement Installations Zoneline WarrantyDucted Installation Comments New InstallationsGeappliances.com Page Category Alphabetical IndexExterior Grille Color Samples Beige Maple BittersweetYears of innovation and we’re just getting started