GE 6100, 4100 230/208-Volt Line-Cord Connected Units, 230/208-Volt Permanently Connected Units

Page 42

Power Connection for 4100 and 6100 Series Zoneline® Units

All 4100 and 6100 Series Zoneline units are equipped with universal heaters allowing chassis installation flexibility. The Zoneline units are connected to the building power supply by a unique power connection kit. By utilizing a separate universal power connection (UPC) kit, each unit is capable of providing various outputs of electric resistance heat to more closely meet the heating requirements of the particular room, thereby increasing the installation flexibility of the particular chassis. This power connection kit is the only means of supplying power to the Zoneline chassis. The appropriate

kit is determined by the voltage, the means of electrical connection, either line-cord connected or permanently connected, and the desired resistance heat output that may be supported by the branch circuit.

230/208-Volt Line-Cord Connected Units

Line Cord Kits consist of a self-aligning nine-pin molded connector that plugs into a mating connector on the Zoneline chassis and insulated line cord with an electrical plug on the end. The configuration of the electrical plug conforms to NEC standards for the circuit amperage and the position of the wires in the nine-pin connector determines the heater wattage and current requirements when it is plugged into the Zoneline chassis.

The power connection kit is selected by the amperage of the circuit where it will be installed. Each line cord kit has an integral Leakage Current Detection and Interruption (LCDI) or Arc Fault Current Interrupter (AFCI) device as required by the National Electrical Code (NEC) and Underwriters Laboratory (UL) for line-cord connected air conditioners manufactured on or after August 1, 2004. The line-cord power connection kits are shown in the table below.

230/208-Volt Line-Cord Connected Units

Line Cord

Electric

Electric

Electric

Min. Circuit

Heat

Heater

Heat

Protection

Kit

BTUH

Watts

Amps

(Amps)

 

 

 

 

 

 

RAK3153A

8150/7900

2400/2320

11.0/11.6

15

RAK3203A

11200/10900

3300/3200

15.1/16.0

20

RAK3303A

16000/15450

4700/4530

21.2/22.4

30

Electric Heat Amps include electric heater and fan motor current draw.

230/208-Volt Permanently Connected Units

Permanently connected units do not require the LCDI or AFCI device. Permanent connection is usually made through the use of a sub-base. Each 230/208-volt sub-base consists of a sub-base with appropriate receptacle for minimum circuit amperage, a chaseway to route power connector from the sub-base to the chassis, wiring to connect the sub-base

to building wiring and a short line cord with a self-aligning nine-pin connector to connect to chassis and plug into the receptacle in the sub-base. Permanent, or direct-wired, installation of a 230/208-volt unit requires a junction box kit, RAK4002A, which attaches to the chassis to form an enclosed junction box.

The short sub-base line cord may not be used without the sub-base.

For 4100 and 6100 Series 230/208-volt units where a permanent installation using flexible conduit is desired, the RAK4002A forms an enclosed junction box on the chassis. The RAK4002A has a 7/8"-diameter hole to allow conduit to be connected to the junction box. For direct connection, purchase and install the appropriate Universal Power Supply Kit (also referred to as the Direct Connection Kit below) that matches the ampacity of the building circuit connected to the unit. This nine-pin connector with three 7"-long conductor wires is used for direct connections to the building wiring inside a direct-connect junction box. These wires are then connected to the building wiring by field-supplied connectors.

230/208 Volt Sub-Base and Direct-Connected Units

 

Direct

Electric

Electric

Electric

Min. Circuit

Sub-Base

Connection

Heat

Heater

Heat

Protection

 

Kit

BTUH

Watts

Amps

(Amps)

 

 

 

 

 

 

RAK204D15P

RAK4157

8150/7900

2400/2320

11.0/11.6

15

RAK204D20P

RAK4207

11200/10900

3300/3200

15.1/16.0

20

RAK204D30P

RAK4307

16000/15450

4700/4530

21.2/22.4

30

Electric Heat Amps include electric heater and fan motor current draw.

265- or 277-Volt Unit Installation — Permanently Connected Units

National Electric Code (Article 440.60) requires permanent connection for units connected to power sources over 250 volts; therefore these units must be permanently connected (direct-wired) with field-supplied connectors. Units connected using a sub-base meet the requirement for permanent connection since all wiring is internal wiring between the sub-base and the chassis.

Since 265-volt units may not be line-cord connected, an LCDI device is not required.

265 Volt Sub-Base and Direct-Connected Units

 

Electric Heat

Electric Heater

Electric Heat

Min. Circuit

Sub-Base

Protection

BTUH

Watts

Amps

 

(Amps)

 

 

 

 

RAK3153A

8150

2400

9.6

15

RAK3203A

11550

3400

13.3

20

RAK3303A

16350

4800

18.6

30

Electric Heat Amps include electric heater and fan motor current draw.

Each 265-volt sub-base kit consists of a sub-base with appropriate receptacle for minimum circuit amperage, a chaseway to route the power connector from the sub-base to the chassis and wiring to connect the sub-base to the building wiring.

The 265-volt power connection kit must be ordered separately.

All wiring must conform to local electrical regulations and codes.

42

Image 42
Contents GE Zoneline packaged terminal air conditioners Quick Reference 6100 Series Control Panel230/208-Volt Line Cord Connection Units Power Connection KitsZoneline Chassis Nomenclature Volt Sub-Base and Direct Connected UnitsDeluxe Dry Air 25 Models Cooling With Resistance HeatTable of Contents Introduction Deluxe Line Standard FeaturesDeluxe Line Optional Features Advantages of the GE Zoneline SystemOptional Accessories of the Zoneline System Zoneline SystemZoneline Features Resistance heatFeatures and Benefits Compressor Restart Delay Fan-Only Setting HIGH/LOWFan-Cycle Switch SmartFan Electronic Temperature LimitingCorrosion Protection Optional Up-Front Air FiltersConcealed Manual Vent Control Internal Condensate Removal ICRTo change modes Auxiliary Control SettingsAuxiliary Control-Aux Set Button Press AUX SET AU appears on the displayTemperature limits-Cool CDC Terminal Location and Typical Wiring Central Desk ControlImportant CDC Comments all series applicable Resistance Heat Models Field Wiring TerminalRemote Thermostat Control RAK806 Universal Control Cover LabelFeature Heat Pump Electric Heat Heat Pump ModelsRAK148D1 RAK148P1 Low-Voltage Conductors Zoneline SeriesType Function For remote thermostat operation follow the steps belowHeat Pumps and Energy Savings Balance PointHeat pump defrost Zoneline 6100 Series Heat Pump Operation Zoneline 6100 SeriesZoneline Heat Pump Heat Source Logic Heat pump condensateApplication Comments Air DistributionHigh Wall Mount For units 16-1/4 MIN. x 42-1/4 MIN DimensionsAdditional 16-1/2 MIN. x 42-3/8 MINSub-Base RAK204U No receptacle, no wiring will accept anyWall Case Choice of wall cases is available for Zoneline unitsWall Case Installation Data GeneralSub-bases for the 265-volt units Masonry Wall Construction Architectural Window Louver InstallationWindow, Curtain and Panel Wall Construction Brick, Frame, Stucco Shingle ConstructionInstallation of Wall Case in Wall Opening Preparation of the Wall Case for All Types of ConstructionCase Angles Framing for Wall Case Brick Veneer and Frame ConstructionFrame and Brick Veneer Installation Cord set connected Wall Section Detailed Side ViewWall Case Receptacle Wall Case Installation Cord SET Connected AS Reqd Geappliances.com TOP View RAK204 Series SUB-BASE Installation and Electrical Data RAB71A/77 Wall CaseCondensate Disposal Systems Wall Case with RAD10 Drain KIT External Drain. See page 36 for internal drainInternal Drain. See page 35 for external drain Replacements of Existing Ducted Units Ducted InstallationsNew Ducted Installations Ducted Application ConsiderationsDuct Adapter Extension has 1/2 Insulation Com Exterior Grilles Outdoor GrilleRAG63 Bittersweet Chocolate Exterior Architectural Treatments Special Outdoor Grilles 230/208-Volt Permanently Connected Units Or 277-Volt Unit Installation Permanently Connected Units230/208-Volt Line-Cord Connected Units 230/208 Volt Sub-Base and Direct-Connected UnitsElectrical Wiring Information 4100/6100 Series Replacement of Existing ChassisEssential Elements Ordering Overview Maximum Connected Load Latent System CapacityVolt Units Formula for Calculating Operating Costs Using Above Data Normal Yearly Operating DataTypical 4100 Series, 230/208-Volt Wiring Diagram Typical 4100 Series, 230/208-Volt Schematic Diagram Typical 6100 Series, 230/208-Volt Wiring Diagram Typical 6100 Series, 230/208-Volt Schematic Diagram Suggested Bid Form Specifications Each shall consist of the following sections and componentsAlternate specification for molded wall case Receptacles/Sub-Bases 6 1 H 1 2 D a DPreliminary Specifications CapacityComplete Accessory List Kit Number DescriptionGeneral Installation Suggestions Replacement Installations Zoneline WarrantyDucted Installation Comments New InstallationsGeappliances.com Page Category Alphabetical IndexExterior Grille Color Samples Beige Maple BittersweetYears of innovation and we’re just getting started