Pilot Head

Orifice

Retainer

Clip

Pilot Base

Figure 20.

Pilot orifice removal and replacement.

Mounting

Gasket

 

Screws

 

Regulator

Apply

small

Tower

label

Figure 21. Regulator Assembly.

Figure 22.

Burner plate engagement.

Burner

Notch

Pin

GF 100 DV II Nordic QT

GF 200 DV II Lillehammer

Gas Supply Connection

NOTE: If the optional Blower will be installed, use a 90° Elbow off the valve to create adequate clearance for the main gas line.

The gas supply line connection is made to the valve just inside the left rear leg. The gas supply line should be 3/8" npt with a 1/2" diameter supply, or the appropriate size to provide sufficient gas pressure to the valve regardless of the input setting.

The use of a Flexible Gas Appliance Connector is acceptable in many areas in the U.S. However, Canadian methods vary depending on local code.

ALL INSTALLATIONS MUST COMPLY WITH LOCAL CODE OR IN THE ABSENCE OF LOCAL CODE, MUST COMPLY WITH THE MOST RECENT EDITION OF THE NATIONAL FUEL GAS CODE ANSI Z223.1/NFPA 54 OR CAN-B149.

All codes require a gas shut-off valve (gas cock) and union, to be installed in the supply line, and in the same room as the appliance. This allows for the disconnection of the stove for servicing and maintenance. See fig. 23.

A T-HANDLE GAS COCK IS REQUIRED IN MASSACHUSETTS TO COMPLY WITH CODE 248CMR.

Secure all joints tightly using appropriate tools and sealing compounds. For propane units be sure to use compounds that are propane resistant. Turn on gas supply and test for gas leaks using a soapy water solution. Never use an open flame to check for leaks.

Leak test:

1.Mix a 50-50 solution of water and dish soap.

2.Light appliance- see lighting instructions on the inside back cover of this manual or on the stove’s rating plate.

3.Brush or spray all joints and connections with the soapy water solution.

4.If bubbles appear at any connection or seam or a gas odor is detected, immediately turn gas control knob to the OFF position.

5.Tighten or reconnect the leaking joint and retest for any gas leaks.

Figure 23. Supply valve coupling.

17

Image 17
Contents Installation and Operation Instructions Welcome to Jøtul Table of Contents GF 100 DV II Miscellaneous Kit Contents Jøtul GF 100 DV II Nordic QT SpecificationsGF 100 DV II Accessories Input RatesGF 200 DV II Miscellaneous Kit Contents Jøtul GF 200 DV II Lillehammer SpecificationsSuggested Tools for Installation and Service Stove SetupRemove the Top Plate Remove the Glass PanelLocation Safety InformationHearth Requirements Glass FrontAlcove Installation Intake Air Restriction Venting RequirementsHorizontal Termination Vertical TerminationHorizontal RUN Vertical Vent TerminationVenting Through a Fireplace Co-linear Vent InstallationThese installation requirements must be followed Min. / Max. Horizontal Run Horizontal Vent TerminationHorizontal Termination with Vertical Rise Wall Shield InstallationMin inches, U.S. / *12 inches 30 cm can Horizontal Termination ClearanceTools required Mobile Home InstallationConversion Kit Contents Never USE AN Open Flame to Check for GAS Leaks Gas Conversion ProcedureLeak test Gas Supply ConnectionInches water column High Altitude AdjustmentGas Pressure High Altitude Orifice Chart GF 200 DV II Only Flame Appearance Air Shutter AdjustmentDerating Procedure To adjust the air shutterRemote Control Optional Wall Thermostat or Remote ControlLog Set Installation Proper pilot flame appearance System CheckGlass and Gasket Replacement MaintenanceOnly Use Replacement Kit OperationDate of Purchase Name of InstallerOptional Blower # InstallationBlower Operation Connect power cord to the nearest outletAttach the Blower to the stove Snapstat terminal. See figs.3547a 47b 47b Parts List GF 100 DV II / GF 200 DV II Firebox Assembly47a GF 100 DV II Nordic QT GF 200 DV II Lillehammer GF 100 DV II Nordic QT Cast Iron Parts ListInstall the Lower Panel Optional Antique Brick Panel Kit InstallationInstall the Logset. Refer to pg Replace the Glass FrameControl Valve Lighting InstructionsJøtul North America Jøtul AS