Jotul GF 100 DV II, GF 200 DV II Gas Pressure, High Altitude Adjustment, Inches water column

Page 18

GF 100 DV II Nordic QT GF 200 DV II Lillehammer

Gas Pressure

Correct gas pressure is essential for efficient and safe operation. It is important that the correct pressure is established at the time of the installation. Proper gas pressure provides a consistent flow of gas to the appli- ance and is instrumental in checking for gas leaks.

Pressure Test: Attach a manometer to the appropri- ate test point on the valve. See fig. 24. The gauge connec- tions are located on the front of the valve under the On/ Off/Pilot- knob. Gauge connections are identified by:

E - for Inlet or Supply Pressure (the amount of gas coming to the valve.)

A - for Manifold Pressure (the amount of gas that is coming out of the valve to the burner.)

ALWAYS TEST PRESSURES WITH VALVE CONTROL KNOB SET ON HIGH.

NECESSARY INLET GAS PRESSURES

(inches water column)

 

MIN

MAX

NATURAL GAS

5.0

7.0

PROPANE

12.0

14.5

The appliance and its appliance main gas valve must be disconnected from the gas supply piping system during any pressure testing on that system at test pressures in excess of 1/2 psig (3.5 kPa).

The appliance must be isolated from the gas supply line by closing its individual manual gas shut-off valve (gas cock) during any pressure testing of the gas supply piping system that is equal to or less than pressures of 1/2 psig (3.5 kPa).

MANIFOLD PRESSURES (inches water column)

 

MIN

MAX

NATURAL GAS

1.2

3.8

PROPANE

2.9

11.0

High Altitude Adjustment

The decreased atmospheric pressure of higher altitudes affects heat value of gaseous fuels. Most gas suppliers derate the gas intended for use at elevations above 2000 feet. Check with your gas supplier before performing derate adjustment to the burner.

The GF 100 DV II Nordic QT does not require adjustment for elevations up to 4500 ft. DO NOT DERATE.

The GF 200 DV II Lillehammer may be adjusted for altitude over 2000 ft. (610 - 1371 m). Check with your gas supplier and, if necessary, install High Altitude Adjustment Kit 155808 for Natural Gas, or Kit 155809 for Propane.

See the chart below for appropriate orifice sizes and part numbers.

IN THE U.S:

THE DERATING KIT MUST BE INSTALLED BY AN AUTHORIZED SERVICE TECHNICIAN IN ACCOR- DANCE WITH THE MANUFACTURER’S INSTRUC- TIONS AND ALL CODES AND REQUIREMENTS OF THE AUTHORITY HAVING JURISDICTION. THE INFORMATION LABEL MUST BE FILLED OUT BY THE INSTALLER AND APPLIED TO THE APPLIANCE AT THE TIME OF THE CONVERSION. THE QUALIFIED SERVICE AGENCY PERFORM- ING THIS WORK ASSUMES RESPONSIBILITY FOR THIS DERATING.

IN CANADA,

THIS UNIT HAS BEEN TESTED FOR INSTALLA- TION AT HIGH ALTITUDES IN ACCORDANCE WITH CANADIAN TEST STANDARD CAN/CGA- 2.17.

THE DERATING SHALL BE CARRIED OUT IN ACCORDANCE WITH THE REQUIREMENTS OF THE PROVINCIAL AUTHORITIES HAVING JURISDICTION AND IN ACCORDANCE WITH THE REQUIREMENTS OF THE CAN1-B-149.1

AND .2 INSTALLATION CODE.

For high altitude installations, consult your local gas distributor or the authority having jurisdiction for proper rating methods. If the appliance is converted for high altitude, the Conversion Label, supplied with the kit, must be filled out by the installer and applied to the appliance at the time of the conversion. See fig. 25.

EA

Figure 24. Pressure test points.

18

Image 18
Contents Installation and Operation Instructions Welcome to Jøtul Table of Contents GF 100 DV II Accessories Jøtul GF 100 DV II Nordic QT SpecificationsGF 100 DV II Miscellaneous Kit Contents Input RatesJøtul GF 200 DV II Lillehammer Specifications GF 200 DV II Miscellaneous Kit ContentsRemove the Top Plate Stove SetupSuggested Tools for Installation and Service Remove the Glass PanelHearth Requirements Safety InformationLocation Glass FrontAlcove Installation Horizontal Termination Venting RequirementsIntake Air Restriction Vertical TerminationVertical Vent Termination Horizontal RUNCo-linear Vent Installation These installation requirements must be followedVenting Through a Fireplace Horizontal Vent Termination Min. / Max. Horizontal RunWall Shield Installation Horizontal Termination with Vertical RiseHorizontal Termination Clearance Min inches, U.S. / *12 inches 30 cm canMobile Home Installation Conversion Kit ContentsTools required Gas Conversion Procedure Never USE AN Open Flame to Check for GAS LeaksGas Supply Connection Leak testHigh Altitude Adjustment Gas PressureInches water column Derating Procedure Flame Appearance Air Shutter AdjustmentHigh Altitude Orifice Chart GF 200 DV II Only To adjust the air shutterOptional Wall Thermostat or Remote Control Log Set InstallationRemote Control System Check Proper pilot flame appearanceOnly Use Replacement Kit MaintenanceGlass and Gasket Replacement OperationName of Installer Date of PurchaseInstallation Optional Blower #Attach the Blower to the stove Connect power cord to the nearest outletBlower Operation Snapstat terminal. See figs.3547a 47b Parts List GF 100 DV II / GF 200 DV II Firebox Assembly 47a47b GF 100 DV II Nordic QT GF 200 DV II Lillehammer Cast Iron Parts List GF 100 DV II Nordic QTInstall the Logset. Refer to pg Optional Antique Brick Panel Kit InstallationInstall the Lower Panel Replace the Glass FrameLighting Instructions Control ValveJøtul AS Jøtul North America