Johnson Controls GG9S'MP Section Vi Twinning And Staging, UIM-H-0712, Accessory Connections

Page 15
ACCESSORY CONNECTIONS

364861-UIM-H-0712

ACCESSORY CONNECTIONS

The furnace control will allow power-switching control of various acces- sories.

ELECTRONIC AIR CLEANER CONNECTION

Two 1/4” (6.4 mm) spade terminals (EAC and NEUTRAL) for electronic air cleaner connections are located on the control board. The terminals provide 115 VAC (1.0 amp maximum) during circulating blower opera- tion.

HUMIDIFIER CONNECTION

Two 1/4” (6.4 mm) spade terminals (HUM and NEUTRAL) for humidifier connections are located on the control board. The terminals provide 115 VAC (1.0 amp maximum) during heating system operation.

A mounting hole is provided on the control panel next to the furnace control board for mounting a humidifier transformer if required.

Vent Pipe

Electrical

Supply

SUPPLYCOMMON

PLENUM

Gas Supply ELECTRONIC AIR CLEANER CONNECTION (Both sides)

1 Coil for HUMIDIFIER CONNECTION Each Furnace

Supply

Air

SECTION VI: TWINNING AND STAGING

In applications where more heating capacity or more airflow capacity is needed than what one furnace can deliver, twinning can be used to make two furnaces operate in tandem. When two furnaces are installed using the same duct system, it is very important that the two furnace cir- culating air blowers operate in unison. If one blower starts before the second blower, the duct system will become pressurized and the blower on the second furnace will turn backwards causing the second furnace to overheat, resulting in damage to the furnace. Twinning is used to make two furnaces operate in tandem, using one duct system, one room thermostat and causing both furnaces to turn on and off simulta- neously.

Before installing the relay and wiring, disconnect electrical power to both furnaces. Failure to cut power could result in electrical shock or equipment damage.

The relay must not be installed in any location where it could be exposed to water. If the relay has been exposed to water in any way, it must not be used.

TWINNING DUCT SYSTEM

Twinned furnaces must only be applied on a common duct system. A single air supply plenum must be used for both furnaces and coil(s). Separate plenums and supply ducts systems cannot be utilized. A sin- gle return air plenum, common to both furnaces must be used. It is sug- gested that a return platform be utilized, with bottom air entrance into each furnace. If a side entrance returns system is used, the common return duct must be divided equally so as to supply each furnace with an equal amount of return air.

Both furnaces must be identical models in both heating capacity and CFM capacity. Both furnaces must be operated on the same motor speed tap. See typical application, Figure 20.

If furnace staging is desired with two single stage furnaces on a com- mon duct, where the gas burner on the first furnace operates on W1 and the gas burner on the second furnace operates on W2, then the use of an air-mixing device in the plenum to mix the air from both fur- naces is strongly recommended. The mixing device must be installed before any ducts that supply air to occupied spaces. Twinning causes both indoor fans to operate simultaneously. If a mixing device is not used, any ducts that are connected down stream from the furnace that operates on W2, will be supplying cold air in the Heating mode to the occupied spaces unless W2 is energized.

FIGURE 20: Typical Twinned Furnace Application

When two furnaces are twinned, typical system total airflow will be approximately 85% of additive individual furnaces, i.e., two 2000 CFM units will yield a total 3400 CFM.

If a return duct is connected to only one furnace (with a connection between the two furnaces) an imbalance in the airflow will occur and the furnace furthest from the return plenum will overheat.

GAS PIPING

Furnace gas supplies must be provided as specified with these instruc- tions. Since the furnaces are side by side, with no space between, gas supplies must enter on the right and left respectively. All gas piping must be in accordance with the national fuel gas code, ANSI Z223.1, latest edition, and/or all local code or utility requirements.

TWINNING

In applications where more heating capacity or more airflow capacity is needed than what one furnace can deliver, twinning can be used to make two furnaces operate in tandem, using one duct system and one room thermostat. When one duct system is used for two furnaces, it is necessary that the two blowers operate in unison. The twinning function of the board in this furnace ensures that both blowers turn on and off simultaneously, and operate on the same blower speed.

The control in the furnace has the single-wire twinning feature. With this feature, a wire is connected between the TWIN terminal on one furnace board to the TWIN terminal on the second furnace board. The board then communicates the blower status from one furnace to the other along this wire. This communication makes the second furnace blower come on at the same time, and on the same speed, as the first furnace blower. To ensure stable communication, the common terminal of each control must be connected.

Twinning Instructions

Connect the control wiring as shown in Figure 21.

1.Connect the low voltage wiring from the wall thermostat to the ter- minal strip on the control board of Furnace #1.

2.Connect a wire from the TWIN terminal of Furnace #1 to the TWIN terminal of Furnace #2.

3.Install a separate 24V relay as shown in the diagram below. Use of this relay is required, as it ensures that the transformers of the two furnaces are isolated, thus preventing the possibility of any safety devices being bypassed.

4.Connect the 24V common wires of furnace #1 to the 24V common terminal of furnace #2.

Johnson Controls Unitary Products

15

Image 15
Contents 95.5% AFUE Single Stage Multi-position INSTALLATION MANUALRESIDENTIAL GAS FURNACE MODELS TG9S*MP, GG9S*MP364861-UIM-H-0712 SECTION I SAFETYSPECIFIC SAFETY RULES AND PRECAUTIONS SAFETY REQUIREMENTS364861-UIM-H-0712 STEP 1 - SafetySTEP 2 - General Installation STEP 6 - Gas Piping and Gas Pipe Pressure TestingINSPECTION Clearances for access/serviceInstallation in a residential garage 364861-UIM-H-0712SECTION II DUCTWORK FLOOR BASE AND DUCTWORK INSTALLATION - DOWNFLOWThe duct system’s design and installation must installedCOIL FLANGE INSTALLATION COIL INSTALLATIONCOIL/FURNACE ASSEMBLY - MC/FC/PC SERIES COILS FURNACE ASSEMBLY - MC & FC SERIES COILSDIMENSION “C” INCH DOWNFLOW DUCT CONNECTORSCOIL / FURNACE ASSEMBLY - HC SERIES COILS BOTTOM RETURN AND ATTIC INSTALLATIONSDOWNFLOW APPLICATION ATTIC INSTALLATIONSUSPENDED FURNACE / CRAWL SPACE INSTALLATION 364861-UIM-H-0712attempt to install filters inside the furnace FILTER INSTALLATIONFIGURE 13 Dimensions Cabinet Dimensions InchesSECTION IV GAS PIPING DANGERGAS SAFETY GAS PIPING INSTALLATIONDANGER SECTION V ELECTRICAL POWERHIGH ALTITUDE PRESSURE SWITCH CONVERSION ELECTRICAL POWER CONNECTIONSInput LOW VOLTAGE CONTROL WIRING CONNECTIONS364861-UIM-H-0712 SUPPLY VOLTAGE CONNECTIONSAC 5D 364861-UIM-H-0712Johnson Controls Unitary Products HP 2C Single Stage Heat Pump - Single Stage PSC Furnace364861-UIM-H-0712 364861-UIM-H-0712 ACCESSORY CONNECTIONSELECTRONIC AIR CLEANER CONNECTION SECTION VI TWINNING AND STAGINGSTAGING 364861-UIM-H-0712Twinning Operation Staging OperationOpen Stand Pipe Anti-siphonair vent 5” Min Tee 364861-UIM-H-0712CONDENSATE DRAIN TERMINATION Johnson Controls Unitary ProductsUPFLOW pressure switch hose1 pressure switchhose INDUCER ROTATED FOR RIGHT SIDE VENTINGAIRFLOW AIRFLOW DOWNFLOW - INDUCER ROTATED FOR LEFT SIDE VENTINGDOWNFLOW - INDUCER ROTATED FOR RIGHT SIDE VENTING AIRFLOW HORIZONTAL - LEFT INDUCER ROTATEDHORIZONTAL - LEFT INDUCER AS RECEIVED Except for 130K ModelHORIZONTAL - RIGHT Move pressure switch hose to this position1Move pressure switch hose to this position HORIZONTAL - RIGHT INDUCER ROTATEDCOMBUSTION AIR/VENT PIPE SIZING COMBUSTION AIR AND VENT SAFETYSECTION VIII COMBUSTION AIR AND VENT SYSTEM 364861-UIM-H-0712364861-UIM-H-0712 COMBUSTION AIR AND VENT PIPING ASSEMBLYFIGURE 29 Dimensions Elbow A DimensionVENT CLEARANCES Canadian Installations1,3US Installation2,3 364861-UIM-H-0712VENTING MULTIPLE UNITS 364861-UIM-H-0712VENT SYSTEM VENT APPLICATIONS AND TERMINATIONOutdoor Combustion Air 364861-UIM-H-0712DOWNWARD VENTING COMBUSTION AIR SUPPLYCombustion Air Source From Outdoors 364861-UIM-H-0712Ambient Combustion Air Supply Dampers, Louvers and Grilles Canada OnlyVentilated Combustion Air Termination 364861-UIM-H-0712Air Supply Openings and Ducts Ventilated Combustion AirVENT BLOWER ROTATION SECTION IX START-UPAND ADJUSTMENTSSpecially Engineered Installations 364861-UIM-H-0712HOT SURFACE IGNITION SYSTEM 364861-UIM-H-0712IGNITION SYSTEM SEQUENCE CALCULATING THE FURNACE INPUT NAT. GAS1 Cu Ft 364861-UIM-H-0712Johnson Controls Unitary Products 1 RevolutionRead the manifold gas pressure ADJUSTMENT OF MANIFOLD GAS PRESSURE & INPUT RATE364861-UIM-H-0712 Read the inlet gas pressure364861-UIM-H-0712 ADJUSTMENT OF TEMPERATURE RISEADJUSTMENT OF FAN CONTROL SETTINGS DANGERBottom Airflow Data SCFM 364861-UIM-H-0712Johnson Controls Unitary Products 364861-UIM-H-0712ROLLOUT SWITCH CONTROLS SECTION X SAFETY CONTROLSSECTION XI NORMAL OPERATION AND DIAGNOSTICS BLOWER DOOR SAFETY SWITCHFURNACE CONTROL DIAGNOSTICS 364861-UIM-H-0712Johnson Controls Unitary Products 364861-UIM-H-0712 SECTION XII REPLACEMENT PARTS LISTREPLACEMENT PART CONTACT INFORMATION DIAGNOSTIC FAULT CODE STORAGE AND RETRIEVALJohnson Controls Unitary Products Wiring Diagram - 95% Single-StageFurnaceSECTION XIII WIRING DIAGRAMNorman, OK York International Corp 5005 York Drive