Johnson Controls GG9S'MP, TG9S'MP UIM-H-0712, Combustion Air And Vent Piping Assembly, Dimensions

Page 23
FIGURE 29: Dimensions

364861-UIM-H-0712

 

 

 

 

 

 

 

A

 

 

 

 

 

 

 

 

 

 

 

A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A

 

 

 

 

 

 

 

A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

STANDARD ELBOW

LONG (SWEEP) ELBOW

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FIGURE 29: Dimensions

 

 

 

 

 

 

 

 

 

 

TABLE 8: Elbow Dimensions

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Elbow "A" Dimension

 

 

 

 

 

 

 

 

 

 

2" Standard

 

 

 

2-5/16"

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3" Standard

 

 

 

3-1/16"

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2" Sweep

 

 

 

3-1/4"

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3" Sweep

 

 

 

4-1/16"

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Dimensions are those required in Standard ASTM D-3311.

TABLE 9: Equivalent Length of Fittings

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fitting

 

 

 

 

 

Equivalent Length

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2" 90° sweep elbow

 

 

 

 

 

5 feet of 2" pipe

 

 

2" 45° sweep elbow

 

 

 

 

 

2-1/2 feet of 2" pipe

2" 90° standard elbow

 

 

 

 

 

7 feet of 2" pipe

2" 45° standard elbow

 

 

 

 

 

3-1/2 feet of 2" pipe

 

 

3" 90° sweep elbow

 

 

 

 

 

5 feet of 3" pipe

 

 

3" 45° sweep elbow

 

 

 

 

 

2-1/2 feet of 3" pipe

3" 90° standard elbow

 

 

 

 

 

7 feet of 3" pipe

3" 45° standard elbow

 

 

 

 

 

3-1/2 feet of 3" pipe

4" 90° elbow (sweep or standard)

 

 

 

 

 

5 feet of 4" pipe

4" 45° elbow (sweep or standard)

 

 

 

 

 

2-1/2 feet of 4" pipe

2" corrugated connector

 

 

 

 

 

10 feet of 2" pipe

3" corrugated connector

 

 

 

 

 

10 feet of 3" pipe

4" corrugated connector

 

 

 

 

 

10 feet of 4" pipe

Example:

An 80,000 BTUH furnace requires 32 feet of pipe and five 90º elbows. Using 2" pipe and standard elbows, the total equivalent length will be:

32 feet of 2" pipe =

32 equivalent feet

5 - 90º standard 2" elbows = (5 x 7) =

35 equivalent feet

Total =

67 equivalent feet of 2" pipe

This exceeds the 65 foot maximum equivalent length of 2" pipe allowed for that model and is thus not acceptable.

By using sweep elbows, the total equivalent length will be:

32 feet of 2" pipe =

32 equivalent feet

5 - 90º sweep 2" elbows = (5 x 5) =

25 equivalent feet

Total =

57 equivalent feet of 2" pipe

This is less than the 65 foot maximum equivalent length of 2" pipe allowed for that model and is thus acceptable.

Alternatively, using 3" pipe and standard elbows, the total equivalent length will be:

32 feet of 3" pipe =

32 equivalent feet

5 - 90º standard 3" elbows = (5 x 7) =

35 equivalent feet

Total =

67 equivalent feet of 3" pipe

This is less than the 90 foot maximum equivalent length of 3" pipe allowed for that model and is thus acceptable.

TABLE 10: Combustion Air Intake and Vent Connection Size at Furnace (All Models)

FURNACE VENT CONNECTION SIZES

Furnace Input

All

Intake Pipe Size

2” (5.1 cm)

Vent Pipe Size

2” (5.1 cm)

Furnace vent pipe connections are sized for 2” (5.1 cm). pipe. Any pipe size change must be made outside the furnace casing in a verti- cal pipe section to allow proper drainage of condensate. An offset using two 45º (degree) elbows will be required for plenum clearance when the vent is increased to 3” (7.6 cm).

Accessory concentric vent / intake termination kits 1CT0302 and 1CT0303, and for Canadian applications 1CT0302-636 and 1CT0303-636 are available and approved for use with these fur- naces. Horizontal sidewall vent terminations kits 1HT0901 & 1HT0902 are also approved for use with these furnaces.

COMBUSTION AIR AND VENT PIPING ASSEMBLY

The final assembly procedure for the combustion air and vent piping is as follows:

1.Cut piping to the proper length beginning at the furnace.

2.Deburr the piping inside and outside.

3.Chamfer (bevel) the outer edges of the piping.

4.Dry-fit the vent piping assembly from the furnace to the outside ter- mination checking for proper fit support and slope.

5.Dry-fit the combustion air piping assembly checking for proper fit, support and slope on the following systems:

a.Sealed combustion air systems from the furnace to the out- side termination.

b.Ventilated combustion air systems from the furnace to the attic or crawl space termination.

Solvent cements are flammable and must be used in well-ventilated areas only. Keep them away from heat, sparks and open flames. Do not breathe vapors and avoid contact with skin and eyes.

6.Disassemble the combustion air and vent piping, apply cement primer and the cement per the manufactures instructions. Primer and cement must conform to ASTM D2564 for PVC, or ASTM D2235 for ABS piping.

7.All joints must provide a permanent airtight and watertight seal.

8.Support the combustion air and vent piping such that it is angled a minimum of 1/4” per foot (21 mm/m) so that condensate will flow back towards the furnace. Piping should be supported with pipe hangers to prevent sagging.

9.Seal around the openings where the combustion air and / or vent piping pass through the roof or sidewalls.

COMBUSTION AIR / VENTING

The vent must be installed with the minimum required clearances, and must comply with local codes and requirements.

Johnson Controls Unitary Products

23

Image 23
Contents 95.5% AFUE Single Stage Multi-position INSTALLATION MANUALRESIDENTIAL GAS FURNACE MODELS TG9S*MP, GG9S*MP364861-UIM-H-0712 SECTION I SAFETYSPECIFIC SAFETY RULES AND PRECAUTIONS SAFETY REQUIREMENTS364861-UIM-H-0712 STEP 1 - SafetySTEP 2 - General Installation STEP 6 - Gas Piping and Gas Pipe Pressure TestingINSPECTION Clearances for access/serviceInstallation in a residential garage 364861-UIM-H-0712SECTION II DUCTWORK FLOOR BASE AND DUCTWORK INSTALLATION - DOWNFLOWThe duct system’s design and installation must installedCOIL FLANGE INSTALLATION COIL INSTALLATIONCOIL/FURNACE ASSEMBLY - MC/FC/PC SERIES COILS FURNACE ASSEMBLY - MC & FC SERIES COILSDIMENSION “C” INCH DOWNFLOW DUCT CONNECTORSCOIL / FURNACE ASSEMBLY - HC SERIES COILS BOTTOM RETURN AND ATTIC INSTALLATIONSDOWNFLOW APPLICATION ATTIC INSTALLATIONSUSPENDED FURNACE / CRAWL SPACE INSTALLATION 364861-UIM-H-0712attempt to install filters inside the furnace FILTER INSTALLATIONFIGURE 13 Dimensions Cabinet Dimensions InchesSECTION IV GAS PIPING DANGERGAS SAFETY GAS PIPING INSTALLATIONDANGER SECTION V ELECTRICAL POWERHIGH ALTITUDE PRESSURE SWITCH CONVERSION ELECTRICAL POWER CONNECTIONSInput LOW VOLTAGE CONTROL WIRING CONNECTIONS364861-UIM-H-0712 SUPPLY VOLTAGE CONNECTIONSJohnson Controls Unitary Products AC 5D364861-UIM-H-0712 364861-UIM-H-0712 HP 2CSingle Stage Heat Pump - Single Stage PSC Furnace 364861-UIM-H-0712 ACCESSORY CONNECTIONSELECTRONIC AIR CLEANER CONNECTION SECTION VI TWINNING AND STAGINGSTAGING 364861-UIM-H-0712Twinning Operation Staging OperationOpen Stand Pipe Anti-siphonair vent 5” Min Tee 364861-UIM-H-0712CONDENSATE DRAIN TERMINATION Johnson Controls Unitary ProductsUPFLOW pressure switch hose1 pressure switchhose INDUCER ROTATED FOR RIGHT SIDE VENTINGDOWNFLOW - INDUCER ROTATED FOR RIGHT SIDE VENTING AIRFLOW AIRFLOWDOWNFLOW - INDUCER ROTATED FOR LEFT SIDE VENTING AIRFLOW HORIZONTAL - LEFT INDUCER ROTATEDHORIZONTAL - LEFT INDUCER AS RECEIVED Except for 130K ModelHORIZONTAL - RIGHT Move pressure switch hose to this position1Move pressure switch hose to this position HORIZONTAL - RIGHT INDUCER ROTATEDCOMBUSTION AIR/VENT PIPE SIZING COMBUSTION AIR AND VENT SAFETYSECTION VIII COMBUSTION AIR AND VENT SYSTEM 364861-UIM-H-0712364861-UIM-H-0712 COMBUSTION AIR AND VENT PIPING ASSEMBLYFIGURE 29 Dimensions Elbow A DimensionVENT CLEARANCES Canadian Installations1,3US Installation2,3 364861-UIM-H-0712VENTING MULTIPLE UNITS 364861-UIM-H-0712VENT SYSTEM VENT APPLICATIONS AND TERMINATIONOutdoor Combustion Air 364861-UIM-H-0712DOWNWARD VENTING COMBUSTION AIR SUPPLYCombustion Air Source From Outdoors 364861-UIM-H-0712Ambient Combustion Air Supply Dampers, Louvers and Grilles Canada OnlyVentilated Combustion Air Termination 364861-UIM-H-0712Air Supply Openings and Ducts Ventilated Combustion AirVENT BLOWER ROTATION SECTION IX START-UPAND ADJUSTMENTSSpecially Engineered Installations 364861-UIM-H-0712HOT SURFACE IGNITION SYSTEM 364861-UIM-H-0712IGNITION SYSTEM SEQUENCE CALCULATING THE FURNACE INPUT NAT. GAS1 Cu Ft 364861-UIM-H-0712Johnson Controls Unitary Products 1 RevolutionRead the manifold gas pressure ADJUSTMENT OF MANIFOLD GAS PRESSURE & INPUT RATE364861-UIM-H-0712 Read the inlet gas pressure364861-UIM-H-0712 ADJUSTMENT OF TEMPERATURE RISEADJUSTMENT OF FAN CONTROL SETTINGS DANGERBottom Airflow Data SCFM 364861-UIM-H-0712Johnson Controls Unitary Products 364861-UIM-H-0712ROLLOUT SWITCH CONTROLS SECTION X SAFETY CONTROLSSECTION XI NORMAL OPERATION AND DIAGNOSTICS BLOWER DOOR SAFETY SWITCHJohnson Controls Unitary Products FURNACE CONTROL DIAGNOSTICS364861-UIM-H-0712 364861-UIM-H-0712 SECTION XII REPLACEMENT PARTS LISTREPLACEMENT PART CONTACT INFORMATION DIAGNOSTIC FAULT CODE STORAGE AND RETRIEVALJohnson Controls Unitary Products Wiring Diagram - 95% Single-StageFurnaceSECTION XIII WIRING DIAGRAMNorman, OK York International Corp 5005 York Drive