Johnson Controls TG9S'MP UIM-H-0712, Adjustment Of Manifold Gas Pressure & Input Rate, Gas Valve

Page 32
ADJUSTMENT OF MANIFOLD GAS PRESSURE & INPUT RATE

364861-UIM-H-0712

ADJUSTMENT OF MANIFOLD GAS PRESSURE & INPUT RATE

Inlet and manifold gas pressure may be measured by connecting the “U” tube manometer to the gas valve with a piece of tubing. Follow the appropriate section in the instructions below. Refer to Figure 40 for a drawing of the locations of the pressure ports on the gas valve.

Turn gas off at the ball valve or gas cock on gas supply line before the gas valve. Find the pressure ports on the gas valve marked Out P and In P.

1.The manifold pressure must be taken at the port marked OUT P.

2.The gas line pressure must be taken at the port marked IN P.

3.Using a 3/32” (2.4 mm) Allen wrench, loosen the set screw by turn- ing it 1 turn counter clockwise. DO NOT REMOVE THE SET SCREW FROM THE PRESSURE PORT.

Read the inlet gas pressure

Connect the positive side of the manometer to the IN P Tap on the gas valve. Do not connect any tubing to the negative side of the manometer, as it will reference atmospheric pressure. Refer to Figure 41 for connec- tion details.

1.Turn gas and electrical supplies on and follow the operating instruc- tions to place the unit back in operation.

Table 15: Inlet Gas Pressure Range

INLET GAS PRESSURE RANGE

Natural Gas

Propane (LP)

The cap for the pressure regulator must be removed entirely to gain access to the adjustment screw. Loosening or tightening the cap does not adjust the flow of gas.

NOTICE

The regulated outlet pressure has been calibrated at the factory. Additional pressure adjustment should not be necessary. If adjust- ment is necessary, set to the following specifications. After adjust- ment, check for gas leakage.

1.Refer to Figure 40 for location of pressure regulator adjustment cap and adjustment screws on main gas valve.

2.Turn gas and electrical supplies on and follow the operating instruc- tions to place the unit back in operation.

3.Adjust manifold pressure by adjusting gas valve regulator screw for the appropriate gas per the following:

Table 16: Nominal Manifold Pressure

NOMINAL MANIFOLD PRESSURE

Natural Gas

3.5" w.c. (0.87 kPa)

Propane (LP) Gas

10.0" w.c. (2.488 kPa)

Minimum

4.5” w.c. (1.12 kPa)

8.0” w.c. (1.99 kPa)

Maximum

10.5” w.c. (2.61 kPa)

13.0” w.c. (3.24 kPa).

The inlet gas pressure operating range table specifies what the mini- mum and maximum gas line pressures must be for the furnace to operate safely. The gas line pressure MUST BE a minimum of:

• 7” w.c. (1.74 kPA) for Natural Gas

OUTLET

PRESSURE

PORT

INLET Read the inlet gas pressure

WRENCH BOSS INLET

PRESSURE PORT

 

VENT PORT

 

OUTLET

OFF

 

ON

MAIN REGULATOR

ON/OFF SWITCH

ADJUSTMENT

 

(Shown in ON position)

 

• 11” w.c. (2.74 kPA) for Propane (LP) Gas

in order to obtain the BTU input specified on the rating plate and/or the nominal manifold pressure specified in these instructions and on the rating plate.

2.Once the correct gas inlet pressure has been established, see Table 15, turn the gas valve to OFF and turn the electrical supply switch to OFF; then remove the flexible tubing from the gas valve pressure tap and tighten the pressure tap plug using the 3/32” (2.4 mm) Allen wrench.

3.Turn the electrical and gas supplies back on, and with the burners in operation, check for gas leakage around the gas valve pressure port for leakage using an approved non-corrosive gas leak detec- tion fluid, or other non-flammable leak detection methods.

Read the manifold gas pressure

Connect the positive side of the manometer to the adapter previously installed in the OUT P Tap on the gas valve. Do not connect any tubing to the negative side of the manometer, as it will reference atmospheric pressure. Refer to Figure 41 for connection details.

FIGURE 41: Gas Valve

If gas valve regulator is turned in (clockwise), manifold pressure is increased. If screw is turned out (counterclockwise), manifold pres- sure will decrease.

4.After the manifold pressure has been adjusted, re-calculate the fur- nace input to make sure you have not exceeded the specified input on the rating plate. Refer to “CALCULATING THE FURNACE INPUT (NATURAL GAS)”.

5.Once the correct BTU (kW) input has been established, turn the gas valve to OFF and turn the electrical supply switch to OFF; then remove the flexible tubing from the gas valve pressure tap and tighten the pressure tap plug using the 3/32” (2.4 mm) Allen wrench.

6.Turn the electrical and gas supplies back on, and with the burners in operation, check for gas leakage around the gas valve pressure port for leakage using an approved non-corrosive gas leak detec- tion fluid, or other non-flammable leak detection methods.

32

Johnson Controls Unitary Products

Image 32
Contents INSTALLATION MANUAL RESIDENTIAL GAS FURNACEMODELS TG9S*MP, GG9S*MP 95.5% AFUE Single Stage Multi-positionSECTION I SAFETY SPECIFIC SAFETY RULES AND PRECAUTIONSSAFETY REQUIREMENTS 364861-UIM-H-0712STEP 1 - Safety STEP 2 - General InstallationSTEP 6 - Gas Piping and Gas Pipe Pressure Testing 364861-UIM-H-0712Clearances for access/service Installation in a residential garage364861-UIM-H-0712 INSPECTIONFLOOR BASE AND DUCTWORK INSTALLATION - DOWNFLOW The duct system’s design and installation mustinstalled SECTION II DUCTWORKCOIL INSTALLATION COIL/FURNACE ASSEMBLY - MC/FC/PC SERIES COILSFURNACE ASSEMBLY - MC & FC SERIES COILS COIL FLANGE INSTALLATIONDOWNFLOW DUCT CONNECTORS COIL / FURNACE ASSEMBLY - HC SERIES COILSBOTTOM RETURN AND ATTIC INSTALLATIONS DIMENSION “C” INCHATTIC INSTALLATION SUSPENDED FURNACE / CRAWL SPACE INSTALLATION364861-UIM-H-0712 DOWNFLOW APPLICATIONFILTER INSTALLATION FIGURE 13 DimensionsCabinet Dimensions Inches attempt to install filters inside the furnaceDANGER GAS SAFETYGAS PIPING INSTALLATION SECTION IV GAS PIPINGSECTION V ELECTRICAL POWER HIGH ALTITUDE PRESSURE SWITCH CONVERSIONELECTRICAL POWER CONNECTIONS DANGERLOW VOLTAGE CONTROL WIRING CONNECTIONS 364861-UIM-H-0712SUPPLY VOLTAGE CONNECTIONS InputJohnson Controls Unitary Products AC 5D364861-UIM-H-0712 364861-UIM-H-0712 HP 2CSingle Stage Heat Pump - Single Stage PSC Furnace ACCESSORY CONNECTIONS ELECTRONIC AIR CLEANER CONNECTIONSECTION VI TWINNING AND STAGING 364861-UIM-H-0712364861-UIM-H-0712 Twinning OperationStaging Operation STAGING364861-UIM-H-0712 CONDENSATE DRAIN TERMINATIONJohnson Controls Unitary Products Open Stand Pipe Anti-siphonair vent 5” Min Teepressure switch hose 1 pressure switchhoseINDUCER ROTATED FOR RIGHT SIDE VENTING UPFLOWDOWNFLOW - INDUCER ROTATED FOR RIGHT SIDE VENTING AIRFLOW AIRFLOWDOWNFLOW - INDUCER ROTATED FOR LEFT SIDE VENTING HORIZONTAL - LEFT INDUCER ROTATED HORIZONTAL - LEFTINDUCER AS RECEIVED Except for 130K Model AIRFLOWMove pressure switch hose to this position 1Move pressure switch hose to this positionHORIZONTAL - RIGHT INDUCER ROTATED HORIZONTAL - RIGHTCOMBUSTION AIR AND VENT SAFETY SECTION VIII COMBUSTION AIR AND VENT SYSTEM364861-UIM-H-0712 COMBUSTION AIR/VENT PIPE SIZINGCOMBUSTION AIR AND VENT PIPING ASSEMBLY FIGURE 29 DimensionsElbow A Dimension 364861-UIM-H-0712Canadian Installations1,3 US Installation2,3364861-UIM-H-0712 VENT CLEARANCES364861-UIM-H-0712 VENT SYSTEMVENT APPLICATIONS AND TERMINATION VENTING MULTIPLE UNITS364861-UIM-H-0712 DOWNWARD VENTINGCOMBUSTION AIR SUPPLY Outdoor Combustion Air364861-UIM-H-0712 Ambient Combustion Air SupplyDampers, Louvers and Grilles Canada Only Combustion Air Source From Outdoors364861-UIM-H-0712 Air Supply Openings and DuctsVentilated Combustion Air Ventilated Combustion Air TerminationSECTION IX START-UPAND ADJUSTMENTS Specially Engineered Installations364861-UIM-H-0712 VENT BLOWER ROTATION364861-UIM-H-0712 IGNITION SYSTEM SEQUENCECALCULATING THE FURNACE INPUT NAT. GAS HOT SURFACE IGNITION SYSTEM364861-UIM-H-0712 Johnson Controls Unitary Products1 Revolution 1 Cu FtADJUSTMENT OF MANIFOLD GAS PRESSURE & INPUT RATE 364861-UIM-H-0712Read the inlet gas pressure Read the manifold gas pressureADJUSTMENT OF TEMPERATURE RISE ADJUSTMENT OF FAN CONTROL SETTINGSDANGER 364861-UIM-H-0712364861-UIM-H-0712 Bottom Airflow Data SCFM364861-UIM-H-0712 Johnson Controls Unitary ProductsSECTION X SAFETY CONTROLS SECTION XI NORMAL OPERATION AND DIAGNOSTICSBLOWER DOOR SAFETY SWITCH ROLLOUT SWITCH CONTROLSJohnson Controls Unitary Products FURNACE CONTROL DIAGNOSTICS364861-UIM-H-0712 SECTION XII REPLACEMENT PARTS LIST REPLACEMENT PART CONTACT INFORMATIONDIAGNOSTIC FAULT CODE STORAGE AND RETRIEVAL 364861-UIM-H-0712Wiring Diagram - 95% Single-StageFurnace SECTION XIII WIRINGDIAGRAM Johnson Controls Unitary ProductsYork International Corp 5005 York Drive Norman, OK