Johnson Controls GG9S'MP Section Ii Ductwork, UIM-H-0712, Ductwork General Information, Factory

Page 5
SECTION II: DUCTWORK

364861-UIM-H-0712

SECTION II: DUCTWORK

DUCTWORK GENERAL INFORMATION

The duct system’s design and installation must:

1.Handle an air volume appropriate for the served space and within the operating parameters of the furnace specifications.

2.Be installed in accordance of National Fire Protection Association as outlined in NFPA standard 90B (latest editions) or applicable national, provincial, state, and local fire and safety codes.

3.Create a closed duct system. For residential and non-HUD Modular Home installations, when a furnace is installed so that the supply ducts carry air circulated by the furnace to areas outside the space containing the furnace, the return air shall also be handled by a duct(s) sealed to the furnace casing and terminating outside the space containing the furnace.

4.Complete a path for heated or cooled air to circulate through the air conditioning and heating equipment and to and from the condi- tioned space.

The cooling coil must be installed in the supply air duct, downstream of the furnace. Cooled air may not be passed over the heat exchanger.

When the furnace is used with a cooling coil, the coil must be installed parallel with, or in the supply air side of the furnace to avoid condensa- tion in the primary heat exchanger. When a parallel flow arrangement is used, dampers or other means used to control airflow must be ade- quate to prevent chilled air from entering the furnace. If manually oper- ated, the damper must be equipped with means to prevent the furnace or the air conditioner from operating unless the damper is in full heat or cool position.

When replacing an existing furnace, if the existing plenum is not the same size as the new furnace then the existing plenum must be removed and a new plenum installed that is the proper size for the new furnace. If the plenum is shorter than 12” (30.5 cm) the turbulent air flow may cause the limit controls not to operate as designed, or the limit con- trols may not operate at all.

The duct system is a very important part of the installation. If the duct system is improperly sized the furnace will not operate properly. The ducts attached to the furnace plenum, should be of sufficient size so that the furnace operates at the specified external static pressure and within the air temperature rise specified on the nameplate.

The minimum plenum height is 12” (30.5 cm). The furnace will not operate properly on a shorter plenum height. The minimum recom- mended rectangular duct height is 4” (10.1 cm) attached to the ple- num.

If a matching cooling coil is used, it may be placed directly on the fur- nace outlet and sealed to prevent leakage. If thermoplastic evaporator ‘A’ coil drain pans are to be installed in the upflow/horizontal configura- tion, then extra 2” minimum spacing may be needed to ensure against drain pan distortion.

On all installations without a coil, a removable access panel is recom- mended in the outlet duct such that smoke or reflected light would be observable inside the casing to indicate the presence of leaks in the heat exchanger. This access cover shall be attached in such a manner as to prevent leaks.

The duct system must be properly sized to obtain the correct airflow for the furnace size that is being installed.

Refer to Table 6 or the furnace rating plate for the correct rise range and static pressures.

If the ducts are undersized, the result will be high duct static pres- sures and/or high temperature rises which can result in a heat exchanger OVERHEATING CONDITION. This condition can result in premature heat exchanger failure, which can result in personal injury, property damage, or death.

DUCT FLANGES

Four flanges are provided to attach ductwork to the furnace. These flanges are rotated down for shipment. In order to use the flanges, remove the screw holding an individual flange, rotate the flange so it is in the upward position and reinstall the screw then repeat this for all 4 flanges.

If the flanges are not used, they must remain in the rotated down posi- tion as shipped.

For duct attachment,
Factory
if needed.
installed

FIGURE 1: Duct Attachment

DUCTWORK INSTALLATION AND SUPPLY PLENUM CONNECTION - UPFLOW/HORIZONTAL

Attach the supply plenum to the furnace outlet. The use of an approved flexible duct connector is recommended on all installations. This connection should be sealed to prevent air leakage. The sheet metal should be crosshatched to eliminate any popping of the sheet metal when the indoor fan is energized.

FLOOR BASE AND DUCTWORK INSTALLATION - DOWNFLOW

Installations on combustible material or directly on any floors must use a combustible floor base shown in Figure 8. Follow the instructions supplied with the combustible floor base accessory. This combustible floor base can be replaced with a matching cooling coil, properly sealed to

DUCTWORK GENERAL INFORMATIONThe duct system’s design and installation must: prevent leaks. Follow the instructions supplied with the cooling coil cabinet for installing the cabinet to the duct con- nector. Plug intake and vent pipe holes in bottom panel and move grom-

met to desired vent side exit.

Downflow Air Conditioning Coil Cabinet

The furnace should be installed with coil cabinet part number specifi- cally intended for downflow application. If a matching cooling coil is used, it may be placed directly on the furnace outlet and sealed to pre- vent leakage. For details of the coil cabinet dimensions and installation requirements, refer to the installation instructions supplied with the coil cabinet.

Attach the air conditioning coil cabinet to the duct connector, and then position the furnace on top of the coil cabinet. The connection to the fur- nace, air conditioning coil cabinet, duct connector, and supply air duct must be sealed to prevent air leakage.

Johnson Controls Unitary Products

5

Image 5
Contents RESIDENTIAL GAS FURNACE INSTALLATION MANUALMODELS TG9S*MP, GG9S*MP 95.5% AFUE Single Stage Multi-positionSPECIFIC SAFETY RULES AND PRECAUTIONS SECTION I SAFETYSAFETY REQUIREMENTS 364861-UIM-H-0712STEP 2 - General Installation STEP 1 - SafetySTEP 6 - Gas Piping and Gas Pipe Pressure Testing 364861-UIM-H-0712Installation in a residential garage Clearances for access/service364861-UIM-H-0712 INSPECTIONThe duct system’s design and installation must FLOOR BASE AND DUCTWORK INSTALLATION - DOWNFLOWinstalled SECTION II DUCTWORKCOIL/FURNACE ASSEMBLY - MC/FC/PC SERIES COILS COIL INSTALLATIONFURNACE ASSEMBLY - MC & FC SERIES COILS COIL FLANGE INSTALLATIONCOIL / FURNACE ASSEMBLY - HC SERIES COILS DOWNFLOW DUCT CONNECTORSBOTTOM RETURN AND ATTIC INSTALLATIONS DIMENSION “C” INCHSUSPENDED FURNACE / CRAWL SPACE INSTALLATION ATTIC INSTALLATION364861-UIM-H-0712 DOWNFLOW APPLICATIONFIGURE 13 Dimensions FILTER INSTALLATIONCabinet Dimensions Inches attempt to install filters inside the furnaceGAS SAFETY DANGERGAS PIPING INSTALLATION SECTION IV GAS PIPINGHIGH ALTITUDE PRESSURE SWITCH CONVERSION SECTION V ELECTRICAL POWERELECTRICAL POWER CONNECTIONS DANGER364861-UIM-H-0712 LOW VOLTAGE CONTROL WIRING CONNECTIONSSUPPLY VOLTAGE CONNECTIONS InputJohnson Controls Unitary Products AC 5D364861-UIM-H-0712 364861-UIM-H-0712 HP 2CSingle Stage Heat Pump - Single Stage PSC Furnace ELECTRONIC AIR CLEANER CONNECTION ACCESSORY CONNECTIONSSECTION VI TWINNING AND STAGING 364861-UIM-H-0712Twinning Operation 364861-UIM-H-0712Staging Operation STAGINGCONDENSATE DRAIN TERMINATION 364861-UIM-H-0712Johnson Controls Unitary Products Open Stand Pipe Anti-siphonair vent 5” Min Tee1 pressure switchhose pressure switch hoseINDUCER ROTATED FOR RIGHT SIDE VENTING UPFLOWDOWNFLOW - INDUCER ROTATED FOR RIGHT SIDE VENTING AIRFLOW AIRFLOWDOWNFLOW - INDUCER ROTATED FOR LEFT SIDE VENTING HORIZONTAL - LEFT HORIZONTAL - LEFT INDUCER ROTATEDINDUCER AS RECEIVED Except for 130K Model AIRFLOW1Move pressure switch hose to this position Move pressure switch hose to this positionHORIZONTAL - RIGHT INDUCER ROTATED HORIZONTAL - RIGHTSECTION VIII COMBUSTION AIR AND VENT SYSTEM COMBUSTION AIR AND VENT SAFETY364861-UIM-H-0712 COMBUSTION AIR/VENT PIPE SIZINGFIGURE 29 Dimensions COMBUSTION AIR AND VENT PIPING ASSEMBLYElbow A Dimension 364861-UIM-H-0712US Installation2,3 Canadian Installations1,3364861-UIM-H-0712 VENT CLEARANCESVENT SYSTEM 364861-UIM-H-0712VENT APPLICATIONS AND TERMINATION VENTING MULTIPLE UNITSDOWNWARD VENTING 364861-UIM-H-0712COMBUSTION AIR SUPPLY Outdoor Combustion AirAmbient Combustion Air Supply 364861-UIM-H-0712Dampers, Louvers and Grilles Canada Only Combustion Air Source From OutdoorsAir Supply Openings and Ducts 364861-UIM-H-0712Ventilated Combustion Air Ventilated Combustion Air TerminationSpecially Engineered Installations SECTION IX START-UPAND ADJUSTMENTS364861-UIM-H-0712 VENT BLOWER ROTATIONIGNITION SYSTEM SEQUENCE 364861-UIM-H-0712CALCULATING THE FURNACE INPUT NAT. GAS HOT SURFACE IGNITION SYSTEMJohnson Controls Unitary Products 364861-UIM-H-07121 Revolution 1 Cu Ft364861-UIM-H-0712 ADJUSTMENT OF MANIFOLD GAS PRESSURE & INPUT RATERead the inlet gas pressure Read the manifold gas pressureADJUSTMENT OF FAN CONTROL SETTINGS ADJUSTMENT OF TEMPERATURE RISEDANGER 364861-UIM-H-0712Bottom Airflow Data SCFM 364861-UIM-H-0712Johnson Controls Unitary Products 364861-UIM-H-0712SECTION XI NORMAL OPERATION AND DIAGNOSTICS SECTION X SAFETY CONTROLSBLOWER DOOR SAFETY SWITCH ROLLOUT SWITCH CONTROLSJohnson Controls Unitary Products FURNACE CONTROL DIAGNOSTICS364861-UIM-H-0712 REPLACEMENT PART CONTACT INFORMATION SECTION XII REPLACEMENT PARTS LISTDIAGNOSTIC FAULT CODE STORAGE AND RETRIEVAL 364861-UIM-H-0712SECTION XIII WIRING Wiring Diagram - 95% Single-StageFurnaceDIAGRAM Johnson Controls Unitary ProductsNorman, OK York International Corp 5005 York Drive