MANIFOLD PRESSURE “U” TUBE CONNECTION
| OUTLET |
| |
| PRESSURE TAP |
| |
GAS VALVE | 1/4” TUBING |
| |
|
|
| |
FLAME |
|
| MAINIFOLD |
|
| PIPE | |
SENSOR |
|
|
|
|
|
| 3.5 IN |
|
|
| WATER |
|
|
| COLUMN |
GAS |
|
| GAS |
| PRESSURE | ||
BURNERS |
| ||
| MANOMETER | SHOWN | |
|
|
FIGURE 42: Reading Gas Pressure
After about 5 minutes of operation, determine the furnace temperature rise. Take readings of both the return air and the heated air in the ducts, about six feet (1.8 m) from the furnace where they will not be affected by radiant heat. Increase the blower speed to decrease the temperature rise; decrease the blower speed to increase the rise.
All
Do not energize more than one motor speed at a time or damage to the motor will result.
ADJUSTMENT OF TEMPERATURE RISE
DANGER
The temperature rise, or temperature difference between the return air and the supply (heated) air from the furnace, must be within the range shown on the furnace rating plate and within the application limitations shown in Table 6.
The supply air temperature cannot exceed the “Maximum Supply Air Temperature” specified in these instructions and on the furnace rating plate. Under NO circumstances can the furnace be allowed to operate above the Maximum Supply Air Temperature. Operating the furnace above the Maximum Supply Air Temperature will cause pre- mature heat exchanger failure, high levels of Carbon Monoxide, a fire hazard, personal injury, property damage, and/or death.
ADJUSTMENT OF FAN CONTROL SETTINGS
This furnace is equipped with a
Blower Off Delay Timer Adjustment Jumper (in seconds)
TWIN |
|
|
|
|
|
|
| PARK | PARK |
180 | 120 | 90 | 60 | HI COOL |
| DELAY | BLOWER OFF |
| |
Y/Y2 |
| HEAT | ||
|
|
|
| |
W |
|
|
| |
|
|
|
| |
R |
|
|
|
|
G |
|
|
| L1 |
|
|
|
| |
C |
|
|
| XFMR |
|
|
|
| |
|
|
|
| NEUTRALS |
|
|
| HUM |
|
FIGURE 43: Furnace Control Board
Johnson Controls Unitary Products | 33 |