CARBON MONOXIDE POISONING HAZARD
Failure to follow the steps outlined below for each appliance connected to the venting system being placed into operation could result in carbon- monxide poisoning or death.
The following steps shall be followed for each appliance connected to the venting system being placed into operation, while all other appliances connected to the venting system are not in operation:
1.Inspect the venting system for proper size and horizontal pitch. Determine that there is no blockage, restriction, leakage, corrosion or other deficiencies, which could cause an unsafe condition.
2.Close all building doors and windows and all doors.
3.Turn on clothes dryers and TURN ON any exhaust fans, such as range hoods and bathroom exhausts, so they shall operate at maximum speed. Open the fireplace dampers. Do not operate a summer exhaust fan.
4.Follow the lighting instructions. Place the appliance being inspected in operation. Adjust thermostat so the appliance shall operate contin- uously.
5.Test each appliance (such as a water heater) equipped with a draft hood for spillage
6.After it has been determined that each appliance properly vents when tested as outlined above, return doors, windows, exhaust fans, fire- place dampers and any other gas burning appliance to their normal condition.
7.If improper venting is observed during any of the above tests, a problem exists with either the venting system or the appliance does not have enough combustion air (Supply Air from outside) to complete combustion. This condition must be corrected before the appliance can function safely.
NOTE: An unsafe condition exists when the CO reading exceeds 40 ppm and the draft reading is not in excess of - 0.1” w.c.
8.Any corrections to the venting system and / or to the supply (outside) air system must be in accordance with the National Fuel Gas Code Z223.1 or CAN/CGA B149.1 Natural Gas and Propane Installation Code (latest editions). If the vent system must be resized, follow the appropriate tables in Appendix G of the above codes or for this appliance.
Specially Engineered Installations
The above requirements shall be permitted to be waived where special engineering, approved by the authority having jurisdiction, provides an adequate supply of air for combustion and ventilation.
Be sure to instruct the owner not to block this intake pipe.
VENT BLOWER ROTATION
For ease of venting, the vent blower may be rotated 90° in either direc- tion. For upflow installations the vent may exit through the top or either side of the cabinet. For downflow installations, the vent blower must be rotated so that the vent exits through either side of the cabinet. See Fig- ures
SECTION IX: START-UP AND
ADJUSTMENTS
The initial
All electrical connections made in the field and in the factory should be checked for proper tightness.
When the gas supply is initially connected to the furnace, the gas piping may be full of air. In order to purge this air, it is recommended that the ground union be loosened until the odor of gas is detected. When gas is detected, immediately retighten the union and check for leaks. Allow five minutes for any gas to dissipate before continuing with the
GAS PIPING LEAK CHECK
FIRE OR EXPLOSION HAZARD
Failure to follow the safety warnings exactly could result in serious injury, death or property damage.
Never test for gas leaks with an open flame. Use a commercially available soap solution made specifically for the detection of leaks to check all connections. A fire or explosion may result causing property damage, personal injury or loss of life.
Burner ignition may not be satisfactory on first startup due to residual air in the gas line or until gas manifold pressure is adjusted. The igni- tion control will make three attempts to light before locking out.
It is recommended that when the gas supply is first connected to the furnace, the ground union be loosened until the odor of gas is detected. When gas is detected, immediately tighten the union and check for gas leaks. Allow five minutes for any gas to dissipate before continuing with the startup procedure. Be sure that proper ventilation is available to dilute and carry away any vented gas.
With furnace in operation, check all of the pipe joints, gas valve connec- tions and manual valve connections for leakage using an approved gas detector, a
The furnace and its equipment shutoff valve must be disconnected from the gas supply during any pressure testing of that system at test pres- sures in excess of 0.5 psig (3.45 kPa).
The furnace must be isolated from the gas supply piping system by closing the equipment shutoff valve during any pressure testing of the gas supply system.
Johnson Controls Unitary Products | 29 |