SECTION IV: GAS PIPING

GAS SAFETY

Front ofSECTION IV: GAS PIPINGDANGER

An overpressure protection device, such as a pressure regulator, must be installed in the gas piping system upstream of the furnace and must act to limit the downstream pressure to the gas valve so it does not exceed 0.5 psig [14" w.c. (3.48 kPa)]. Pressures exceeding

0.5psig [14” w.c. (3.48 kPa)] at the gas valve will cause damage to the gas valve, resulting in a fire or explosion or cause damage to the furnace or some of its components that will result in property damage and loss of life.

Install the side filter rack following the instructions provided with that accessory. If a filter(s) is provided at another location in the return air system, the ductwork may be directly attached to the furnace side panel.

Some accessories such as electronic air cleaners and pleated media may require a larger side opening. Follow the instructions supplied with that accessory for side opening requirements. Do not cut the opening larger than the dimensions shown in Figure 13.

OUTLET

PRESSURE

PORT

INLET GAS SAFETY

WRENCH BOSS INLET

PRESSURE PORT

FIGURE 15: Gas Valve

 

VENT PORT

 

OUTLET

OFF

 

ON

MAIN REGULATOR

ON/OFF SWITCH

ADJUSTMENT

 

(Shown in ON position)

 

HORIZONTAL APPLICATION

Horizontal Filters

All filters and mounting provision must be field supplied. All installa- tions must have a filter installed.

Any branch duct (rectangular or round duct) attached to the plenum must attach to the vertical plenum before the filter. The use of straps and/or supports is required to support the weight of the external filter box.

Downflow Filters

Downflow furnaces typically are installed with the filters located above the furnace, extending into the return air plenum or duct. Any branch duct (rectangular or round duct) attached to the plenum must attach to the vertical plenum above the filter height.

Filter(s) may be located in the duct system external to the furnace using an external duct filter box attached to the furnace plenum or at the end of the duct in a return filter grille(s). The use of straps and/or supports is required to support the weight of the external filter box.

Plan your gas supply before determining the correct gas pipe entry. Use 90° service elbow(s), or short nipples and conventional 90° elbow(s) to enter through the cabinet access holes.

GAS PIPING INSTALLATION

Properly sized wrought iron, approved flexible or steel pipe must be used when making gas connections to the unit. If local codes allow the use of a flexible gas appliance connection, always use a new listed con- nector. Do not use a connector that has previously serviced another gas appliance.

Some utility companies or local codes require pipe sizes larger than the minimum sizes listed in these instructions and in the codes. The furnace rating plate and the instructions in this section specify the type of gas approved for this furnace - only use those approved gases. The instal- lation of a drip leg and ground union is required. Refer to Figure 16.

To Gas

Supply

Ground

To Gas

NOTE: Ground Union maybe installed inside or outside unit.

 

Supply

 

External

 

 

 

 

 

Ground

 

External

 

Manual

To Gas

 

Union

 

Manual

Ground

Shut-off

 

Supply

 

 

 

 

 

 

Shut-off

 

Union

 

Valve

To Gas

 

 

 

 

Supply

 

To Gas

 

Valve

 

 

 

 

 

 

 

 

 

 

 

Supply

 

 

 

 

 

 

 

UnionDANGER

Drip

Leg

Gas

Valve

FIGURE 15: Gas Valve Gas

Pipe

Drip

Leg Ground

Union

Gas

 

 

Pipe

Drip

 

Upflow

Leg

Downflow

Drip Leg

External Manual

HORIZONTAL APPLICATION GroundShut-off Valve

Union

Gas

Valve

 

Gas

Gas

 

 

To Gas

 

Valve

 

 

Drip

Pipe

 

 

Supply

 

 

 

 

 

Leg

 

 

 

 

Ground

 

 

 

 

 

 

Horizontal

Drip

 

Union

 

 

 

 

FIGURE 16: Gas Piping

10

Johnson Controls Unitary Products

Image 10
Contents MODELS TG9S*MP, GG9S*MP INSTALLATION MANUALRESIDENTIAL GAS FURNACE 95.5% AFUE Single Stage Multi-positionSAFETY REQUIREMENTS SECTION I SAFETYSPECIFIC SAFETY RULES AND PRECAUTIONS 364861-UIM-H-0712STEP 6 - Gas Piping and Gas Pipe Pressure Testing STEP 1 - SafetySTEP 2 - General Installation 364861-UIM-H-0712364861-UIM-H-0712 Clearances for access/serviceInstallation in a residential garage INSPECTIONinstalled FLOOR BASE AND DUCTWORK INSTALLATION - DOWNFLOWThe duct system’s design and installation must SECTION II DUCTWORKFURNACE ASSEMBLY - MC & FC SERIES COILS COIL INSTALLATIONCOIL/FURNACE ASSEMBLY - MC/FC/PC SERIES COILS COIL FLANGE INSTALLATIONBOTTOM RETURN AND ATTIC INSTALLATIONS DOWNFLOW DUCT CONNECTORSCOIL / FURNACE ASSEMBLY - HC SERIES COILS DIMENSION “C” INCH364861-UIM-H-0712 ATTIC INSTALLATIONSUSPENDED FURNACE / CRAWL SPACE INSTALLATION DOWNFLOW APPLICATIONCabinet Dimensions Inches FILTER INSTALLATIONFIGURE 13 Dimensions attempt to install filters inside the furnaceGAS PIPING INSTALLATION DANGERGAS SAFETY SECTION IV GAS PIPINGELECTRICAL POWER CONNECTIONS SECTION V ELECTRICAL POWERHIGH ALTITUDE PRESSURE SWITCH CONVERSION DANGERSUPPLY VOLTAGE CONNECTIONS LOW VOLTAGE CONTROL WIRING CONNECTIONS364861-UIM-H-0712 Input364861-UIM-H-0712 AC 5DJohnson Controls Unitary Products Single Stage Heat Pump - Single Stage PSC Furnace HP 2C364861-UIM-H-0712 SECTION VI TWINNING AND STAGING ACCESSORY CONNECTIONSELECTRONIC AIR CLEANER CONNECTION 364861-UIM-H-0712Staging Operation 364861-UIM-H-0712Twinning Operation STAGINGJohnson Controls Unitary Products 364861-UIM-H-0712CONDENSATE DRAIN TERMINATION Open Stand Pipe Anti-siphonair vent 5” Min TeeINDUCER ROTATED FOR RIGHT SIDE VENTING pressure switch hose1 pressure switchhose UPFLOWDOWNFLOW - INDUCER ROTATED FOR LEFT SIDE VENTING AIRFLOW AIRFLOWDOWNFLOW - INDUCER ROTATED FOR RIGHT SIDE VENTING INDUCER AS RECEIVED Except for 130K Model HORIZONTAL - LEFT INDUCER ROTATEDHORIZONTAL - LEFT AIRFLOWHORIZONTAL - RIGHT INDUCER ROTATED Move pressure switch hose to this position1Move pressure switch hose to this position HORIZONTAL - RIGHT364861-UIM-H-0712 COMBUSTION AIR AND VENT SAFETYSECTION VIII COMBUSTION AIR AND VENT SYSTEM COMBUSTION AIR/VENT PIPE SIZINGElbow A Dimension COMBUSTION AIR AND VENT PIPING ASSEMBLYFIGURE 29 Dimensions 364861-UIM-H-0712364861-UIM-H-0712 Canadian Installations1,3US Installation2,3 VENT CLEARANCESVENT APPLICATIONS AND TERMINATION 364861-UIM-H-0712VENT SYSTEM VENTING MULTIPLE UNITSCOMBUSTION AIR SUPPLY 364861-UIM-H-0712DOWNWARD VENTING Outdoor Combustion AirDampers, Louvers and Grilles Canada Only 364861-UIM-H-0712Ambient Combustion Air Supply Combustion Air Source From OutdoorsVentilated Combustion Air 364861-UIM-H-0712Air Supply Openings and Ducts Ventilated Combustion Air Termination364861-UIM-H-0712 SECTION IX START-UPAND ADJUSTMENTSSpecially Engineered Installations VENT BLOWER ROTATIONCALCULATING THE FURNACE INPUT NAT. GAS 364861-UIM-H-0712IGNITION SYSTEM SEQUENCE HOT SURFACE IGNITION SYSTEM1 Revolution 364861-UIM-H-0712Johnson Controls Unitary Products 1 Cu FtRead the inlet gas pressure ADJUSTMENT OF MANIFOLD GAS PRESSURE & INPUT RATE364861-UIM-H-0712 Read the manifold gas pressureDANGER ADJUSTMENT OF TEMPERATURE RISEADJUSTMENT OF FAN CONTROL SETTINGS 364861-UIM-H-0712364861-UIM-H-0712 Bottom Airflow Data SCFM364861-UIM-H-0712 Johnson Controls Unitary ProductsBLOWER DOOR SAFETY SWITCH SECTION X SAFETY CONTROLSSECTION XI NORMAL OPERATION AND DIAGNOSTICS ROLLOUT SWITCH CONTROLS364861-UIM-H-0712 FURNACE CONTROL DIAGNOSTICSJohnson Controls Unitary Products DIAGNOSTIC FAULT CODE STORAGE AND RETRIEVAL SECTION XII REPLACEMENT PARTS LISTREPLACEMENT PART CONTACT INFORMATION 364861-UIM-H-0712DIAGRAM Wiring Diagram - 95% Single-StageFurnaceSECTION XIII WIRING Johnson Controls Unitary ProductsYork International Corp 5005 York Drive Norman, OK