Johnson Controls TG9S'MP UIM-H-0712, Twinning Operation, Staging Operation, Staging Instructions

Page 16
Twinning Operation

364861-UIM-H-0712

Twinning Operation

Heating - On a call for heat (W signal) from the wall thermostat, both furnaces will start the ignition sequence and the burners on both fur- naces will light. About thirty seconds after the burners light, the blowers on both furnaces will come on in heating speed. When the thermostat is satisfied, the burners will all shut off and, after the selected blower off delay time, both blowers will shut off at the same time. The twinning control ensures that both blowers come on and shut off at the same time.

Cooling - On a call for cooling (Y signal) from the wall thermostat, both furnace blowers will come on at the same time in cooling speed. When the thermostat is satisfied, both blowers will stay on for 60 seconds, then will shut off at the same time.

Continuous Fan - On a thermostat call for continuous fan (G signal), both furnace blowers will come on at the same time in cooling speed and will stay on until the G signal is removed.

FURNACE 1

FURNACE 2

CONTROL BOARD

CONTROL BOARD

Staging Operation

Heating - On a call for first-stage heat (W1 signal) from the wall thermo- stat, Furnace #1 will start the ignition sequence and the burners will light. About thirty seconds after the burners light, the blowers on both furnaces will come on in heating speed. When the thermostat is satis- fied, the burners will shut off and, after the selected blower off delay time, both blowers will shut off at the same time. On a call for second stage of heat, the burners of Furnace #2 will also light and both blowers will run. The twinning control ensures that both blowers come on and shut off at the same time.

Cooling - On a call for cooling (Y signal) from the wall thermostat, both furnace blowers will come on at the same time. When the thermostat is satisfied, both blowers will stay on for 60 seconds, then will shut off at the same time.

Continuous Fan - On a thermostat call for continuous fan (G signal), both furnace blowers will come on at the same time in cooling speed and will stay on until the G signal is removed.

W

G

Staging Operation W G

FURNACE 1

FURNACE 2

CONTROL BOARD

CONTROL BOARD

C

R

TWIN

Y

ISOLATION

 

 

RELAY

STAGING C

Staging Instructions R TWIN Y CONDENSATE DRAIN LOCATION

W

 

G

 

C

 

R

TWIN

Y

ISOLATION

 

 

RELAY

Manual background W

Manual background G

Manual background C

Manual background R TWIN Y Manual background

TO A/C

 

W G R Y

 

 

WALL THERMOSTAT

FIGURE 21: Twinning Wiring Diagram

STAGING

This control can also be used along with a two-stage wall thermostat to stage two twinned furnaces, making them operate like a single two- stage furnace. This allows only one furnace to supply heat during times when the heat output from one furnace is sufficient to satisfy the demand. When one duct system is used for two furnaces, it is neces- sary that the two blowers operate in unison. The twinning function of this board ensures that both blowers turn on and off simultaneously, and operate on the same blower speed. Even when only one furnace is supplying heat, both furnace blowers must run.

The twinning feature of this board can also be used for staging of two furnaces. With this feature, a single wire is connected between the TWIN terminal on one furnace board to the TWIN terminal on the sec- ond furnace board. The board then communicates the blower status from one furnace to the other along this wire. This communication makes the second furnace blower come on at the same time, and on the same speed, as the first furnace blower. To ensure stable communi- cation, the common terminal of each control must be connected.

Staging Instructions

Connect the control wiring as shown in Figure 22.

1.Connect the low voltage wiring from the wall thermostat to the ter- minal strip on the control board of Furnace #1. For staging applica- tions, the wire from thermostat W1 is connected to the W connection on the board on Furnace #1. The wire from thermostat W2 is connected to Furnace #2 through a separate relay, as described below.

TO A/C

 

 

 

 

W1 G R Y W2

 

WALL THERMOSTAT

FIGURE 22: Staging Wiring Diagram

SECTION VII: CONDENSATE PIPING AND FURNACE VENTING CONFIGURATION

CONDENSATE DRAIN LOCATION

As shipped from the factory:

For all 040, 060, & 080K input furnaces the main drain is plumbed through the casing right-side opening when viewed from the front of the furnace.

For all 100, 120, & 130K input furnaces the main drain is plumbed through the casing left-side opening when viewed from the front of the furnace.

NOTICE

The Figures 25 - 28 show the condensate drain arrangement for the various possible furnace and vent blower positions.

The condensate hoses must slope downwards at all points.

The furnace condensate pan is self priming and contains an internal trap to prevent flue gas leaking. Do not install an external condensate trap.

2.Connect a wire from the TWIN terminal of Furnace #1 to the TWIN terminal of Furnace #2.

3.Install a separate 24V relay as shown in the diagram below. Use of this relay is required, as it ensures that the transformers of the two furnaces are isolated, thus preventing the possibility of any safety devices being bypassed.

4.Connect the 24V common between furnace #1 and furnace #2.

When drain hose routing changes are required (shown in Figures 25 - 28), be sure to cap all un-used openings.

If rerouting hoses - excess length should be cut off so that no sagging loops will collect and hold condensate - which will cause the furnace to not operate.

No hose clamps are needed for connecting to the condensate pan.

16

Johnson Controls Unitary Products

Image 16
Contents INSTALLATION MANUAL RESIDENTIAL GAS FURNACEMODELS TG9S*MP, GG9S*MP 95.5% AFUE Single Stage Multi-positionSECTION I SAFETY SPECIFIC SAFETY RULES AND PRECAUTIONSSAFETY REQUIREMENTS 364861-UIM-H-0712STEP 1 - Safety STEP 2 - General InstallationSTEP 6 - Gas Piping and Gas Pipe Pressure Testing 364861-UIM-H-0712Clearances for access/service Installation in a residential garage364861-UIM-H-0712 INSPECTIONFLOOR BASE AND DUCTWORK INSTALLATION - DOWNFLOW The duct system’s design and installation mustinstalled SECTION II DUCTWORKCOIL INSTALLATION COIL/FURNACE ASSEMBLY - MC/FC/PC SERIES COILSFURNACE ASSEMBLY - MC & FC SERIES COILS COIL FLANGE INSTALLATIONDOWNFLOW DUCT CONNECTORS COIL / FURNACE ASSEMBLY - HC SERIES COILSBOTTOM RETURN AND ATTIC INSTALLATIONS DIMENSION “C” INCHATTIC INSTALLATION SUSPENDED FURNACE / CRAWL SPACE INSTALLATION364861-UIM-H-0712 DOWNFLOW APPLICATIONFILTER INSTALLATION FIGURE 13 DimensionsCabinet Dimensions Inches attempt to install filters inside the furnaceDANGER GAS SAFETYGAS PIPING INSTALLATION SECTION IV GAS PIPINGSECTION V ELECTRICAL POWER HIGH ALTITUDE PRESSURE SWITCH CONVERSIONELECTRICAL POWER CONNECTIONS DANGERLOW VOLTAGE CONTROL WIRING CONNECTIONS 364861-UIM-H-0712SUPPLY VOLTAGE CONNECTIONS Input364861-UIM-H-0712 AC 5DJohnson Controls Unitary Products Single Stage Heat Pump - Single Stage PSC Furnace HP 2C364861-UIM-H-0712 ACCESSORY CONNECTIONS ELECTRONIC AIR CLEANER CONNECTIONSECTION VI TWINNING AND STAGING 364861-UIM-H-0712364861-UIM-H-0712 Twinning OperationStaging Operation STAGING364861-UIM-H-0712 CONDENSATE DRAIN TERMINATIONJohnson Controls Unitary Products Open Stand Pipe Anti-siphonair vent 5” Min Teepressure switch hose 1 pressure switchhoseINDUCER ROTATED FOR RIGHT SIDE VENTING UPFLOWDOWNFLOW - INDUCER ROTATED FOR LEFT SIDE VENTING AIRFLOW AIRFLOWDOWNFLOW - INDUCER ROTATED FOR RIGHT SIDE VENTING HORIZONTAL - LEFT INDUCER ROTATED HORIZONTAL - LEFTINDUCER AS RECEIVED Except for 130K Model AIRFLOWMove pressure switch hose to this position 1Move pressure switch hose to this positionHORIZONTAL - RIGHT INDUCER ROTATED HORIZONTAL - RIGHTCOMBUSTION AIR AND VENT SAFETY SECTION VIII COMBUSTION AIR AND VENT SYSTEM364861-UIM-H-0712 COMBUSTION AIR/VENT PIPE SIZINGCOMBUSTION AIR AND VENT PIPING ASSEMBLY FIGURE 29 DimensionsElbow A Dimension 364861-UIM-H-0712Canadian Installations1,3 US Installation2,3364861-UIM-H-0712 VENT CLEARANCES364861-UIM-H-0712 VENT SYSTEMVENT APPLICATIONS AND TERMINATION VENTING MULTIPLE UNITS364861-UIM-H-0712 DOWNWARD VENTINGCOMBUSTION AIR SUPPLY Outdoor Combustion Air364861-UIM-H-0712 Ambient Combustion Air SupplyDampers, Louvers and Grilles Canada Only Combustion Air Source From Outdoors364861-UIM-H-0712 Air Supply Openings and DuctsVentilated Combustion Air Ventilated Combustion Air TerminationSECTION IX START-UPAND ADJUSTMENTS Specially Engineered Installations364861-UIM-H-0712 VENT BLOWER ROTATION364861-UIM-H-0712 IGNITION SYSTEM SEQUENCECALCULATING THE FURNACE INPUT NAT. GAS HOT SURFACE IGNITION SYSTEM364861-UIM-H-0712 Johnson Controls Unitary Products1 Revolution 1 Cu FtADJUSTMENT OF MANIFOLD GAS PRESSURE & INPUT RATE 364861-UIM-H-0712Read the inlet gas pressure Read the manifold gas pressureADJUSTMENT OF TEMPERATURE RISE ADJUSTMENT OF FAN CONTROL SETTINGSDANGER 364861-UIM-H-0712364861-UIM-H-0712 Bottom Airflow Data SCFM364861-UIM-H-0712 Johnson Controls Unitary ProductsSECTION X SAFETY CONTROLS SECTION XI NORMAL OPERATION AND DIAGNOSTICSBLOWER DOOR SAFETY SWITCH ROLLOUT SWITCH CONTROLS364861-UIM-H-0712 FURNACE CONTROL DIAGNOSTICSJohnson Controls Unitary Products SECTION XII REPLACEMENT PARTS LIST REPLACEMENT PART CONTACT INFORMATIONDIAGNOSTIC FAULT CODE STORAGE AND RETRIEVAL 364861-UIM-H-0712Wiring Diagram - 95% Single-StageFurnace SECTION XIII WIRINGDIAGRAM Johnson Controls Unitary ProductsYork International Corp 5005 York Drive Norman, OK