Johnson Controls GG9S'MP Section Iii Filters, UIM-H-0712, Filter Installation, Left Side, Front

Page 9
LEFT SIDE

364861-UIM-H-0712

LEFT SIDE

Combustion Air Inlet

Condensate Drain

Gas Pipe

(Downflow)

Entry

Vent Outlet

Electrical

 

Entry

 

Condensate

 

Drain

 

Thermostat

 

Wiring

28.5”

 

29.5”

 

(For Cladded door add appoximately an additional .75”)

FRONT

A

 

 

RIGHT SIDE

 

 

 

Combustion Air Inlet

 

 

Gas Pipe

Condensate Drain

 

 

Entry

(Downflow)

 

 

Electrical

 

 

 

Entry

Vent Outlet

 

33

Condensate

23”

 

 

Drain

 

 

 

 

 

Thermostat

Optional Return Air

 

 

Wiring

14”

 

Cutout (Either side)

 

 

 

 

 

 

 

 

1”

 

 

1.5”

 

.56”

23.8”

3”

 

 

 

Vent

 

 

Outlet

B

Combustion

 

Air Inlet

 

 

C

 

 

.56”

.56”

 

20”

 

 

 

SUPPLY END

B

24.25”

RETURN END
FIGURE 13: Dimensions

Table 3: Cabinet and Duct Dimensions

BTUH (kW)NominalCabinet

 

Cabinet Dimensions (Inches)

 

Approximate

 

 

Operating Weights

Input

CFM (m3/min)

Size

 

 

 

 

 

 

 

 

 

 

 

 

 

A (in)

A (cm)

B (in)

B (cm)

C (in)

C (cm)

Lbs (kg)

 

 

 

 

 

 

 

 

 

 

 

 

 

40 (11.7)

800 (22.7)

A

14 1/2

36.8

13 3/8

34.0

11 3/4

29.8

113 (51.3)

60 (17.6)

1000 (28.3)

A

14 1/2

36.8

13 3/8

34.0

11 3/4

29.8

118 (53.5)

60 (17.6)

1200 (34.0)

B

17 1/2

44.4

16 3/8

41.6

13 1/4

33.7

122 (55.3)

80 (23.4)

1200 (34.0)

B

17 1/2

44.4

16 3/8

41.6

14 3/4

37.5

126 (57.2)

80 (23.4)

1600 (45.3)

C

21

53.3

19 7/8

50.5

16 1/2

41.9

136 (61.7)

80 (23.4)

2200 (62.3)

C

21

53.3

19 7/8

50.5

16 1/2

41.9

139 (63.0)

100 (29.3)

1600 (45.3)

C

21

53.3

19 7/8

50.5

18 1/4

46.4

142 (64.4)

100 (29.3)

2000 (56.6)

C

21

53.3

19 7/8

50.5

18 1/4

46.4

145 (65.8)

120 (35.1)

1600 (45.3)

D

24 1/2

62.2

23 3/8

59.4

21 3/4

55.2

153 (69.4)

120 (35.1)

2000 (56.6)

D

24 1/2

62.2

23 3/8

59.4

21 3/4

55.2

156 (70.7)

130 (38.1)

2000 (56.6)

D

24 1/2

62.2

23 3/8

59.4

No Hole

No Hole

160 (72.5)

SECTION III: FILTERS

FILTER INSTALLATION

All applications require the use of a field installed filter. All filters and mounting provision must be field supplied.

Filters must be installed external to the furnace cabinet. DO NOT

attempt to install filters inside the furnace.

NOTICE

Single side return above 1800 CFM is approved as long as the filter velocity does not exceed filter manufacturer’s recommendation and a transition is used to allow use on a 20x25 filter.

Table 4: Recommended Filter Sizes (High Velocity 600 FPM)

CFM (m³/min)

Cabinet Size

Side (in)

Bottom (in)

800 (22.7)

A

16 x 25

14 x 25

1000 (28.3)

A

16 x 25

14 x 25

1200 (34.0)

A

16 x 25

14 x 25

1200 (34.0)

B

16 x 25

16 x 25

1600 (45.3)

B

16 x 25

16 x 25

1600 (45.3)

C

16 x 25

20 x 25

2000 (56.6)

C

(2) 16 x 25

20 x 25

2200 (62.3)

C

(2) 16 x 25

20 x 25

2000 (56.6)

D

(2) 16 x 25

22 x 25

1.Air velocity through throwaway type filters may not exceed 300 feet per min- ute (91.4 m/min). All velocities over this require the use of high velocity fil- ters.

2.Do not exceed 1800 CFM using a single side return and a 16x25 filter. For CFM greater than 1800, you may use two side returns or one side and the bottom or one side return with a transition to allow use of a 20x25 filter.

Johnson Controls Unitary Products

9

Image 9
Contents RESIDENTIAL GAS FURNACE INSTALLATION MANUALMODELS TG9S*MP, GG9S*MP 95.5% AFUE Single Stage Multi-positionSPECIFIC SAFETY RULES AND PRECAUTIONS SECTION I SAFETYSAFETY REQUIREMENTS 364861-UIM-H-0712STEP 2 - General Installation STEP 1 - SafetySTEP 6 - Gas Piping and Gas Pipe Pressure Testing 364861-UIM-H-0712Installation in a residential garage Clearances for access/service364861-UIM-H-0712 INSPECTIONThe duct system’s design and installation must FLOOR BASE AND DUCTWORK INSTALLATION - DOWNFLOWinstalled SECTION II DUCTWORKCOIL/FURNACE ASSEMBLY - MC/FC/PC SERIES COILS COIL INSTALLATIONFURNACE ASSEMBLY - MC & FC SERIES COILS COIL FLANGE INSTALLATIONCOIL / FURNACE ASSEMBLY - HC SERIES COILS DOWNFLOW DUCT CONNECTORSBOTTOM RETURN AND ATTIC INSTALLATIONS DIMENSION “C” INCHSUSPENDED FURNACE / CRAWL SPACE INSTALLATION ATTIC INSTALLATION364861-UIM-H-0712 DOWNFLOW APPLICATIONFIGURE 13 Dimensions FILTER INSTALLATIONCabinet Dimensions Inches attempt to install filters inside the furnaceGAS SAFETY DANGERGAS PIPING INSTALLATION SECTION IV GAS PIPINGHIGH ALTITUDE PRESSURE SWITCH CONVERSION SECTION V ELECTRICAL POWERELECTRICAL POWER CONNECTIONS DANGER364861-UIM-H-0712 LOW VOLTAGE CONTROL WIRING CONNECTIONSSUPPLY VOLTAGE CONNECTIONS InputAC 5D 364861-UIM-H-0712Johnson Controls Unitary Products HP 2C Single Stage Heat Pump - Single Stage PSC Furnace364861-UIM-H-0712 ELECTRONIC AIR CLEANER CONNECTION ACCESSORY CONNECTIONSSECTION VI TWINNING AND STAGING 364861-UIM-H-0712Twinning Operation 364861-UIM-H-0712Staging Operation STAGINGCONDENSATE DRAIN TERMINATION 364861-UIM-H-0712Johnson Controls Unitary Products Open Stand Pipe Anti-siphonair vent 5” Min Tee1 pressure switchhose pressure switch hoseINDUCER ROTATED FOR RIGHT SIDE VENTING UPFLOWAIRFLOW AIRFLOW DOWNFLOW - INDUCER ROTATED FOR LEFT SIDE VENTINGDOWNFLOW - INDUCER ROTATED FOR RIGHT SIDE VENTING HORIZONTAL - LEFT HORIZONTAL - LEFT INDUCER ROTATEDINDUCER AS RECEIVED Except for 130K Model AIRFLOW1Move pressure switch hose to this position Move pressure switch hose to this positionHORIZONTAL - RIGHT INDUCER ROTATED HORIZONTAL - RIGHTSECTION VIII COMBUSTION AIR AND VENT SYSTEM COMBUSTION AIR AND VENT SAFETY364861-UIM-H-0712 COMBUSTION AIR/VENT PIPE SIZINGFIGURE 29 Dimensions COMBUSTION AIR AND VENT PIPING ASSEMBLYElbow A Dimension 364861-UIM-H-0712US Installation2,3 Canadian Installations1,3364861-UIM-H-0712 VENT CLEARANCESVENT SYSTEM 364861-UIM-H-0712VENT APPLICATIONS AND TERMINATION VENTING MULTIPLE UNITSDOWNWARD VENTING 364861-UIM-H-0712COMBUSTION AIR SUPPLY Outdoor Combustion AirAmbient Combustion Air Supply 364861-UIM-H-0712Dampers, Louvers and Grilles Canada Only Combustion Air Source From OutdoorsAir Supply Openings and Ducts 364861-UIM-H-0712Ventilated Combustion Air Ventilated Combustion Air TerminationSpecially Engineered Installations SECTION IX START-UPAND ADJUSTMENTS364861-UIM-H-0712 VENT BLOWER ROTATIONIGNITION SYSTEM SEQUENCE 364861-UIM-H-0712CALCULATING THE FURNACE INPUT NAT. GAS HOT SURFACE IGNITION SYSTEMJohnson Controls Unitary Products 364861-UIM-H-07121 Revolution 1 Cu Ft364861-UIM-H-0712 ADJUSTMENT OF MANIFOLD GAS PRESSURE & INPUT RATERead the inlet gas pressure Read the manifold gas pressureADJUSTMENT OF FAN CONTROL SETTINGS ADJUSTMENT OF TEMPERATURE RISEDANGER 364861-UIM-H-0712Bottom Airflow Data SCFM 364861-UIM-H-0712Johnson Controls Unitary Products 364861-UIM-H-0712SECTION XI NORMAL OPERATION AND DIAGNOSTICS SECTION X SAFETY CONTROLSBLOWER DOOR SAFETY SWITCH ROLLOUT SWITCH CONTROLSFURNACE CONTROL DIAGNOSTICS 364861-UIM-H-0712Johnson Controls Unitary Products REPLACEMENT PART CONTACT INFORMATION SECTION XII REPLACEMENT PARTS LISTDIAGNOSTIC FAULT CODE STORAGE AND RETRIEVAL 364861-UIM-H-0712SECTION XIII WIRING Wiring Diagram - 95% Single-StageFurnaceDIAGRAM Johnson Controls Unitary ProductsNorman, OK York International Corp 5005 York Drive