Johnson Controls GG9S'MP, TG9S'MP UIM-H-0712, Vent System, Vent Applications And Termination

Page 25
VENT SYSTEM

364861-UIM-H-0712

VENT SYSTEM

This furnace is certified to be installed with one of two possible vent configurations.

1.Horizontal vent system. This vent system can be installed com- pletely horizontal or combinations of horizontal, vertical, or offset using elbows.

2.Vertical vent system. This vent system can be installed completely vertical or a combination of horizontal, vertical, or offset using elbows.

NOTICE

On 130K BTU models, there is no provision for the vent to exit the top of the cabinet, the vent must always exit one of the sides.

VENT APPLICATIONS AND TERMINATION

When selecting the location for a combustion air / vent termination, the

Maintain 12” minimum clearance above highest anticipated snow level.

12” vertical separation

 

between combustion air

12” minimum

intake and vent.

below overhang

 

 

12” minimum

 

separation between

 

bottom of

 

combustion air pipe

 

and bottom of vent.

 

Maintain 12”

 

minimum clearance

 

above highest

 

anticipated snow

 

level or grade,

 

whichever is higher.

following should be considered:

FIGURE 32: Termination Configuration - 2 Pipe

1.Observe all clearances listed in vent clearances in these instruc- tions.

2.Termination should be positioned where vent vapors will not dam- age plants or shrubs or air conditioning equipment.

3.Termination should be located where it will not be affected by wind gusts, light snow, airborne leaves or allow recirculation of flue gases.

4.Termination should be located where it will not be damaged or exposed to flying stones, balls, etc.

5.Termination should be positioned where vent vapors are not objec- tionable.

6.Horizontal portions of the vent system must slope upwards and be supported to prevent sagging.

7.Direct vent systems must be installed so the vent and the combus- tion air pipes terminate in the same atmospheric zone. Refer to Fig- ures 32 or 33.

12” MIN.

12” MIN.VENT APPLICATIONS AND TERMINATION

12” Minimum below overhang

12” Minimum separation between bottom of combustion air intake and bottom of vent

VENTING MULTIPLE UNITS Maintain 12” minimumclearance above highest anticipated snow level or grade, whichever is higher

Maintain 12” minimum clearance above highest anticipated snow level. Maximum 24” above roof.

12” Min.

12” Min.

FIGURE 31: Termination Configuration - 1 Pipe

FIGURE 33: Termination Configuration - 2 Pipe Basement

VENTING MULTIPLE UNITS

Multiple units can be installed in a space or structure as either a single pipe configuration or a two-pipe configuration.

The combustion air side of the single pipe configuration shown in Figure 31 is referred to in these instructions as ambient combustion air supply. Follow the instructions for ambient combustion air installations, paying particular attention to the section on air source from inside the building. The vent for a single pipe system must be installed as specified in the venting section of these instructions with the vent terminating as shown in Figure 31. Each furnace must have a separate vent pipe. Under NO circumstances can the two vent pipes be tied together.

The combustion air side of the two-pipe configuration shown in Figure 32 can be installed so the combustion air pipe terminates as described in outdoor combustion air or ventilated combustion air sections in these instructions. Follow the instructions for outdoor combustion air or venti- lated combustion air and the instructions for installing the vent system with the vent terminating as shown in Figures 34 or 35. The two-pipe system must have a separate combustion air pipe and a separate vent pipe for each furnace. Under NO circumstances can the two combus- tion air or vent pipes be tied together. The combustion air and vent pipes must terminate in the same atmospheric zone.

Johnson Controls Unitary Products

25

Image 25
Contents RESIDENTIAL GAS FURNACE INSTALLATION MANUALMODELS TG9S*MP, GG9S*MP 95.5% AFUE Single Stage Multi-positionSPECIFIC SAFETY RULES AND PRECAUTIONS SECTION I SAFETYSAFETY REQUIREMENTS 364861-UIM-H-0712STEP 2 - General Installation STEP 1 - SafetySTEP 6 - Gas Piping and Gas Pipe Pressure Testing 364861-UIM-H-0712Installation in a residential garage Clearances for access/service364861-UIM-H-0712 INSPECTIONThe duct system’s design and installation must FLOOR BASE AND DUCTWORK INSTALLATION - DOWNFLOWinstalled SECTION II DUCTWORKCOIL/FURNACE ASSEMBLY - MC/FC/PC SERIES COILS COIL INSTALLATIONFURNACE ASSEMBLY - MC & FC SERIES COILS COIL FLANGE INSTALLATIONCOIL / FURNACE ASSEMBLY - HC SERIES COILS DOWNFLOW DUCT CONNECTORSBOTTOM RETURN AND ATTIC INSTALLATIONS DIMENSION “C” INCHSUSPENDED FURNACE / CRAWL SPACE INSTALLATION ATTIC INSTALLATION364861-UIM-H-0712 DOWNFLOW APPLICATIONFIGURE 13 Dimensions FILTER INSTALLATIONCabinet Dimensions Inches attempt to install filters inside the furnaceGAS SAFETY DANGERGAS PIPING INSTALLATION SECTION IV GAS PIPINGHIGH ALTITUDE PRESSURE SWITCH CONVERSION SECTION V ELECTRICAL POWERELECTRICAL POWER CONNECTIONS DANGER364861-UIM-H-0712 LOW VOLTAGE CONTROL WIRING CONNECTIONSSUPPLY VOLTAGE CONNECTIONS Input364861-UIM-H-0712 AC 5DJohnson Controls Unitary Products Single Stage Heat Pump - Single Stage PSC Furnace HP 2C364861-UIM-H-0712 ELECTRONIC AIR CLEANER CONNECTION ACCESSORY CONNECTIONSSECTION VI TWINNING AND STAGING 364861-UIM-H-0712Twinning Operation 364861-UIM-H-0712Staging Operation STAGINGCONDENSATE DRAIN TERMINATION 364861-UIM-H-0712Johnson Controls Unitary Products Open Stand Pipe Anti-siphonair vent 5” Min Tee1 pressure switchhose pressure switch hoseINDUCER ROTATED FOR RIGHT SIDE VENTING UPFLOWDOWNFLOW - INDUCER ROTATED FOR LEFT SIDE VENTING AIRFLOW AIRFLOWDOWNFLOW - INDUCER ROTATED FOR RIGHT SIDE VENTING HORIZONTAL - LEFT HORIZONTAL - LEFT INDUCER ROTATEDINDUCER AS RECEIVED Except for 130K Model AIRFLOW1Move pressure switch hose to this position Move pressure switch hose to this positionHORIZONTAL - RIGHT INDUCER ROTATED HORIZONTAL - RIGHTSECTION VIII COMBUSTION AIR AND VENT SYSTEM COMBUSTION AIR AND VENT SAFETY364861-UIM-H-0712 COMBUSTION AIR/VENT PIPE SIZINGFIGURE 29 Dimensions COMBUSTION AIR AND VENT PIPING ASSEMBLYElbow A Dimension 364861-UIM-H-0712US Installation2,3 Canadian Installations1,3364861-UIM-H-0712 VENT CLEARANCESVENT SYSTEM 364861-UIM-H-0712VENT APPLICATIONS AND TERMINATION VENTING MULTIPLE UNITSDOWNWARD VENTING 364861-UIM-H-0712COMBUSTION AIR SUPPLY Outdoor Combustion AirAmbient Combustion Air Supply 364861-UIM-H-0712Dampers, Louvers and Grilles Canada Only Combustion Air Source From OutdoorsAir Supply Openings and Ducts 364861-UIM-H-0712Ventilated Combustion Air Ventilated Combustion Air TerminationSpecially Engineered Installations SECTION IX START-UPAND ADJUSTMENTS364861-UIM-H-0712 VENT BLOWER ROTATIONIGNITION SYSTEM SEQUENCE 364861-UIM-H-0712CALCULATING THE FURNACE INPUT NAT. GAS HOT SURFACE IGNITION SYSTEMJohnson Controls Unitary Products 364861-UIM-H-07121 Revolution 1 Cu Ft364861-UIM-H-0712 ADJUSTMENT OF MANIFOLD GAS PRESSURE & INPUT RATERead the inlet gas pressure Read the manifold gas pressureADJUSTMENT OF FAN CONTROL SETTINGS ADJUSTMENT OF TEMPERATURE RISEDANGER 364861-UIM-H-0712Bottom Airflow Data SCFM 364861-UIM-H-0712Johnson Controls Unitary Products 364861-UIM-H-0712SECTION XI NORMAL OPERATION AND DIAGNOSTICS SECTION X SAFETY CONTROLSBLOWER DOOR SAFETY SWITCH ROLLOUT SWITCH CONTROLS364861-UIM-H-0712 FURNACE CONTROL DIAGNOSTICSJohnson Controls Unitary Products REPLACEMENT PART CONTACT INFORMATION SECTION XII REPLACEMENT PARTS LISTDIAGNOSTIC FAULT CODE STORAGE AND RETRIEVAL 364861-UIM-H-0712SECTION XIII WIRING Wiring Diagram - 95% Single-StageFurnaceDIAGRAM Johnson Controls Unitary ProductsNorman, OK York International Corp 5005 York Drive