Honeywell 3.5 Installing the Control, Mounting the Control Cabinet, Installing the Cabinet Lock

Page 11
Installing the Control

S E C T I O N 3

Installing the Control

• • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • •

This section describes the procedures for mounting and wiring the control panel and all the peripheral devices.

Mounting the Control Cabinet

To mount the control cabinet, perform the following steps:

Step

1

2

UL

Action

Before mounting the circuit board, remove the metal knockouts for the wiring entry that you will be using.

DO NOT ATTEMPT TO REMOVE THE KNOCKOUTS AFTER THE CIRCUIT BOARD HAS BEEN INSTALLED.

Using fasteners or anchors (not supplied), mount the control cabinet to a sturdy wall in a clean, dry area that is not readily accessible to the general public. The back of the cabinet has 4 holes for this purpose.

To provide certificated burglary service for UL installations, refer to the special requirements and Figure 3-2 Cabinet Attack Resistance Considerations to follow. For UL Commercial Burglary installations that require ATTACK RESISTANCE, use the cabinet included in the VISTA-ULKT kit.

Installing the Cabinet Lock

1.Remove cabinet door, then remove the lock knockout from the door. Insert the key into the lock.

2.Position the lock in the hole, making certain that the latch will make contact with the latch bracket when the door is closed.

3.When correctly positioned, push the lock until it is held securely by its snap tabs.

Use Part Number K4445 Lock (supplied).

CHECK

SNAP

POSITION

TAB

LOCKED

PUSH

 

 

ADEMCO

 

SNAP

UNLOCKED

TAB

CABINET DOOR

STEP 1

BOTTOM

PUSH

ON LOCK

UNTIL IT

IS SEATED

SECURELY

ADEMCO

 

STEP 2

_lock_snap-001-V0

 

cab

Figure 3-1: Installing the Lock

Grade A Mercantile Premises Listing Guidelines

The panel door must be supervised. Mount the clip-on tamper switch (supplied) to the cabinet’s right side wall as shown in the diagram below, and wire it to one of the hardwire zones.

Use a bell with a tamper-protected housing such as the AB12. The bell housing’s tamper switch and inner tamper linings must also be wired to the hardwire zone.

Assign the tampers’ hardwire zone to a burglary partition. Program the hardwire zone for day trouble/night alarm (zone type 5) when only one burglary partition is used. Program it for 24-hr. audible alarm (zone type 7) when more than one burglary partition is used.

All wiring between the bell and panel must be run in conduit. Remaining wires do not need to be run in conduit.

All wiring that is not run in conduit must exit from the knockout openings on the bottom or back of the cabinet.

All unused knockouts must be plugged using the disc plugs and carriage bolts (supplied), as indicated in the diagram below.

Fasten the cabinet door to the cabinet backbox using the 18 one-inch-long Phillips-head screws (supplied) after all wiring, programming, and checkout procedures have been completed.

3-1

Image 11
Contents N7001V5 5/04 Rev A $0&29,67$3DUWLWLRQHG6HFXULW\6\VWHP QVWDOODWLRQDQG6HWXS*XLGHPage Table of Contents Index List of Figures PRODUCT MODEL NUMBERS Conventions Used in This ManualAbout the VISTA-40 FeaturesGeneral Description S E C T I O NEvent Log VISTA-40Installation and Setup GuideAdditional Features S E C T I O N Setting-Upa Partitioned SystemPartitioning Theory of PartitioningVISTA-40Installation and Setup Guide Grade A Mercantile Premises Listing Guidelines Installing the ControlInstalling the Cabinet Lock Mounting the Control CabinetStep Action Installing the Control’s Circuit BoardVISTA-40Installation and Setup Guide Wire Gauge Installing the KeypadsSection 3 - Installing the Control Wire Run Length/Gauge TableWiring the Alarm Output Installing External SoundersVISTA-40Installation and Setup Guide Alarm Output SupervisionUsing a Siren Driver Telephone Line ConnectionsSection 3 - Installing the Control Supervising the Alarm OutputON CONTROL VISTA-40Installation and Setup GuideFigure 3-9 Wiring Connections for Zones TERMINALSUsing 4-WireSmoke Detectors on Zones Section 3 - Installing the ControlUsing 2-WireSmoke Detectors on Zone Compatible 2-WireSmoke DetectorsSmoke Detectors Compatible with the 333PRM VISTA-40InstallationTOand Setup GuideUsing Smoke Power Reversal Module Installing the 333PRMCONTROL PANEL Section 3 - Installing the ControlFOUR-WIREDETECTOR CIRCUIT FOUR-WIREDETECTOR CIRCUIT3-10 Installing RPM DevicesVISTA-40Installation and Setup Guide Using 2-WireLatching Glassbreaks on ZoneFigure 3-16 Polling Loop Connections to the Section 3 - Installing the Control3-11 Step ActionPolling Loop Supervision VISTA-40Installation and Setup GuideUsing the 4297 Polling Loop Extender 3-12Installation and Setup of the 5881 RF Receivers Wireless Zone ExpansionSection 3 - Installing the Control RF System Installation AdvisoriesStep VISTA-40Installation and Setup Guide3-14 Step Action5800 Series Transmitter Setup Section 3 - Installing the ControlInstalling the 5800TM Module The 5800TM must not be installed withinInstalling the 4204 Relay Modules Installing Relay DevicesVISTA-40Installation and Setup Guide Transmitter Battery LifeThe wire that reads + 50VDC is the RING side Installing the Ground Start ModuleSection 3 - Installing the Control Installing X10 DevicesWiring for the Remote Keyswitch Installing a Remote KeyswitchVISTA-40Installation and Setup Guide Keyswitch Tamper OperationSection 3 - Installing the Control Installing a 4100SMRemote Keypad Sounder Long Range Radio Connected to the J7 TriggersUL installations Installing the 4285/4286 VIP ModuleVISTA-40Installation and Setup Guide Connecting the 4100SM to a Serial PrinterStep Action Section 3 - Installing the Control3-21 Step Action3-22 Installing the Audio Alarm Verification ModuleVISTA-40Installation and Setup Guide UVCM AND UVST SUMMARY OF CONNECTIONS Connecting the TransformerSection 3 - Installing the Control 3-23Output VISTA-40Installation and Setup GuidePower Limiting Outputs 3-24AC Power Outlet Ground Available from Determining the Control’s Power Supply LoadPanel Earth Ground Connections Section 3 - Installing the ControlAlarm Determining the Size of the Standby BatteryVISTA-40Installation and Setup Guide Table 3 Alarm Output Current Load3-27 Section 3 - Installing the ControlTable 6 Battery Selection Table Recommended Battery3-28 VISTA-40Installation and Setup GuideData Field Programming Mode ProgrammingProgram Modes Entering and Exiting Programming Mode1Enter Program Mode Installer Code + #93 Menu Mode ProgrammingVISTA-40Installation and Setup Guide Entry ErrorsOPTIONS VISTA-40Installation and Setup Guide#93 Menu Mode Programming Commands MAIN MENUCommunication Defaults Zone Number DesignationsVISTA-40Installation and Setup Guide Zone DefaultsSection 4 - Programming Zone Response Type DefinitionsCommunication Defaults for Zones Type 05 Trouble by Day/Alarm by NightType 07 24-HourAudible Alarm Zone Input Type DefinitionsVISTA-40Installation and Setup Guide Type 06 24-HourSilent AlarmStep Programming for Access ControlProgramming for 4100SM Section 4 - ProgrammingVISTA-40Installation and Setup Guide Installer Code Data Field DescriptionsAbout Data Field Programming Programming Data FieldsPrevent Fire Timeout VISTA-40Installation and Setup GuideAlarm Sounder Duration partition-specific Keyswitch AssignmentSection 5 - Data Field Descriptions 24 25 26Power-Upin Previous State PABX Access CodeEnable Open/Close report for Keyswitch 38 39VISTA-40Installation and Setup Guide Download Command EnablesTITLE and DATA ENTRIES 45 46 47 48 49Section 5 - Data Field Descriptions FIELDAlarm Code for Zones 59 60 61 62VISTA-40Installation and Setup Guide Alarm Code for ZonesAlarm Code for Zones 74 75 76 77Supervisory and Restore Codes Alarm Code for ZonesRestore Report Timing 82 83 84VISTA-40Installation and Setup Guide Non-AlarmReport Codes Second Digit1*34 1*01 1*02 1*03 1*04 1*05 1*09 1*28 1*29 1*301*31 1*331*39 1*361*37 1*381*58 1*491*53 1*572*19 2*022*17 2*18Access Security Downloading PrimerGeneral Information Remote Downloading is not a UL Listed featureStage What Happens Getting On-Linewith a Control PanelVISTA-40Installation and Setup Guide On-LineControl FunctionsSection 24 - Downloading Primer Direct-WireDownloadingTelco Handoff VISTA-40Installation and Setup Guide General Information Setting the Real-TimeClockSetting the Time and Date S E C T I O NVISTA-40Installation and Setup Guide S E C T I O N User Access CodesUser Codes & Levels of Authority Level 0 Installer User 1 CodeLevel 6 Duress Codes Multiple Partition AccessVISTA-40Installation and Setup Guide EXAMPLE OF MULTIPLE PARTITION ACCESSPROMPTEXPLANATION Adding a Master, Manager, or Operator CodeSection 9 - User Access Codes Exiting the User Edit Mode Changing a Master, Manager, or Operator CodeAdding an RF Key to an Existing User Deleting a Master, Manager, or Operator CodeBurglary Walk-TestCode + 5 TEST Testing the SystemBattery Test Dialer TestTransmitter ID Sniffer Mode Testing Wireless TransmittersVISTA-40Installation and Setup Guide Step Action 1Enter Installer Code +Power Failure To the InstallerTrouble Conditions Section 10 - Testing The SystemATLIS-FAXFAXBACK Automated Fax Retrieval System VISTA-40Installation and Setup GuideContacting Technical Support Technical SupportA P P E N D I X A UL Installation RequirementsUL365 Police Station Connected Burglar Alarm Regulatory Agency StatementsFor Grade AA Service UL611/UL1610 Central Station Burglary AlarmVISTA-40Installation and Setup Guide For Grade A ServiceFCC PART 68 NOTICE IN THE EVENT OF TELEPHONE OPERATIONAL PROBLEMSAppendix A - Regulatory Agency Statements AVIS VISTA-40Installation and Setup GuideCANADIAN EMISSIONS STATEMENTS Event Logging Commands Summary of System CommandsA P P E N D I X B User Code Commands Programming CommandsVISTA-40Installation and Setup Guide Interface Wiring SpecificationsA P P E N D I X C Interface WiringVISTA-40Installation and Setup Guide Code Contact ID Event CodesA P P E N D I X D TABLE OF CONTACT ID EVENT CODESVISTA-40Installation and Setup Guide Index-1 IndexIndex-2 VISTA-40Installation and Setup GuideIndex-3 IndexIndex-4 VISTA-40Installation and Setup GuideTHE LIMITATIONS OF THIS ALARM SYSTEM LIMITED WARRANTY Page Page Page Page Page Page Page N7001V5 5/04 Rev A 165 Eileen Way, Syosset, New York¬19+l