Honeywell 3.5, ZyAIR G-3000 manual Wireless Zone Expansion, Installing the Control, 3-13

Page 23
Wireless Zone Expansion

Section 3 - Installing the Control

Wireless Zone Expansion

UL

The 5881ENHC RF Receiver and the 5869 Holdup

Switch Transmitter are listed for UL Commercial

 

 

Burglary applications. All other RF receivers and

 

transmitters are not listed for UL Commercial

 

Burglary applications.

 

 

The following table lists the receivers that may be used and the number of zones they support.

5800 Series Receivers

Receiver

Zones

5881L

up to 8

5881M

up to 16

5881H

up to 64

In Canada, 5800 systems must use 5882 Series receivers: 5882L/5882H. Information to the 5881 Receivers applies as well to the 5882 Receivers. Both receivers use the same transmitters.

RF System Operation and Supervision

The 5800 RF system operation has the following characteristics:

The receiver responds to a frequency of 345MHz.

The receiver has a nominal range of 200 feet.

Supervised transmitters send a supervisory signal every 70-90 minutes.

Zones 88 and 90 are used to supervise the RF reception of receivers 2 and 1, respectively. The reception is supervised for two conditions:

1.The receiver goes “deaf” (doesn’t hear from any transmitter) within a programmed interval of time (defined by program field 1*30).

2.Proper RF reception is impeded (i.e., jamming or other RF interference). The control checks for this condition every 45 seconds.

UL

A response type (05 Day/Night) must be

nd

 

programmed for zones 90 (1st receiver) and 88

 

(2 receiver) for UL installations.

 

 

The 5881ENHC receiver contains front and back tampers that permit its use in commercial burglary installations.

You may only mount the 5881ENHC its own plastic housing. Otherwise, the receiver constantly reports a tamper condition.

The control checks the receiver connections about every 45 seconds. The receiver supervisory zone is 89 and 91 for receivers 2 and 1, respectively.

NOTE: These zones must be programmed with a response type (e.g., type 05 Day/Night Trouble) before they supervise the connection to the receiver.

Use two identical receivers to provide either a greater area of coverage or redundant protection. They must be set for different addresses.

Any zone from 1 to 64 can be used as a 5800 Series wireless zone, with the exception of zone 64 (reserved for a wireless keypad).

RF System Installation Advisories

Place the receiver in a high, centrally located area. Do not place it on or near metal objects. This will decrease the range and/or block transmissions.

Install the RF receiver at least 10 feet from the control panel or any keypads, to avoid interference from the microprocessors in these units.

If dual receivers are used:

a.They must be at least 10 feet from each other, as well as from the control panel and remote keypads.

b.Each receiver must be set to a different device address. The receiver set to the lower address is considered the 1st RF receiver for supervisory purposes.

c.The House IDs must be the same.

d.Using two receivers does not increase the number of transmitters the system can support (63 zones using the 5881H, plus a wireless keypad).

Installation and Setup of the 5881 RF Receivers

Take note of the address you select for the RF receiver, as this address must be enabled in the system’s Device Programming in the #93 Menu Mode.

SCREW

5881ENHC-001-V0

Figure 3-19: Installing the 5881ENHC with Tamper

Protection

3-13

Image 23
Contents N7001V5 5/04 Rev A $0&29,67$3DUWLWLRQHG6HFXULW\6\VWHP QVWDOODWLRQDQG6HWXS*XLGHPage Table of Contents Index List of Figures PRODUCT MODEL NUMBERS Conventions Used in This ManualAbout the VISTA-40 FeaturesGeneral Description S E C T I O NEvent Log VISTA-40Installation and Setup GuideAdditional Features S E C T I O N Setting-Upa Partitioned SystemPartitioning Theory of PartitioningVISTA-40Installation and Setup Guide Grade A Mercantile Premises Listing Guidelines Installing the ControlInstalling the Cabinet Lock Mounting the Control CabinetStep Action Installing the Control’s Circuit BoardVISTA-40Installation and Setup Guide Wire Gauge Installing the KeypadsSection 3 - Installing the Control Wire Run Length/Gauge TableWiring the Alarm Output Installing External SoundersVISTA-40Installation and Setup Guide Alarm Output SupervisionUsing a Siren Driver Telephone Line ConnectionsSection 3 - Installing the Control Supervising the Alarm OutputON CONTROL VISTA-40Installation and Setup GuideFigure 3-9 Wiring Connections for Zones TERMINALSUsing 4-WireSmoke Detectors on Zones Section 3 - Installing the ControlUsing 2-WireSmoke Detectors on Zone Compatible 2-WireSmoke DetectorsSmoke Detectors Compatible with the 333PRM VISTA-40InstallationTOand Setup GuideUsing Smoke Power Reversal Module Installing the 333PRMCONTROL PANEL Section 3 - Installing the ControlFOUR-WIREDETECTOR CIRCUIT FOUR-WIREDETECTOR CIRCUIT3-10 Installing RPM DevicesVISTA-40Installation and Setup Guide Using 2-WireLatching Glassbreaks on ZoneFigure 3-16 Polling Loop Connections to the Section 3 - Installing the Control3-11 Step ActionPolling Loop Supervision VISTA-40Installation and Setup GuideUsing the 4297 Polling Loop Extender 3-12Installation and Setup of the 5881 RF Receivers Wireless Zone ExpansionSection 3 - Installing the Control RF System Installation AdvisoriesStep VISTA-40Installation and Setup Guide3-14 Step Action5800 Series Transmitter Setup Section 3 - Installing the ControlInstalling the 5800TM Module The 5800TM must not be installed withinInstalling the 4204 Relay Modules Installing Relay DevicesVISTA-40Installation and Setup Guide Transmitter Battery LifeThe wire that reads + 50VDC is the RING side Installing the Ground Start ModuleSection 3 - Installing the Control Installing X10 DevicesWiring for the Remote Keyswitch Installing a Remote KeyswitchVISTA-40Installation and Setup Guide Keyswitch Tamper OperationSection 3 - Installing the Control Installing a 4100SMRemote Keypad Sounder Long Range Radio Connected to the J7 TriggersUL installations Installing the 4285/4286 VIP ModuleVISTA-40Installation and Setup Guide Connecting the 4100SM to a Serial PrinterStep Action Section 3 - Installing the Control3-21 Step Action3-22 Installing the Audio Alarm Verification ModuleVISTA-40Installation and Setup Guide UVCM AND UVST SUMMARY OF CONNECTIONS Connecting the TransformerSection 3 - Installing the Control 3-23Output VISTA-40Installation and Setup GuidePower Limiting Outputs 3-24AC Power Outlet Ground Available from Determining the Control’s Power Supply LoadPanel Earth Ground Connections Section 3 - Installing the ControlAlarm Determining the Size of the Standby BatteryVISTA-40Installation and Setup Guide Table 3 Alarm Output Current Load3-27 Section 3 - Installing the ControlTable 6 Battery Selection Table Recommended Battery3-28 VISTA-40Installation and Setup GuideData Field Programming Mode ProgrammingProgram Modes Entering and Exiting Programming Mode1Enter Program Mode Installer Code + #93 Menu Mode ProgrammingVISTA-40Installation and Setup Guide Entry ErrorsOPTIONS VISTA-40Installation and Setup Guide#93 Menu Mode Programming Commands MAIN MENUCommunication Defaults Zone Number DesignationsVISTA-40Installation and Setup Guide Zone DefaultsSection 4 - Programming Zone Response Type DefinitionsCommunication Defaults for Zones Type 05 Trouble by Day/Alarm by NightType 07 24-HourAudible Alarm Zone Input Type DefinitionsVISTA-40Installation and Setup Guide Type 06 24-HourSilent AlarmStep Programming for Access ControlProgramming for 4100SM Section 4 - ProgrammingVISTA-40Installation and Setup Guide Installer Code Data Field DescriptionsAbout Data Field Programming Programming Data FieldsPrevent Fire Timeout VISTA-40Installation and Setup GuideAlarm Sounder Duration partition-specific Keyswitch AssignmentSection 5 - Data Field Descriptions 24 25 26Power-Upin Previous State PABX Access CodeEnable Open/Close report for Keyswitch 38 39VISTA-40Installation and Setup Guide Download Command EnablesTITLE and DATA ENTRIES 45 46 47 48 49Section 5 - Data Field Descriptions FIELDAlarm Code for Zones 59 60 61 62VISTA-40Installation and Setup Guide Alarm Code for ZonesAlarm Code for Zones 74 75 76 77Supervisory and Restore Codes Alarm Code for ZonesRestore Report Timing 82 83 84VISTA-40Installation and Setup Guide Non-AlarmReport Codes Second Digit1*34 1*01 1*02 1*03 1*04 1*05 1*09 1*28 1*29 1*301*31 1*331*39 1*361*37 1*381*58 1*491*53 1*572*19 2*022*17 2*18Access Security Downloading PrimerGeneral Information Remote Downloading is not a UL Listed featureStage What Happens Getting On-Linewith a Control PanelVISTA-40Installation and Setup Guide On-LineControl FunctionsSection 24 - Downloading Primer Direct-WireDownloadingTelco Handoff VISTA-40Installation and Setup Guide General Information Setting the Real-TimeClockSetting the Time and Date S E C T I O NVISTA-40Installation and Setup Guide S E C T I O N User Access CodesUser Codes & Levels of Authority Level 0 Installer User 1 CodeLevel 6 Duress Codes Multiple Partition AccessVISTA-40Installation and Setup Guide EXAMPLE OF MULTIPLE PARTITION ACCESSPROMPTEXPLANATION Adding a Master, Manager, or Operator CodeSection 9 - User Access Codes Exiting the User Edit Mode Changing a Master, Manager, or Operator CodeAdding an RF Key to an Existing User Deleting a Master, Manager, or Operator CodeBurglary Walk-TestCode + 5 TEST Testing the SystemBattery Test Dialer TestTransmitter ID Sniffer Mode Testing Wireless TransmittersVISTA-40Installation and Setup Guide Step Action 1Enter Installer Code +Power Failure To the InstallerTrouble Conditions Section 10 - Testing The SystemATLIS-FAXFAXBACK Automated Fax Retrieval System VISTA-40Installation and Setup GuideContacting Technical Support Technical SupportA P P E N D I X A UL Installation RequirementsUL365 Police Station Connected Burglar Alarm Regulatory Agency StatementsFor Grade AA Service UL611/UL1610 Central Station Burglary AlarmVISTA-40Installation and Setup Guide For Grade A ServiceFCC PART 68 NOTICE IN THE EVENT OF TELEPHONE OPERATIONAL PROBLEMSAppendix A - Regulatory Agency Statements AVIS VISTA-40Installation and Setup GuideCANADIAN EMISSIONS STATEMENTS Event Logging Commands Summary of System CommandsA P P E N D I X B User Code Commands Programming CommandsVISTA-40Installation and Setup Guide Interface Wiring SpecificationsA P P E N D I X C Interface WiringVISTA-40Installation and Setup Guide Code Contact ID Event CodesA P P E N D I X D TABLE OF CONTACT ID EVENT CODESVISTA-40Installation and Setup Guide Index-1 IndexIndex-2 VISTA-40Installation and Setup GuideIndex-3 IndexIndex-4 VISTA-40Installation and Setup GuideTHE LIMITATIONS OF THIS ALARM SYSTEM LIMITED WARRANTY Page Page Page Page Page Page Page N7001V5 5/04 Rev A 165 Eileen Way, Syosset, New York¬19+l