Zone Number Designations
The
Zone | Function |
Zone Index
The zones are designated as follows:
ZONE # | ZONE | ACTUAL ZONE | |
RANGE | FUNCTION | ||
| |||
01 – 64 | Protection | As indicated | |
| zones |
|
1 | |
5 | Audio Alarm Verification (if used) |
7Keyswitch (if used)
8
95✳ + 1 Panic
96# + 3 Panic
99 | ✳ + # Panic |
70, 88, 89, | System |
90, 91, & | Supervisory |
97 | Zones |
|
|
70:Bell Supervision
88:2nd Wireless Receiver – not receiving signals
89:2nd Wireless Receiver – not talking to control
90:1st Wireless Receiver – not receiving signals
91:1st Wireless Receiver – not talking to control
97:Polling Loop (short circuit)
Zone Defaults
Zone # | Zone Type |
01 | 09 |
Zone #
70
Zone Type
00
92, 95, 96, | Duress and |
& 99 | Keypad Panics |
92:Duress
95:1 + ✳ panic (A key)
96:3 + # panic (C key)
99: ✳ + # panic (B key)
02 | 03 |
03 | 03 |
04 | 03 |
05 | 03 |
06 | 03 |
07 | 03 |
08 | 03 |
0903
87
88
90
91
92*
95
96
97
99
00
00
00
00
N/A
00
00
05
06
Supervisory zones should be given a response type of 05 (Trouble by Day, Alarm by Night).
NOTES: *Zone 92 is the Duress zone. Programming of the zone response type is not applicable. This zone requires only the report code programming.
Communication Defaults
*45 | PRIMARY FORMAT | [1] ADEMCO Contact ID | *51 | DUAL REPORTING |
| [0] no |
| ||||
*46 | LOW SPEED FORMAT (Prim) [0] ADEMCO Low Speed | *52 | STANDARD/EXPANDED REPORT FOR PRIMARY | ||||||||
*47 | SECONDARY FORMAT | [1] ADEMCO Contact ID |
| [0] | [0] | [0] | [0] | [0] | [0] | standard | |
*48 | LOW SPEED FORMAT (Sec.) | [0] ADEMCO Low Speed |
| Alarm | Rstr | Bypass | Trbl | Opn/Cls Low Bat |
| ||
*49 | CHECKSUM VERIFICATION [0] | [0] | *53 | STANDARD/EXPANDED REPORT FOR SECONDARY | |||||||
| No checksum | Primary | Secondary |
| [0] | [0] | [0] | [0] | [0] | [0] | standard |
*50 | SESCOA/RADIONICS SEL. | [0] Radionics |
| Alarm | Rstr | Bypass | Trbl | Opn/Cls Low Bat |
|