Type 06: 24-Hour Silent Alarm
Sends a report to the central station but provides no keypad display or sounding. Assign this zone type to a zone containing an Emergency button.
Type 07: 24-Hour Audible Alarm
Sends a report to the central station and provides an alarm sound at the keypad and an audible external alarm. Assign this zone type to a zone containing an Emergency button.
Type 08: 24-Hour Auxiliary Alarm
Sends a report to central station and provides an alarm sound at the keypad only. (No bell output is provided.) Assign this zone type to a zone an Emergency button or one containing monitoring devices such as water sensors or temperature sensors.
Type 09: Supervised Fire (Without Verification)
Provides a fire alarm on a short circuit and a trouble condition on open circuit. A fire alarm produces a pulsing of the bell output. A zone of this type is always active and cannot be bypassed.
Type 10: Interior with Delay
Provides entry and exit delays (using the programmed entry and exit delay times) when armed in the AWAY mode. Provides only exit delay when armed in the MAXIMUM mode (no entry delay). Delay begins whenever sensors in this zone are violated, regardless of whether or not an entry/exit delay zone was tripped first.
Zones programmed for Interior with Delay are automatically bypassed when the panel is armed in the STAY or INSTANT mode.
Assign this zone type to a zone covering an area such as a foyer, lobby, or hallway through which one must pass upon entry or exit (to and from the keypad).
Type 20: Arm-STAY (5800 Series devices only)
Causes the system to arm in the STAY mode when the zone is activated.
Type 21: Arm-AWAY (5800 Series devices only)
Causes the system to arm in the AWAY mode when the zone is activated.
Type 22: Disarm (5800 Series devices only)
Causes the system to disarm when the zone is activated.
Type 23: No Alarm Response
Used on a zone when an output relay action is desired, but with no accompanying alarm (e.g., for access door).
NOTE FOR PANIC KEYS: Keypad panic zones share the same zone response type for both partitions, but panics may be individually enabled for each partition.
IMPORTANT! FAULT ANNUNCIATION
Polling loop and RF troubles (zones 88, 89, 90, 91, and 97) report as trouble conditions only, and as such, should be assigned zone type 05 if annunciation is desired. See Polling Loop Supervision and RF System Operation and Supervision in SECTION 3 Installing the Control for more information.
Zone Input Type Definitions
Each zone must be assigned an input type, which defines the where the system will “look” for status of the zone (RF receiver, polling loop, etc.). Zone input types are defined below.
Type 01 Hardwired (HW)
Reserved for the
Type 03 Supervised RF (RF)
Select for 5800 Series RF transmitters that will be supervised for
Type 04 Unsupervised RF (UR)
Select for 5800 Series RF transmitters that will not be supervised for
Type 05 Unsupervised Button RF (BR)
Select for 5800 Series RF transmitters specifically designed for this input type. Check the transmitter’s instructions for proper programming of the input type. These transmitters send only fault signals. They do not send
Type 06 Serial Number Polling Loop (SL)
Select for polling loop devices with a
Type 07 DIP Switch Loop (DP)
Select for polling loop devices that use DIP switches for programming the zone number of the device.
Type 08 Dip Switch Polling Loop Right Loop (PS)
Select for the second loop of