Honeywell ZyAIR G-3000, 3.5 VISTA-40Installation and Setup Guide, Field, TITLE and DATA ENTRIES

Page 48
*12

VISTA-40 Installation and Setup Guide

FIELD

TITLE and DATA ENTRIES

EXPLANATION

 

 

 

*12

*13

Exit Delay #2 (partition-specific)

Enter 03-15multiplied by 15 seconds. 00 = no delay.

Alarm Sounder Duration (partition-specific)

Exit Delay #2 is used for a secondary door requiring a longer delay than those assigned to Exit Delay #1.

NOTE: The delay may not exceed 60 seconds for UL installations.

Defines the length of time the Bell Output and the keypad’s sounder will sound for all audible alarms.

*14

*15

Enter 01-15multiplied by 2 minutes. 00 = no timeout.

Zone 9 Fast/Slow Response

0 = slow 350ms

1 = fast 10ms

Keyswitch Assignment

Enter 1-2partition keyswitch is being used. Enter 0 if the keyswitch is not used.

Must be minimum 16 minutes for UL Commercial Burglary installations.

Select the response time for devices connected to zone 9.

The keyswitch requires the use of zone 7 wired loop (zone 7 is no longer available as protection zone). The fire and panic alarm voltage triggers (J7) automatically become ARMING and READY status outputs for the Keyswitch LEDs.

Openings/closing report as user “0” if enabled in field *40.

*16

*17

*19

*20

Confirmation of Arming Ding (partition-specific)

0 = disable

1 = enable

AC Loss Keypad Sounding

0 = disable

1 = enable

Randomize AC Loss Report

0 = disable

1 = enable

VIP Module Phone Code

￿1-9= first digit of access code

or # = second digit of access code (enter # +11 for “”, or # +12 for “#”)

To disable enter 00 for the 1st digit

If enabled, produces ½-second external alarm sounding (“ding”) at the end of exit delay (or after kissoff from the central station, if sending closing reports).

Must be 1 for UL installations.

If enabled, sounding at the keypad (rapid beeping) occurs when AC power is lost (sounding occurs about 2 minutes after actual AC loss).

If enabled, randomizes AC loss reporting between 10 and 40 min. after an actual AC loss.

If disabled, AC loss reporting about 2 minutes after actual AC loss.

Selecting this option helps prevent an overload of AC loss messages at the central station during a community blackout.

If a 4285/4286 Voice Module is being used, enter the 2-digit phone code used to access the system.

Must be disabled for UL installations.

*21

Prevent Fire Timeout

If enabled, there is no timeout of the alarm sounder duration for all fire

0

= disable (timeout)

zones, regardless of partition, so that fire sounding continues until the

1

= enable (no timeout)

system is reset.

 

 

If disabled, (timeout) the normal burglary sounder duration (field 13)

 

 

applies to fire alarms.

 

 

 

*22

*23

Keypad Panic Enables (partition- specific)

0 = disable

1 = enable

Multiple Alarms (partition- specific)

0 = disable

1 = enable

If enabled, the keypad panics (zones 995, 996, and 999) may be used in this partition. There are 3 entries in this field, one for each panic.

If enabled, allows more than one alarm sounding for a given zone during an armed period.

NOTE: that multiple alarm soundings will not occur more frequently than allowed by the programmed alarm sounder duration. This has no impact on the number of communication messages transmitted.

Must be 1 for UL installations.

5-2

Image 48
Contents $0&29,67$ 3DUWLWLRQHG6HFXULW\6\VWHPQVWDOODWLRQDQG6HWXS*XLGH N7001V5 5/04 Rev APage Table of Contents Index List of Figures Conventions Used in This Manual PRODUCT MODEL NUMBERSFeatures General DescriptionS E C T I O N About the VISTA-40VISTA-40Installation and Setup Guide Additional FeaturesEvent Log Setting-Upa Partitioned System PartitioningTheory of Partitioning S E C T I O NVISTA-40Installation and Setup Guide Installing the Control Installing the Cabinet LockMounting the Control Cabinet Grade A Mercantile Premises Listing GuidelinesInstalling the Control’s Circuit Board VISTA-40Installation and Setup GuideStep Action Installing the Keypads Section 3 - Installing the ControlWire Run Length/Gauge Table Wire GaugeInstalling External Sounders VISTA-40Installation and Setup GuideAlarm Output Supervision Wiring the Alarm OutputTelephone Line Connections Section 3 - Installing the ControlSupervising the Alarm Output Using a Siren DriverVISTA-40Installation and Setup Guide Figure 3-9 Wiring Connections for ZonesTERMINALS ON CONTROLSection 3 - Installing the Control Using 2-WireSmoke Detectors on ZoneCompatible 2-WireSmoke Detectors Using 4-WireSmoke Detectors on ZonesVISTA-40InstallationTOand Setup Guide Using Smoke Power Reversal ModuleInstalling the 333PRM Smoke Detectors Compatible with the 333PRMSection 3 - Installing the Control FOUR-WIREDETECTOR CIRCUITFOUR-WIREDETECTOR CIRCUIT CONTROL PANELInstalling RPM Devices VISTA-40Installation and Setup GuideUsing 2-WireLatching Glassbreaks on Zone 3-10Section 3 - Installing the Control 3-11Step Action Figure 3-16 Polling Loop Connections to theVISTA-40Installation and Setup Guide Using the 4297 Polling Loop Extender3-12 Polling Loop SupervisionWireless Zone Expansion Section 3 - Installing the ControlRF System Installation Advisories Installation and Setup of the 5881 RF ReceiversVISTA-40Installation and Setup Guide 3-14Step Action StepSection 3 - Installing the Control Installing the 5800TM ModuleThe 5800TM must not be installed within 5800 Series Transmitter SetupInstalling Relay Devices VISTA-40Installation and Setup GuideTransmitter Battery Life Installing the 4204 Relay ModulesInstalling the Ground Start Module Section 3 - Installing the ControlInstalling X10 Devices The wire that reads + 50VDC is the RING sideInstalling a Remote Keyswitch VISTA-40Installation and Setup GuideKeyswitch Tamper Operation Wiring for the Remote KeyswitchInstalling a 4100SM Remote Keypad SounderLong Range Radio Connected to the J7 Triggers Section 3 - Installing the ControlInstalling the 4285/4286 VIP Module VISTA-40Installation and Setup GuideConnecting the 4100SM to a Serial Printer UL installationsSection 3 - Installing the Control 3-21Step Action Step ActionInstalling the Audio Alarm Verification Module VISTA-40Installation and Setup Guide3-22 Connecting the Transformer Section 3 - Installing the Control3-23 UVCM AND UVST SUMMARY OF CONNECTIONSVISTA-40Installation and Setup Guide Power Limiting Outputs3-24 OutputDetermining the Control’s Power Supply Load Panel Earth Ground ConnectionsSection 3 - Installing the Control AC Power Outlet Ground Available fromDetermining the Size of the Standby Battery VISTA-40Installation and Setup GuideTable 3 Alarm Output Current Load AlarmSection 3 - Installing the Control Table 6 Battery Selection TableRecommended Battery 3-27VISTA-40Installation and Setup Guide 3-28Programming Program ModesEntering and Exiting Programming Mode Data Field Programming Mode#93 Menu Mode Programming VISTA-40Installation and Setup GuideEntry Errors 1Enter Program Mode Installer Code +VISTA-40Installation and Setup Guide #93 Menu Mode Programming CommandsMAIN MENU OPTIONSZone Number Designations VISTA-40Installation and Setup GuideZone Defaults Communication DefaultsZone Response Type Definitions Communication Defaults for ZonesType 05 Trouble by Day/Alarm by Night Section 4 - ProgrammingZone Input Type Definitions VISTA-40Installation and Setup GuideType 06 24-HourSilent Alarm Type 07 24-HourAudible AlarmProgramming for Access Control Programming for 4100SMSection 4 - Programming StepVISTA-40Installation and Setup Guide Data Field Descriptions About Data Field ProgrammingProgramming Data Fields Installer CodeVISTA-40Installation and Setup Guide Alarm Sounder Duration partition-specificKeyswitch Assignment Prevent Fire Timeout24 25 26 Power-Upin Previous StatePABX Access Code Section 5 - Data Field Descriptions38 39 VISTA-40Installation and Setup GuideDownload Command Enables Enable Open/Close report for Keyswitch45 46 47 48 49 Section 5 - Data Field DescriptionsFIELD TITLE and DATA ENTRIES59 60 61 62 VISTA-40Installation and Setup GuideAlarm Code for Zones Alarm Code for Zones74 75 76 77 Supervisory and Restore CodesAlarm Code for Zones Alarm Code for Zones82 83 84 VISTA-40Installation and Setup GuideNon-AlarmReport Codes Second Digit Restore Report Timing1*01 1*02 1*03 1*04 1*05 1*09 1*28 1*29 1*30 1*311*33 1*341*36 1*371*38 1*391*49 1*531*57 1*582*02 2*172*18 2*19Downloading Primer General InformationRemote Downloading is not a UL Listed feature Access SecurityGetting On-Linewith a Control Panel VISTA-40Installation and Setup GuideOn-LineControl Functions Stage What HappensDirect-WireDownloading Telco HandoffSection 24 - Downloading Primer VISTA-40Installation and Setup Guide Setting the Real-TimeClock Setting the Time and DateS E C T I O N General InformationVISTA-40Installation and Setup Guide User Access Codes User Codes & Levels of AuthorityLevel 0 Installer User 1 Code S E C T I O NMultiple Partition Access VISTA-40Installation and Setup GuideEXAMPLE OF MULTIPLE PARTITION ACCESS Level 6 Duress CodesAdding a Master, Manager, or Operator Code Section 9 - User Access CodesPROMPTEXPLANATION Changing a Master, Manager, or Operator Code Adding an RF Key to an Existing UserDeleting a Master, Manager, or Operator Code Exiting the User Edit ModeTesting the System Battery TestDialer Test Burglary Walk-TestCode + 5 TESTTesting Wireless Transmitters VISTA-40Installation and Setup GuideStep Action 1Enter Installer Code + Transmitter ID Sniffer ModeTo the Installer Trouble ConditionsSection 10 - Testing The System Power FailureVISTA-40Installation and Setup Guide Contacting Technical SupportTechnical Support ATLIS-FAXFAXBACK Automated Fax Retrieval SystemUL Installation Requirements UL365 Police Station Connected Burglar AlarmRegulatory Agency Statements A P P E N D I X AUL611/UL1610 Central Station Burglary Alarm VISTA-40Installation and Setup GuideFor Grade A Service For Grade AA ServiceIN THE EVENT OF TELEPHONE OPERATIONAL PROBLEMS Appendix A - Regulatory Agency StatementsFCC PART 68 NOTICE VISTA-40Installation and Setup Guide CANADIAN EMISSIONS STATEMENTSAVIS Summary of System Commands A P P E N D I X BUser Code Commands Programming Commands Event Logging CommandsVISTA-40Installation and Setup Guide Specifications A P P E N D I X CInterface Wiring Interface WiringVISTA-40Installation and Setup Guide Contact ID Event Codes A P P E N D I X DTABLE OF CONTACT ID EVENT CODES CodeVISTA-40Installation and Setup Guide Index Index-1VISTA-40Installation and Setup Guide Index-2Index Index-3VISTA-40Installation and Setup Guide Index-4THE LIMITATIONS OF THIS ALARM SYSTEM LIMITED WARRANTY Page Page Page Page Page Page Page 165 Eileen Way, Syosset, New York ¬19+lN7001V5 5/04 Rev A