3.In Table 3, enter devices connected to the Alarm Output. Calculate alarm currents, then add to get the Alarm Output current subtotal.
Table 3: Alarm Output Current Load
|
|
|
|
| Total Current | ||
Device |
| Device Current X | Standby |
| Alarm | ||
|
| ||||||
Model # |
| # of Units |
|
|
| ||
|
|
|
|
|
|
|
|
4.In Table 4, enter the total calculated subtotals of all listed outputs from Tables 1 through 3, then add to get the combined current.
Table 4: Total VISTA-40 Current Load
Total Current
Standby Alarm
XXXXXX |
XXXXXX |
XXXXXX |
XXXXXX |
XXXXXX |
XXXXXX |
Polling Loop Subtotal (see Table 1)
Aux. Power Subtotal (see Table 2)
Alarm Output Subtotal (see Table 3)
250mA
330mA
XXXXXX |
Alarm Output Subtotal |
(terminals 4 & 5 – 1.7A max.) |
Total Current Load
Determining the Size of the Standby Battery
The cabinet supplied with the control panel can house batteries of up to 12V, 14AH (two 12V, 7AH batteries wired in parallel). The
Use Table 5 to determine the required backup battery capacity and use Table 6 to determine the battery model number. A dual battery harness is supplied that allows two batteries to be wired in parallel for increased capacity.
5.Using the total calculated from Table 4, calculate the battery capacity required for the installation.
when 17.2AH batteries are used.
|
| DO NOT use Gates batteries (sealed |
|
| type). These batteries require a different |
| ||
|
| charging voltage than is supplied by the panel. |
| ||
|
|
|
|
|
|
UL |
| Household Fire or Combination |
| Household/Fire/Burglary installations require | |
|
| the use of a backup battery that is capable of |
|
| providing 24 hours of standby time followed by |
|
| 4 minutes of alarm time. UL1023 Household |
|
| |
|
| backup battery that is capable of providing 4 |
|
| hours of standby time followed by 4 minutes of |
|
| alarm time. |
Table 5: Battery Capacity Calculation Table
Capacity | Formula |
|
|
| |
Standby | For | |
Capacity | Total standby current X 4 hours | |
| X 1.4 contingency factor. | |
| For | |
| Total standby current X 24 | |
| hours X 1.1 contingency factor. | |
Alarm | For | |
Capacity | time: |
|
| Total alarm curr. |
|
| X | 0.067 (4 min) |
| X | 0.250 (15 min) |
Calculated
Value
| Total | Add standby and alarm |
|
|
| Capacity | capacities |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|