Honeywell ZyAIR G-3000 Determining the Size of the Standby Battery, 3-26, Total Current, Device

Page 36
Table 3: Alarm Output Current Load

VISTA-40 Installation and Setup Guide

3.In Table 3, enter devices connected to the Alarm Output. Calculate alarm currents, then add to get the Alarm Output current subtotal.

Table 3: Alarm Output Current Load

 

 

 

 

 

Total Current

Device

 

Device Current X

Standby

 

Alarm

 

 

Model #

 

# of Units

 

 

 

 

 

 

 

 

 

 

 

4.In Table 4, enter the total calculated subtotals of all listed outputs from Tables 1 through 3, then add to get the combined current.

Table 4: Total VISTA-40 Current Load

Total Current

Standby Alarm

XXXXXX

XXXXXX

XXXXXX

XXXXXX

XXXXXX

XXXXXX

Polling Loop Subtotal (see Table 1)

Aux. Power Subtotal (see Table 2)

Alarm Output Subtotal (see Table 3)

VISTA-40 PCB Current (Includes 2- wire smoke detector loading on zone 1)

250mA

330mA

XXXXXX

Alarm Output Subtotal

(terminals 4 & 5 – 1.7A max.)

Total Current Load

Determining the Size of the Standby Battery

The cabinet supplied with the control panel can house batteries of up to 12V, 14AH (two 12V, 7AH batteries wired in parallel). The VISTA-ULKT kit provides a cabinet that can house batteries of up to 12V, 17.2AH and that may be used with this panel. The total standby current drawn from the auxiliary power and polling loop outputs combined must be limited to 270mA when 14AH batteries are used; and to 390mA

Use Table 5 to determine the required backup battery capacity and use Table 6 to determine the battery model number. A dual battery harness is supplied that allows two batteries to be wired in parallel for increased capacity.

5.Using the total calculated from Table 4, calculate the battery capacity required for the installation.

when 17.2AH batteries are used.

 

 

DO NOT use Gates batteries (sealed lead-acid

 

 

type). These batteries require a different

 

 

 

charging voltage than is supplied by the panel.

 

 

 

 

 

 

 

UL

 

Household Fire or Combination

 

Household/Fire/Burglary installations require

 

 

the use of a backup battery that is capable of

 

 

providing 24 hours of standby time followed by

 

 

4 minutes of alarm time. UL1023 Household

 

 

Burglary-only installations require the use of a

 

 

backup battery that is capable of providing 4

 

 

hours of standby time followed by 4 minutes of

 

 

alarm time.

Table 5: Battery Capacity Calculation Table

Capacity

Formula

 

 

 

Standby

For 4-hour standby time:

Capacity

Total standby current X 4 hours

 

X 1.4 contingency factor.

 

For 24-hour standby time:

 

Total standby current X 24

 

hours X 1.1 contingency factor.

Alarm

For 4-, 5-, or 15-minute alarm

Capacity

time:

 

 

Total alarm curr.

 

 

X

0.067 (4 min)

 

X

0.250 (15 min)

Calculated

Value

 

Total
Add standby and alarm

 

 

 

Capacity

capacities

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3-26

Image 36
Contents $0&29,67$ 3DUWLWLRQHG6HFXULW\6\VWHPQVWDOODWLRQDQG6HWXS*XLGH N7001V5 5/04 Rev APage Table of Contents Index List of Figures Conventions Used in This Manual PRODUCT MODEL NUMBERSFeatures General DescriptionS E C T I O N About the VISTA-40VISTA-40Installation and Setup Guide Additional FeaturesEvent Log Setting-Upa Partitioned System PartitioningTheory of Partitioning S E C T I O NVISTA-40Installation and Setup Guide Installing the Control Installing the Cabinet LockMounting the Control Cabinet Grade A Mercantile Premises Listing GuidelinesInstalling the Control’s Circuit Board VISTA-40Installation and Setup GuideStep Action Installing the Keypads Section 3 - Installing the ControlWire Run Length/Gauge Table Wire GaugeInstalling External Sounders VISTA-40Installation and Setup GuideAlarm Output Supervision Wiring the Alarm OutputTelephone Line Connections Section 3 - Installing the ControlSupervising the Alarm Output Using a Siren DriverVISTA-40Installation and Setup Guide Figure 3-9 Wiring Connections for ZonesTERMINALS ON CONTROLSection 3 - Installing the Control Using 2-WireSmoke Detectors on ZoneCompatible 2-WireSmoke Detectors Using 4-WireSmoke Detectors on ZonesVISTA-40InstallationTOand Setup Guide Using Smoke Power Reversal ModuleInstalling the 333PRM Smoke Detectors Compatible with the 333PRMSection 3 - Installing the Control FOUR-WIREDETECTOR CIRCUITFOUR-WIREDETECTOR CIRCUIT CONTROL PANELInstalling RPM Devices VISTA-40Installation and Setup GuideUsing 2-WireLatching Glassbreaks on Zone 3-10Section 3 - Installing the Control 3-11Step Action Figure 3-16 Polling Loop Connections to theVISTA-40Installation and Setup Guide Using the 4297 Polling Loop Extender3-12 Polling Loop SupervisionWireless Zone Expansion Section 3 - Installing the ControlRF System Installation Advisories Installation and Setup of the 5881 RF ReceiversVISTA-40Installation and Setup Guide 3-14Step Action StepSection 3 - Installing the Control Installing the 5800TM ModuleThe 5800TM must not be installed within 5800 Series Transmitter SetupInstalling Relay Devices VISTA-40Installation and Setup GuideTransmitter Battery Life Installing the 4204 Relay ModulesInstalling the Ground Start Module Section 3 - Installing the ControlInstalling X10 Devices The wire that reads + 50VDC is the RING sideInstalling a Remote Keyswitch VISTA-40Installation and Setup GuideKeyswitch Tamper Operation Wiring for the Remote KeyswitchInstalling a 4100SM Remote Keypad SounderLong Range Radio Connected to the J7 Triggers Section 3 - Installing the ControlInstalling the 4285/4286 VIP Module VISTA-40Installation and Setup GuideConnecting the 4100SM to a Serial Printer UL installationsSection 3 - Installing the Control 3-21Step Action Step ActionInstalling the Audio Alarm Verification Module VISTA-40Installation and Setup Guide3-22 Connecting the Transformer Section 3 - Installing the Control3-23 UVCM AND UVST SUMMARY OF CONNECTIONSVISTA-40Installation and Setup Guide Power Limiting Outputs3-24 OutputDetermining the Control’s Power Supply Load Panel Earth Ground ConnectionsSection 3 - Installing the Control AC Power Outlet Ground Available fromDetermining the Size of the Standby Battery VISTA-40Installation and Setup GuideTable 3 Alarm Output Current Load AlarmSection 3 - Installing the Control Table 6 Battery Selection TableRecommended Battery 3-27VISTA-40Installation and Setup Guide 3-28Programming Program ModesEntering and Exiting Programming Mode Data Field Programming Mode#93 Menu Mode Programming VISTA-40Installation and Setup GuideEntry Errors 1Enter Program Mode Installer Code +VISTA-40Installation and Setup Guide #93 Menu Mode Programming CommandsMAIN MENU OPTIONSZone Number Designations VISTA-40Installation and Setup GuideZone Defaults Communication DefaultsZone Response Type Definitions Communication Defaults for ZonesType 05 Trouble by Day/Alarm by Night Section 4 - ProgrammingZone Input Type Definitions VISTA-40Installation and Setup GuideType 06 24-HourSilent Alarm Type 07 24-HourAudible AlarmProgramming for Access Control Programming for 4100SMSection 4 - Programming StepVISTA-40Installation and Setup Guide Data Field Descriptions About Data Field ProgrammingProgramming Data Fields Installer CodeVISTA-40Installation and Setup Guide Alarm Sounder Duration partition-specificKeyswitch Assignment Prevent Fire Timeout24 25 26 Power-Upin Previous StatePABX Access Code Section 5 - Data Field Descriptions38 39 VISTA-40Installation and Setup GuideDownload Command Enables Enable Open/Close report for Keyswitch45 46 47 48 49 Section 5 - Data Field DescriptionsFIELD TITLE and DATA ENTRIES59 60 61 62 VISTA-40Installation and Setup GuideAlarm Code for Zones Alarm Code for Zones74 75 76 77 Supervisory and Restore CodesAlarm Code for Zones Alarm Code for Zones82 83 84 VISTA-40Installation and Setup GuideNon-AlarmReport Codes Second Digit Restore Report Timing1*01 1*02 1*03 1*04 1*05 1*09 1*28 1*29 1*30 1*311*33 1*341*36 1*371*38 1*391*49 1*531*57 1*582*02 2*172*18 2*19Downloading Primer General InformationRemote Downloading is not a UL Listed feature Access SecurityGetting On-Linewith a Control Panel VISTA-40Installation and Setup GuideOn-LineControl Functions Stage What HappensDirect-WireDownloading Telco HandoffSection 24 - Downloading Primer VISTA-40Installation and Setup Guide Setting the Real-TimeClock Setting the Time and DateS E C T I O N General InformationVISTA-40Installation and Setup Guide User Access Codes User Codes & Levels of AuthorityLevel 0 Installer User 1 Code S E C T I O NMultiple Partition Access VISTA-40Installation and Setup GuideEXAMPLE OF MULTIPLE PARTITION ACCESS Level 6 Duress CodesAdding a Master, Manager, or Operator Code Section 9 - User Access CodesPROMPTEXPLANATION Changing a Master, Manager, or Operator Code Adding an RF Key to an Existing UserDeleting a Master, Manager, or Operator Code Exiting the User Edit ModeTesting the System Battery TestDialer Test Burglary Walk-TestCode + 5 TESTTesting Wireless Transmitters VISTA-40Installation and Setup GuideStep Action 1Enter Installer Code + Transmitter ID Sniffer ModeTo the Installer Trouble ConditionsSection 10 - Testing The System Power FailureVISTA-40Installation and Setup Guide Contacting Technical SupportTechnical Support ATLIS-FAXFAXBACK Automated Fax Retrieval SystemUL Installation Requirements UL365 Police Station Connected Burglar AlarmRegulatory Agency Statements A P P E N D I X AUL611/UL1610 Central Station Burglary Alarm VISTA-40Installation and Setup GuideFor Grade A Service For Grade AA ServiceIN THE EVENT OF TELEPHONE OPERATIONAL PROBLEMS Appendix A - Regulatory Agency StatementsFCC PART 68 NOTICE VISTA-40Installation and Setup Guide CANADIAN EMISSIONS STATEMENTSAVIS Summary of System Commands A P P E N D I X BUser Code Commands Programming Commands Event Logging CommandsVISTA-40Installation and Setup Guide Specifications A P P E N D I X CInterface Wiring Interface WiringVISTA-40Installation and Setup Guide Contact ID Event Codes A P P E N D I X DTABLE OF CONTACT ID EVENT CODES CodeVISTA-40Installation and Setup Guide Index Index-1VISTA-40Installation and Setup Guide Index-2Index Index-3VISTA-40Installation and Setup Guide Index-4THE LIMITATIONS OF THIS ALARM SYSTEM LIMITED WARRANTY Page Page Page Page Page Page Page 165 Eileen Way, Syosset, New York ¬19+lN7001V5 5/04 Rev A