Honeywell 3.5 manual Installing the Control, Using 2-WireSmoke Detectors on Zone, Step Action

Page 17
Using 2-Wire Smoke Detectors on Zone 1

Using 2-Wire Smoke Detectors on Zone 1

Zone 1 can support up to 16 2-wire smoke detectors.

The alarm current on zone 1 supports only one smoke detector in the alarmed state.

Compatible 2-Wire Smoke Detectors

Section 3 - Installing the Control

2kEOLR

(+)

10

(+)

SMOKE

ZONE1

 

 

 

2-WIRE SMOKE

 

 

 

DETECTOR

 

 

(-)

11

(-)

DETECTOR TYPE

Photoelectric, direct-wire

Photoelectric w/heat sensor, direct-wire

Photoelectric w/B401B base

Photoelectric w/heat sensor & B401B

Ionization, direct-wire

Ionization w/B401B base

Photoelectric duct detect (DH400 base)

Photoelectric duct detect (DH400 base)

Ionization duct detector (DH400 base)

Ionization, direct-wire

Ionization w/B110LP base

Photoelectric, direct-wire

Photoelectric w/heat sensor, direct-wire

Photoelectric w/B110LP base

DEVICE MODEL #

System Sensor 2400

System Sensor 2400TH

System Sensor 2451

System Sensor 2451TH

System Sensor 1400

System Sensor 1451

System Sensor 2451

System Sensor 2451

System Sensor 1451DH

System Sensor 1100

System Sensor 1151

System Sensor 2100

System Sensor 2100T

System Sensor 2151

Figure 3-10: 2-Wire Smoke Detector on Zone 1

Using 4-Wire Smoke Detectors on Zones 1-8

You may use as many 4-wire smoke detectors as can be powered from the panel’s Auxiliary Power output without exceeding the output’s rating (750mA).

Auxiliary power to 4-wire smoke detectors is not automatically reset after an alarm, and therefore must be momentarily interrupted using a 4204 Relay Module.

Compatible 4-Wire Smoke Detectors

Use any UL Listed 4-wire smoke detector that is rated for 10-14VDC operation and that has alarm reset time not exceeding 6 seconds. Some compatible 4-wire smoke detectors are listed below.

These smoke detectors are UL Listed for use UL with the VISTA-40 and are the only 2-wire

smoke detectors that may be used.

Wiring 2-Wire Smoke Detectors to Zone 1

2K EOL resistors must be used on fire zones and must be connected across the loop wires of each zone at the last detector.

To wire 2-wire smoke detectors to zone 1, perform the following steps:

Step Action

1Select up to 16 2-wire smoke detectors from the list of compatible detectors.

2Connect 2-wire smoke detectors across zone 1 terminals (10 and 11) as shown in Figure 3- 10. Observe proper polarity when connecting the detectors.

3Connect the EOL resistor at the last detector in the loop across the zone 1 terminals. The

EOL resistor must be connected across the loop wires at the last detector.

Detector Type

Detector Model #

Photoelectric, direct wire

System Sensor 2412

Photoelectric w/heat

System Sensor 2412TH

sensor, direct wire

 

Ionization, direct wire

System Sensor 1412

 

 

Wiring 4-Wire Smoke Detectors

 

 

UL

Power to 4-wire smoke detectors must be

supervised with an EOL device (use a System

Sensor A77-716B EOL relay module connected as shown in Figure 3-11).

To wire 4-wire smoke detectors to zones 1-8, perform the following steps:

Step Action

1Select 4-wire smoke detectors (see list of compatible detectors shown previously in this section).

2Connect detectors (including heat detectors, if used) across terminals of the zone selected. All detectors must be wired in parallel. See Figure 3-11.

3Connect the EOLR at the last detector in the loop across the zone’s terminals. You must connect the EOLR across the loop wires at the last detector.

3-7

Image 17
Contents 3DUWLWLRQHG6HFXULW\6\VWHP $0&29,67$QVWDOODWLRQDQG6HWXS*XLGH N7001V5 5/04 Rev APage Table of Contents Index List of Figures PRODUCT MODEL NUMBERS Conventions Used in This ManualGeneral Description FeaturesS E C T I O N About the VISTA-40Event Log VISTA-40Installation and Setup GuideAdditional Features Partitioning Setting-Upa Partitioned SystemTheory of Partitioning S E C T I O NVISTA-40Installation and Setup Guide Installing the Cabinet Lock Installing the ControlMounting the Control Cabinet Grade A Mercantile Premises Listing GuidelinesStep Action Installing the Control’s Circuit BoardVISTA-40Installation and Setup Guide Section 3 - Installing the Control Installing the KeypadsWire Run Length/Gauge Table Wire GaugeVISTA-40Installation and Setup Guide Installing External SoundersAlarm Output Supervision Wiring the Alarm OutputSection 3 - Installing the Control Telephone Line ConnectionsSupervising the Alarm Output Using a Siren DriverFigure 3-9 Wiring Connections for Zones VISTA-40Installation and Setup GuideTERMINALS ON CONTROLUsing 2-WireSmoke Detectors on Zone Section 3 - Installing the ControlCompatible 2-WireSmoke Detectors Using 4-WireSmoke Detectors on ZonesUsing Smoke Power Reversal Module VISTA-40InstallationTOand Setup GuideInstalling the 333PRM Smoke Detectors Compatible with the 333PRMFOUR-WIREDETECTOR CIRCUIT Section 3 - Installing the ControlFOUR-WIREDETECTOR CIRCUIT CONTROL PANELVISTA-40Installation and Setup Guide Installing RPM DevicesUsing 2-WireLatching Glassbreaks on Zone 3-103-11 Section 3 - Installing the ControlStep Action Figure 3-16 Polling Loop Connections to theUsing the 4297 Polling Loop Extender VISTA-40Installation and Setup Guide3-12 Polling Loop SupervisionSection 3 - Installing the Control Wireless Zone ExpansionRF System Installation Advisories Installation and Setup of the 5881 RF Receivers3-14 VISTA-40Installation and Setup GuideStep Action StepInstalling the 5800TM Module Section 3 - Installing the ControlThe 5800TM must not be installed within 5800 Series Transmitter SetupVISTA-40Installation and Setup Guide Installing Relay DevicesTransmitter Battery Life Installing the 4204 Relay ModulesSection 3 - Installing the Control Installing the Ground Start ModuleInstalling X10 Devices The wire that reads + 50VDC is the RING sideVISTA-40Installation and Setup Guide Installing a Remote KeyswitchKeyswitch Tamper Operation Wiring for the Remote KeyswitchRemote Keypad Sounder Installing a 4100SMLong Range Radio Connected to the J7 Triggers Section 3 - Installing the ControlVISTA-40Installation and Setup Guide Installing the 4285/4286 VIP ModuleConnecting the 4100SM to a Serial Printer UL installations3-21 Section 3 - Installing the ControlStep Action Step Action3-22 Installing the Audio Alarm Verification ModuleVISTA-40Installation and Setup Guide Section 3 - Installing the Control Connecting the Transformer3-23 UVCM AND UVST SUMMARY OF CONNECTIONSPower Limiting Outputs VISTA-40Installation and Setup Guide3-24 OutputPanel Earth Ground Connections Determining the Control’s Power Supply LoadSection 3 - Installing the Control AC Power Outlet Ground Available fromVISTA-40Installation and Setup Guide Determining the Size of the Standby BatteryTable 3 Alarm Output Current Load AlarmTable 6 Battery Selection Table Section 3 - Installing the ControlRecommended Battery 3-273-28 VISTA-40Installation and Setup GuideProgram Modes ProgrammingEntering and Exiting Programming Mode Data Field Programming ModeVISTA-40Installation and Setup Guide #93 Menu Mode ProgrammingEntry Errors 1Enter Program Mode Installer Code +#93 Menu Mode Programming Commands VISTA-40Installation and Setup GuideMAIN MENU OPTIONSVISTA-40Installation and Setup Guide Zone Number DesignationsZone Defaults Communication DefaultsCommunication Defaults for Zones Zone Response Type DefinitionsType 05 Trouble by Day/Alarm by Night Section 4 - ProgrammingVISTA-40Installation and Setup Guide Zone Input Type DefinitionsType 06 24-HourSilent Alarm Type 07 24-HourAudible AlarmProgramming for 4100SM Programming for Access ControlSection 4 - Programming StepVISTA-40Installation and Setup Guide About Data Field Programming Data Field DescriptionsProgramming Data Fields Installer CodeAlarm Sounder Duration partition-specific VISTA-40Installation and Setup GuideKeyswitch Assignment Prevent Fire TimeoutPower-Upin Previous State 24 25 26PABX Access Code Section 5 - Data Field DescriptionsVISTA-40Installation and Setup Guide 38 39Download Command Enables Enable Open/Close report for KeyswitchSection 5 - Data Field Descriptions 45 46 47 48 49FIELD TITLE and DATA ENTRIESVISTA-40Installation and Setup Guide 59 60 61 62Alarm Code for Zones Alarm Code for ZonesSupervisory and Restore Codes 74 75 76 77Alarm Code for Zones Alarm Code for ZonesVISTA-40Installation and Setup Guide 82 83 84Non-AlarmReport Codes Second Digit Restore Report Timing1*31 1*01 1*02 1*03 1*04 1*05 1*09 1*28 1*29 1*301*33 1*341*37 1*361*38 1*391*53 1*491*57 1*582*17 2*022*18 2*19General Information Downloading PrimerRemote Downloading is not a UL Listed feature Access SecurityVISTA-40Installation and Setup Guide Getting On-Linewith a Control PanelOn-LineControl Functions Stage What HappensSection 24 - Downloading Primer Direct-WireDownloadingTelco Handoff VISTA-40Installation and Setup Guide Setting the Time and Date Setting the Real-TimeClockS E C T I O N General InformationVISTA-40Installation and Setup Guide User Codes & Levels of Authority User Access CodesLevel 0 Installer User 1 Code S E C T I O NVISTA-40Installation and Setup Guide Multiple Partition AccessEXAMPLE OF MULTIPLE PARTITION ACCESS Level 6 Duress CodesPROMPTEXPLANATION Adding a Master, Manager, or Operator CodeSection 9 - User Access Codes Adding an RF Key to an Existing User Changing a Master, Manager, or Operator CodeDeleting a Master, Manager, or Operator Code Exiting the User Edit ModeBattery Test Testing the SystemDialer Test Burglary Walk-TestCode + 5 TESTVISTA-40Installation and Setup Guide Testing Wireless TransmittersStep Action 1Enter Installer Code + Transmitter ID Sniffer ModeTrouble Conditions To the InstallerSection 10 - Testing The System Power FailureContacting Technical Support VISTA-40Installation and Setup GuideTechnical Support ATLIS-FAXFAXBACK Automated Fax Retrieval SystemUL365 Police Station Connected Burglar Alarm UL Installation RequirementsRegulatory Agency Statements A P P E N D I X AVISTA-40Installation and Setup Guide UL611/UL1610 Central Station Burglary AlarmFor Grade A Service For Grade AA ServiceFCC PART 68 NOTICE IN THE EVENT OF TELEPHONE OPERATIONAL PROBLEMSAppendix A - Regulatory Agency Statements AVIS VISTA-40Installation and Setup GuideCANADIAN EMISSIONS STATEMENTS A P P E N D I X B Summary of System CommandsUser Code Commands Programming Commands Event Logging CommandsVISTA-40Installation and Setup Guide A P P E N D I X C SpecificationsInterface Wiring Interface WiringVISTA-40Installation and Setup Guide A P P E N D I X D Contact ID Event CodesTABLE OF CONTACT ID EVENT CODES CodeVISTA-40Installation and Setup Guide Index-1 IndexIndex-2 VISTA-40Installation and Setup GuideIndex-3 IndexIndex-4 VISTA-40Installation and Setup GuideTHE LIMITATIONS OF THIS ALARM SYSTEM LIMITED WARRANTY Page Page Page Page Page Page Page N7001V5 5/04 Rev A 165 Eileen Way, Syosset, New York¬19+l