Figure 3-16: Polling Loop Connections to the

Model Number Type

7500

 

Single Technology Glassbreak Detector

 

9500

 

Dual Technology Glassbreak Detector

 

4209U

 

Universal Group Zoning Module

 

4193SN

 

Serialized 2-Zone Expander

 

4293SN

 

Serialized 1-Zone Expander

 

4190SN

 

Serialized 2-Zone Expander

 

998MX

 

Serialized PIR

 

 

 

 

UL

The 4208 must be mounted either inside the

 

control panel’s cabinet or in a separate

 

enclosure that has a tamper-supervised cover.

The 4190WH right loop must not be used, and the left loop must be EOLR-supervised.

The 4278 right loop cannot be used.

The 4194 is not UL Listed.

The 4297 must be powered from the control panel’s Auxiliary Power Output or from a UL Listed supplementary power supply.

The 7500 and 9500 detectors are not UL Listed.

For new polling loop installations, always use twisted pair wiring. In many cases, existing non-twisted pair wiring may be used, but it is more susceptible to interference from other sources, and may be problematic in installations with long wire runs or in high noise environments.

Always locate polling loop wiring at least six inches (15cm) of AC power, telephone, or intercom wiring. The polling loop carries data between the control panel and the devices; interference on this loop can cause an interruption of communication. The polling loop can also cause outgoing interference on the intercom or phone lines. If this spacing cannot be achieved, shielded wire must be used. (Note that the maximum total wire length supported is cut in half when shielded wire is used.)

Section 3 - Installing the Control

To install polling loop devices, perform the following steps:

Step Action

1Select devices from the list of compatible devices shown previously.

2Set the DIP switches in the device (if required). Refer to the device’s instructions for the DIP Switch Tables.

3Mount each device in the desired location. Refer to the device’s instructions.

4Run wires from the control panel to each device on the polling loop (see Figure 3-16). No individual wire run may exceed the lengths shown in the following table.

Maximum Polling Loop Wire Runs

 

Wire Gauge

Max. Length

 

 

#22 gauge

650 feet

 

 

#20 gauge

950 feet

 

 

#18 gauge

1500 feet

 

 

#16 gauge

2400 feet

 

 

 

 

 

5Wire each device to the polling loop, making sure of the correct polarity (refer to the device’s instructions).

NOTE: If you are using serial number devices, and intend to enroll each device through the keypad automatically, wire no more than 25 of these devices to the control at a time. Then power up and program them before connecting the next 25. Leave previously enrolled devices connected. If you intend to manually enter the serial numbers through the keypad or through Compass downloading software, all the devices may be connected before powering up to program.

21

22

23

24

25

No more than 64mA may be drawn on any individual wire run.

When a star configuration is used, the total length of all wire runs combined cannot exceed 4000 ft (2000 ft. if you are using unshielded wire in conduit or shielded wire).

IMPORTANT NOTE: If the installation exceeds or deviates from these parameters, refer to the application note on the Honeywell website for additional information. To access the application note:

1.

Go to the honeywell.com/security website

2.

Click the Honeywell Security & Custom Electronics link.

POLLING LOOP RATING: 128mA MAXIMUM

+ LOOPPOLLING

4190 RPM

4192SD

SMOKE

4278

PIR

-

TO RIGHT LOOP

poll_loop-001-V0

3.

Click the Commercial link.

4.

Click the Documentation link.

5.

Click the V-Plex Application Note.

Figure 3-16: Polling Loop Connections to the

VISTA-40

3-11

Image 21
Contents 3DUWLWLRQHG6HFXULW\6\VWHP $0&29,67$QVWDOODWLRQDQG6HWXS*XLGH N7001V5 5/04 Rev APage Table of Contents Index List of Figures PRODUCT MODEL NUMBERS Conventions Used in This ManualGeneral Description FeaturesS E C T I O N About the VISTA-40VISTA-40Installation and Setup Guide Additional FeaturesEvent Log Partitioning Setting-Upa Partitioned SystemTheory of Partitioning S E C T I O NVISTA-40Installation and Setup Guide Installing the Cabinet Lock Installing the ControlMounting the Control Cabinet Grade A Mercantile Premises Listing GuidelinesInstalling the Control’s Circuit Board VISTA-40Installation and Setup GuideStep Action Section 3 - Installing the Control Installing the KeypadsWire Run Length/Gauge Table Wire GaugeVISTA-40Installation and Setup Guide Installing External SoundersAlarm Output Supervision Wiring the Alarm OutputSection 3 - Installing the Control Telephone Line ConnectionsSupervising the Alarm Output Using a Siren DriverFigure 3-9 Wiring Connections for Zones VISTA-40Installation and Setup GuideTERMINALS ON CONTROLUsing 2-WireSmoke Detectors on Zone Section 3 - Installing the ControlCompatible 2-WireSmoke Detectors Using 4-WireSmoke Detectors on ZonesUsing Smoke Power Reversal Module VISTA-40InstallationTOand Setup GuideInstalling the 333PRM Smoke Detectors Compatible with the 333PRMFOUR-WIREDETECTOR CIRCUIT Section 3 - Installing the ControlFOUR-WIREDETECTOR CIRCUIT CONTROL PANELVISTA-40Installation and Setup Guide Installing RPM DevicesUsing 2-WireLatching Glassbreaks on Zone 3-103-11 Section 3 - Installing the ControlStep Action Figure 3-16 Polling Loop Connections to theUsing the 4297 Polling Loop Extender VISTA-40Installation and Setup Guide3-12 Polling Loop SupervisionSection 3 - Installing the Control Wireless Zone ExpansionRF System Installation Advisories Installation and Setup of the 5881 RF Receivers3-14 VISTA-40Installation and Setup GuideStep Action StepInstalling the 5800TM Module Section 3 - Installing the ControlThe 5800TM must not be installed within 5800 Series Transmitter SetupVISTA-40Installation and Setup Guide Installing Relay DevicesTransmitter Battery Life Installing the 4204 Relay ModulesSection 3 - Installing the Control Installing the Ground Start ModuleInstalling X10 Devices The wire that reads + 50VDC is the RING sideVISTA-40Installation and Setup Guide Installing a Remote KeyswitchKeyswitch Tamper Operation Wiring for the Remote KeyswitchRemote Keypad Sounder Installing a 4100SMLong Range Radio Connected to the J7 Triggers Section 3 - Installing the ControlVISTA-40Installation and Setup Guide Installing the 4285/4286 VIP ModuleConnecting the 4100SM to a Serial Printer UL installations3-21 Section 3 - Installing the ControlStep Action Step ActionInstalling the Audio Alarm Verification Module VISTA-40Installation and Setup Guide3-22 Section 3 - Installing the Control Connecting the Transformer3-23 UVCM AND UVST SUMMARY OF CONNECTIONSPower Limiting Outputs VISTA-40Installation and Setup Guide3-24 OutputPanel Earth Ground Connections Determining the Control’s Power Supply LoadSection 3 - Installing the Control AC Power Outlet Ground Available fromVISTA-40Installation and Setup Guide Determining the Size of the Standby BatteryTable 3 Alarm Output Current Load AlarmTable 6 Battery Selection Table Section 3 - Installing the ControlRecommended Battery 3-273-28 VISTA-40Installation and Setup GuideProgram Modes ProgrammingEntering and Exiting Programming Mode Data Field Programming ModeVISTA-40Installation and Setup Guide #93 Menu Mode ProgrammingEntry Errors 1Enter Program Mode Installer Code +#93 Menu Mode Programming Commands VISTA-40Installation and Setup GuideMAIN MENU OPTIONSVISTA-40Installation and Setup Guide Zone Number DesignationsZone Defaults Communication DefaultsCommunication Defaults for Zones Zone Response Type DefinitionsType 05 Trouble by Day/Alarm by Night Section 4 - ProgrammingVISTA-40Installation and Setup Guide Zone Input Type DefinitionsType 06 24-HourSilent Alarm Type 07 24-HourAudible AlarmProgramming for 4100SM Programming for Access ControlSection 4 - Programming StepVISTA-40Installation and Setup Guide About Data Field Programming Data Field DescriptionsProgramming Data Fields Installer CodeAlarm Sounder Duration partition-specific VISTA-40Installation and Setup GuideKeyswitch Assignment Prevent Fire TimeoutPower-Upin Previous State 24 25 26PABX Access Code Section 5 - Data Field DescriptionsVISTA-40Installation and Setup Guide 38 39Download Command Enables Enable Open/Close report for KeyswitchSection 5 - Data Field Descriptions 45 46 47 48 49FIELD TITLE and DATA ENTRIESVISTA-40Installation and Setup Guide 59 60 61 62Alarm Code for Zones Alarm Code for ZonesSupervisory and Restore Codes 74 75 76 77Alarm Code for Zones Alarm Code for ZonesVISTA-40Installation and Setup Guide 82 83 84Non-AlarmReport Codes Second Digit Restore Report Timing1*31 1*01 1*02 1*03 1*04 1*05 1*09 1*28 1*29 1*301*33 1*341*37 1*361*38 1*391*53 1*491*57 1*582*17 2*022*18 2*19General Information Downloading PrimerRemote Downloading is not a UL Listed feature Access SecurityVISTA-40Installation and Setup Guide Getting On-Linewith a Control PanelOn-LineControl Functions Stage What HappensDirect-WireDownloading Telco HandoffSection 24 - Downloading Primer VISTA-40Installation and Setup Guide Setting the Time and Date Setting the Real-TimeClockS E C T I O N General InformationVISTA-40Installation and Setup Guide User Codes & Levels of Authority User Access CodesLevel 0 Installer User 1 Code S E C T I O NVISTA-40Installation and Setup Guide Multiple Partition AccessEXAMPLE OF MULTIPLE PARTITION ACCESS Level 6 Duress CodesAdding a Master, Manager, or Operator Code Section 9 - User Access CodesPROMPTEXPLANATION Adding an RF Key to an Existing User Changing a Master, Manager, or Operator CodeDeleting a Master, Manager, or Operator Code Exiting the User Edit ModeBattery Test Testing the SystemDialer Test Burglary Walk-TestCode + 5 TESTVISTA-40Installation and Setup Guide Testing Wireless TransmittersStep Action 1Enter Installer Code + Transmitter ID Sniffer ModeTrouble Conditions To the InstallerSection 10 - Testing The System Power FailureContacting Technical Support VISTA-40Installation and Setup GuideTechnical Support ATLIS-FAXFAXBACK Automated Fax Retrieval SystemUL365 Police Station Connected Burglar Alarm UL Installation RequirementsRegulatory Agency Statements A P P E N D I X AVISTA-40Installation and Setup Guide UL611/UL1610 Central Station Burglary AlarmFor Grade A Service For Grade AA ServiceIN THE EVENT OF TELEPHONE OPERATIONAL PROBLEMS Appendix A - Regulatory Agency StatementsFCC PART 68 NOTICE VISTA-40Installation and Setup Guide CANADIAN EMISSIONS STATEMENTSAVIS A P P E N D I X B Summary of System CommandsUser Code Commands Programming Commands Event Logging CommandsVISTA-40Installation and Setup Guide A P P E N D I X C SpecificationsInterface Wiring Interface WiringVISTA-40Installation and Setup Guide A P P E N D I X D Contact ID Event CodesTABLE OF CONTACT ID EVENT CODES CodeVISTA-40Installation and Setup Guide Index-1 IndexIndex-2 VISTA-40Installation and Setup GuideIndex-3 IndexIndex-4 VISTA-40Installation and Setup GuideTHE LIMITATIONS OF THIS ALARM SYSTEM LIMITED WARRANTY Page Page Page Page Page Page Page 165 Eileen Way, Syosset, New York ¬19+lN7001V5 5/04 Rev A