VISTA-40 Installation and Setup Guide

FIELD

TITLE and DATA ENTRIES

EXPLANATION

 

 

 

*82

*83

*84

*85

*86

Non-Alarm Report Codes (Second Digit

Enter 00-15.

First Test Report Time

Enter 00-07the for day (01 = Monday) Enter 00-23for the hour

Enter 00-59for the minutes

Swinger Suppression (partition- specific)

Enter 01-15.

Enter 00 for unlimited reports

Enable Dialer Reports for Panics & Duress (partition-specific)

0 = disable

1 = enable

4208 Module Zone Assignment

0 = other configurations

1 = 10-17 only

This field has ten two-digit entries as follows: Close, Open, Low Battery, Low Battery Restore, AC Loss, AC Restore, Test, Power-up, Cancel, and Program Tamper. Enter the report code 01-15for each type of report.

Enter 00 for no report.

Enter the day and time that the first Test report shall be transmitted. Enter 00 in all locations if the Test report is to be sent immediately upon exiting. Enter 00 in the day location if the report is to be sent at the next occurrence of the time that is set.

This option limits the number of messages (alarms or troubles) sent for a specific zone in an armed period.

Must be 00 for UL installations.

This field has four entries as follows: Zone 95, 96, 99, and Duress. Enable for each partition that the panics and duress reporting is desired.

NOTE: Non-zero report code must be assigned to zone 92 to enable Duress reporting.

Entering 1 allows a single 4208 to be set to zone numbers 10-17, but precludes the use of any other polling loop devices.

Entering 0 allows all other configurations, such as no 4208, more than one 4208, or other polling loop expansion present.

4208 Zone #s available when:

When *86 = 1 4208 DIP switches must be set to:

 

 

 

 

*86 = 1

10-17

Precludes use of any other polling loop expansion

*86 = 0

10-16

17-24

25-32

33-40

41-48

49-56

57-64

With word OFF

sw 2 = ON

sw 3 = ON

sw 4 = ON

sw 5 = OFF

With word ON

sw 2 = OFF

sw 3 = OFF

sw 4 = OFF

sw 5 = ON

*87

*88

*89

Entry Warning (partition-specific)

0 = 3 short beeps

1 = slow continuous beeps

Burglary Alarm Communicator Delay (partition-specific)

0 = no delay

1 = 16-second delay

Restore Report Timing

0 = instant

1 = after bell timeout

2 = when system is disarmed

Select the type of warning for the entry delay period.

Select the delay, if any, for burglary alarm communications.

Must be 0 for UL installations.

Select the time when restore reports are sent after an alarm.

Must be 2 for UL installations.

*90

Secondary Subscriber Account Number (partition-specific)

Enter 00-09; B-F (11-15)

Enter a 3- or 4-digit (depending on report format) secondary subscriber account number. Each number requires a 2-digit entry so as to allow entry of hexadecimal digits (B-F). If a 3-digit account number is to be used, enter data only in the first 3 locations, and enter * in the fourth location.

NOTE: This field must be programmed if a secondary phone number is used (field *34). This account number can be the same as the primary account number.

5-8

Image 54
Contents QVWDOODWLRQDQG6HWXS*XLGH $0&29,67$3DUWLWLRQHG6HFXULW\6\VWHP N7001V5 5/04 Rev APage Table of Contents Index List of Figures Conventions Used in This Manual PRODUCT MODEL NUMBERSS E C T I O N FeaturesGeneral Description About the VISTA-40VISTA-40Installation and Setup Guide Additional FeaturesEvent Log Theory of Partitioning Setting-Upa Partitioned SystemPartitioning S E C T I O NVISTA-40Installation and Setup Guide Mounting the Control Cabinet Installing the ControlInstalling the Cabinet Lock Grade A Mercantile Premises Listing GuidelinesInstalling the Control’s Circuit Board VISTA-40Installation and Setup GuideStep Action Wire Run Length/Gauge Table Installing the KeypadsSection 3 - Installing the Control Wire GaugeAlarm Output Supervision Installing External SoundersVISTA-40Installation and Setup Guide Wiring the Alarm OutputSupervising the Alarm Output Telephone Line ConnectionsSection 3 - Installing the Control Using a Siren DriverTERMINALS VISTA-40Installation and Setup GuideFigure 3-9 Wiring Connections for Zones ON CONTROLCompatible 2-WireSmoke Detectors Section 3 - Installing the ControlUsing 2-WireSmoke Detectors on Zone Using 4-WireSmoke Detectors on ZonesInstalling the 333PRM VISTA-40InstallationTOand Setup GuideUsing Smoke Power Reversal Module Smoke Detectors Compatible with the 333PRMFOUR-WIREDETECTOR CIRCUIT Section 3 - Installing the ControlFOUR-WIREDETECTOR CIRCUIT CONTROL PANELUsing 2-WireLatching Glassbreaks on Zone Installing RPM DevicesVISTA-40Installation and Setup Guide 3-10Step Action Section 3 - Installing the Control3-11 Figure 3-16 Polling Loop Connections to the3-12 VISTA-40Installation and Setup GuideUsing the 4297 Polling Loop Extender Polling Loop SupervisionRF System Installation Advisories Wireless Zone ExpansionSection 3 - Installing the Control Installation and Setup of the 5881 RF ReceiversStep Action VISTA-40Installation and Setup Guide3-14 StepThe 5800TM must not be installed within Section 3 - Installing the ControlInstalling the 5800TM Module 5800 Series Transmitter SetupTransmitter Battery Life Installing Relay DevicesVISTA-40Installation and Setup Guide Installing the 4204 Relay ModulesInstalling X10 Devices Installing the Ground Start ModuleSection 3 - Installing the Control The wire that reads + 50VDC is the RING sideKeyswitch Tamper Operation Installing a Remote KeyswitchVISTA-40Installation and Setup Guide Wiring for the Remote KeyswitchLong Range Radio Connected to the J7 Triggers Installing a 4100SMRemote Keypad Sounder Section 3 - Installing the ControlConnecting the 4100SM to a Serial Printer Installing the 4285/4286 VIP ModuleVISTA-40Installation and Setup Guide UL installationsStep Action Section 3 - Installing the Control3-21 Step ActionInstalling the Audio Alarm Verification Module VISTA-40Installation and Setup Guide3-22 3-23 Connecting the TransformerSection 3 - Installing the Control UVCM AND UVST SUMMARY OF CONNECTIONS3-24 VISTA-40Installation and Setup GuidePower Limiting Outputs OutputSection 3 - Installing the Control Determining the Control’s Power Supply LoadPanel Earth Ground Connections AC Power Outlet Ground Available fromTable 3 Alarm Output Current Load Determining the Size of the Standby BatteryVISTA-40Installation and Setup Guide AlarmRecommended Battery Section 3 - Installing the ControlTable 6 Battery Selection Table 3-27VISTA-40Installation and Setup Guide 3-28Entering and Exiting Programming Mode ProgrammingProgram Modes Data Field Programming ModeEntry Errors #93 Menu Mode ProgrammingVISTA-40Installation and Setup Guide 1Enter Program Mode Installer Code +MAIN MENU VISTA-40Installation and Setup Guide#93 Menu Mode Programming Commands OPTIONSZone Defaults Zone Number DesignationsVISTA-40Installation and Setup Guide Communication DefaultsType 05 Trouble by Day/Alarm by Night Zone Response Type DefinitionsCommunication Defaults for Zones Section 4 - ProgrammingType 06 24-HourSilent Alarm Zone Input Type DefinitionsVISTA-40Installation and Setup Guide Type 07 24-HourAudible AlarmSection 4 - Programming Programming for Access ControlProgramming for 4100SM StepVISTA-40Installation and Setup Guide Programming Data Fields Data Field DescriptionsAbout Data Field Programming Installer CodeKeyswitch Assignment VISTA-40Installation and Setup GuideAlarm Sounder Duration partition-specific Prevent Fire TimeoutPABX Access Code 24 25 26Power-Upin Previous State Section 5 - Data Field DescriptionsDownload Command Enables 38 39VISTA-40Installation and Setup Guide Enable Open/Close report for KeyswitchFIELD 45 46 47 48 49Section 5 - Data Field Descriptions TITLE and DATA ENTRIESAlarm Code for Zones 59 60 61 62VISTA-40Installation and Setup Guide Alarm Code for ZonesAlarm Code for Zones 74 75 76 77Supervisory and Restore Codes Alarm Code for ZonesNon-AlarmReport Codes Second Digit 82 83 84VISTA-40Installation and Setup Guide Restore Report Timing1*33 1*01 1*02 1*03 1*04 1*05 1*09 1*28 1*29 1*301*31 1*341*38 1*361*37 1*391*57 1*491*53 1*582*18 2*022*17 2*19Remote Downloading is not a UL Listed feature Downloading PrimerGeneral Information Access SecurityOn-LineControl Functions Getting On-Linewith a Control PanelVISTA-40Installation and Setup Guide Stage What HappensDirect-WireDownloading Telco HandoffSection 24 - Downloading Primer VISTA-40Installation and Setup Guide S E C T I O N Setting the Real-TimeClockSetting the Time and Date General InformationVISTA-40Installation and Setup Guide Level 0 Installer User 1 Code User Access CodesUser Codes & Levels of Authority S E C T I O NEXAMPLE OF MULTIPLE PARTITION ACCESS Multiple Partition AccessVISTA-40Installation and Setup Guide Level 6 Duress CodesAdding a Master, Manager, or Operator Code Section 9 - User Access CodesPROMPTEXPLANATION Deleting a Master, Manager, or Operator Code Changing a Master, Manager, or Operator CodeAdding an RF Key to an Existing User Exiting the User Edit ModeDialer Test Testing the SystemBattery Test Burglary Walk-TestCode + 5 TESTStep Action 1Enter Installer Code + Testing Wireless TransmittersVISTA-40Installation and Setup Guide Transmitter ID Sniffer ModeSection 10 - Testing The System To the InstallerTrouble Conditions Power FailureTechnical Support VISTA-40Installation and Setup GuideContacting Technical Support ATLIS-FAXFAXBACK Automated Fax Retrieval SystemRegulatory Agency Statements UL Installation RequirementsUL365 Police Station Connected Burglar Alarm A P P E N D I X AFor Grade A Service UL611/UL1610 Central Station Burglary AlarmVISTA-40Installation and Setup Guide For Grade AA ServiceIN THE EVENT OF TELEPHONE OPERATIONAL PROBLEMS Appendix A - Regulatory Agency StatementsFCC PART 68 NOTICE VISTA-40Installation and Setup Guide CANADIAN EMISSIONS STATEMENTSAVIS User Code Commands Programming Commands Summary of System CommandsA P P E N D I X B Event Logging CommandsVISTA-40Installation and Setup Guide Interface Wiring SpecificationsA P P E N D I X C Interface WiringVISTA-40Installation and Setup Guide TABLE OF CONTACT ID EVENT CODES Contact ID Event CodesA P P E N D I X D CodeVISTA-40Installation and Setup Guide Index Index-1VISTA-40Installation and Setup Guide Index-2Index Index-3VISTA-40Installation and Setup Guide Index-4THE LIMITATIONS OF THIS ALARM SYSTEM LIMITED WARRANTY Page Page Page Page Page Page Page 165 Eileen Way, Syosset, New York ¬19+lN7001V5 5/04 Rev A