Honeywell 3.5 Installing the Control, 3-15, Installing the 5800TM Module, Step Action, antennas

Page 25
Installing the 5800TM Module

Section 3 - Installing the Control

Installing the 5800TM Module

Installation of this module is necessary only if you are using a 5827BD or 5804BD Bi-directional device.

The address for the 5800TM must be enabled in the control’s Device Programming in the #93 Menu Mode as a keypad and then assigned to a partition.

To install the 5800TM, perform the following steps:

Step Action

1

Mount the unit using its accompanying

 

mounting bracket near the RF receiver.

 

The 5800TM must not be installed within

 

the control cabinet. It must be between

 

one and two feet from the receiver’s

 

antennas.

2

Set the module for the appropriate address.

 

For Address Setting 28 cut the red jumper;

 

for Address 29 cut the white jumper; for

 

Address 30 cut both jumpers.

5800 Series Transmitter Setup

5800 Series transmitters have the following characteristics:

Transmitters have built-in serial numbers that must be enrolled in the system using the #93 Menu Mode Programming, or input to the control via the downloader.

Transmitters do not have DIP switches (except 5827, described separately).

Some transmitters, such as the 5816 and 5817, can support more than one “zone” (referred to as loops or inputs). Each loop must be assigned a different zone number.

For button-type transmitters (wireless keys), such as the 5804 and 5804BD, you must assign a unique zone number to each individual button used on the transmitter.

Transmitter Input Types

All transmitters have one or more unique factory- assigned input (loop) codes. Transmitters can be programmed as one of the following types:

3

Connect the module’s wire harness to the

 

keypad terminals (6, 7, 8, and 9). Plug the

 

connector at the other end of the harness into

 

the module.

House ID Sniffer Mode

This mode applies only if you are using a wireless keypad (e.g., 5827) or bi-directional devices (e.g., 5804BD). Use the House ID Sniffer mode to make sure you do not choose a House ID that is in use in a nearby system. The House ID must be programmed for the receiver in Device Programming in the #93 Menu Mode.

To enter House ID Sniffer mode, enter your Installer

Type

RF (Supervised RF)

UR (Unsupervised RF)

BR (Unsupervised Button RF)

Description

Sends periodic check-in signals, as well as fault, restore, and low-battery signals. The transmitter must remain within the receiver’s range.

Sends all the signals that the RF type does, but the control does not supervise the check-in signals. The transmitter may therefore be carried off-premises.

These send only fault signals. They do not send low-battery signals until they are activated. The transmitter may be carried off- premises.

Code + [#] + [2].

The receiver now “sniffs” out any House IDs in the area and displays them. Keep the receiver in this mode for about 2 hours. Use a House ID that is not displayed. Exit the Sniffer mode by entering your Installer Code

+ OFF.

As Sniffer mode effectively disables RF point reception, Sniffer mode cannot be entered while any partition is armed.

Transmitter Supervision

Supervised RF transmitters send a check-in signal to the receiver at 70–90 minute intervals. If at least one check-in is not received from each supervised transmitter within a programmed period (field 1∗31), the “missing” transmitter number(s) and “CHECK” or “TRBL” are displayed. Unsupervised RF transmitters (5802MN, 5804) may be carried off the premises.

Some transmitters have built-in tamper protection, and annunciate a “CHECK” condition if covers are removed.

If a loss of supervision occurs on a transmitter programmed for Fire, it reports in Contact ID as a Fire Trouble (373), not Loss of Supervision (381), to the central station.

3-15

Image 25
Contents 3DUWLWLRQHG6HFXULW\6\VWHP $0&29,67$QVWDOODWLRQDQG6HWXS*XLGH N7001V5 5/04 Rev APage Table of Contents Index List of Figures PRODUCT MODEL NUMBERS Conventions Used in This ManualGeneral Description FeaturesS E C T I O N About the VISTA-40Additional Features VISTA-40Installation and Setup GuideEvent Log Partitioning Setting-Upa Partitioned SystemTheory of Partitioning S E C T I O NVISTA-40Installation and Setup Guide Installing the Cabinet Lock Installing the ControlMounting the Control Cabinet Grade A Mercantile Premises Listing GuidelinesVISTA-40Installation and Setup Guide Installing the Control’s Circuit BoardStep Action Section 3 - Installing the Control Installing the KeypadsWire Run Length/Gauge Table Wire GaugeVISTA-40Installation and Setup Guide Installing External SoundersAlarm Output Supervision Wiring the Alarm OutputSection 3 - Installing the Control Telephone Line ConnectionsSupervising the Alarm Output Using a Siren DriverFigure 3-9 Wiring Connections for Zones VISTA-40Installation and Setup GuideTERMINALS ON CONTROLUsing 2-WireSmoke Detectors on Zone Section 3 - Installing the ControlCompatible 2-WireSmoke Detectors Using 4-WireSmoke Detectors on ZonesUsing Smoke Power Reversal Module VISTA-40InstallationTOand Setup GuideInstalling the 333PRM Smoke Detectors Compatible with the 333PRMFOUR-WIREDETECTOR CIRCUIT Section 3 - Installing the ControlFOUR-WIREDETECTOR CIRCUIT CONTROL PANELVISTA-40Installation and Setup Guide Installing RPM DevicesUsing 2-WireLatching Glassbreaks on Zone 3-103-11 Section 3 - Installing the ControlStep Action Figure 3-16 Polling Loop Connections to theUsing the 4297 Polling Loop Extender VISTA-40Installation and Setup Guide3-12 Polling Loop SupervisionSection 3 - Installing the Control Wireless Zone ExpansionRF System Installation Advisories Installation and Setup of the 5881 RF Receivers3-14 VISTA-40Installation and Setup GuideStep Action StepInstalling the 5800TM Module Section 3 - Installing the ControlThe 5800TM must not be installed within 5800 Series Transmitter SetupVISTA-40Installation and Setup Guide Installing Relay DevicesTransmitter Battery Life Installing the 4204 Relay ModulesSection 3 - Installing the Control Installing the Ground Start ModuleInstalling X10 Devices The wire that reads + 50VDC is the RING sideVISTA-40Installation and Setup Guide Installing a Remote KeyswitchKeyswitch Tamper Operation Wiring for the Remote KeyswitchRemote Keypad Sounder Installing a 4100SMLong Range Radio Connected to the J7 Triggers Section 3 - Installing the ControlVISTA-40Installation and Setup Guide Installing the 4285/4286 VIP ModuleConnecting the 4100SM to a Serial Printer UL installations3-21 Section 3 - Installing the ControlStep Action Step ActionVISTA-40Installation and Setup Guide Installing the Audio Alarm Verification Module3-22 Section 3 - Installing the Control Connecting the Transformer3-23 UVCM AND UVST SUMMARY OF CONNECTIONSPower Limiting Outputs VISTA-40Installation and Setup Guide3-24 OutputPanel Earth Ground Connections Determining the Control’s Power Supply LoadSection 3 - Installing the Control AC Power Outlet Ground Available fromVISTA-40Installation and Setup Guide Determining the Size of the Standby BatteryTable 3 Alarm Output Current Load AlarmTable 6 Battery Selection Table Section 3 - Installing the ControlRecommended Battery 3-273-28 VISTA-40Installation and Setup GuideProgram Modes ProgrammingEntering and Exiting Programming Mode Data Field Programming ModeVISTA-40Installation and Setup Guide #93 Menu Mode ProgrammingEntry Errors 1Enter Program Mode Installer Code +#93 Menu Mode Programming Commands VISTA-40Installation and Setup GuideMAIN MENU OPTIONSVISTA-40Installation and Setup Guide Zone Number DesignationsZone Defaults Communication DefaultsCommunication Defaults for Zones Zone Response Type DefinitionsType 05 Trouble by Day/Alarm by Night Section 4 - ProgrammingVISTA-40Installation and Setup Guide Zone Input Type DefinitionsType 06 24-HourSilent Alarm Type 07 24-HourAudible AlarmProgramming for 4100SM Programming for Access ControlSection 4 - Programming StepVISTA-40Installation and Setup Guide About Data Field Programming Data Field DescriptionsProgramming Data Fields Installer CodeAlarm Sounder Duration partition-specific VISTA-40Installation and Setup GuideKeyswitch Assignment Prevent Fire TimeoutPower-Upin Previous State 24 25 26PABX Access Code Section 5 - Data Field DescriptionsVISTA-40Installation and Setup Guide 38 39Download Command Enables Enable Open/Close report for KeyswitchSection 5 - Data Field Descriptions 45 46 47 48 49FIELD TITLE and DATA ENTRIESVISTA-40Installation and Setup Guide 59 60 61 62Alarm Code for Zones Alarm Code for ZonesSupervisory and Restore Codes 74 75 76 77Alarm Code for Zones Alarm Code for ZonesVISTA-40Installation and Setup Guide 82 83 84Non-AlarmReport Codes Second Digit Restore Report Timing1*31 1*01 1*02 1*03 1*04 1*05 1*09 1*28 1*29 1*301*33 1*341*37 1*361*38 1*391*53 1*491*57 1*582*17 2*022*18 2*19General Information Downloading PrimerRemote Downloading is not a UL Listed feature Access SecurityVISTA-40Installation and Setup Guide Getting On-Linewith a Control PanelOn-LineControl Functions Stage What HappensTelco Handoff Direct-WireDownloadingSection 24 - Downloading Primer VISTA-40Installation and Setup Guide Setting the Time and Date Setting the Real-TimeClockS E C T I O N General InformationVISTA-40Installation and Setup Guide User Codes & Levels of Authority User Access CodesLevel 0 Installer User 1 Code S E C T I O NVISTA-40Installation and Setup Guide Multiple Partition AccessEXAMPLE OF MULTIPLE PARTITION ACCESS Level 6 Duress CodesSection 9 - User Access Codes Adding a Master, Manager, or Operator CodePROMPTEXPLANATION Adding an RF Key to an Existing User Changing a Master, Manager, or Operator CodeDeleting a Master, Manager, or Operator Code Exiting the User Edit ModeBattery Test Testing the SystemDialer Test Burglary Walk-TestCode + 5 TESTVISTA-40Installation and Setup Guide Testing Wireless TransmittersStep Action 1Enter Installer Code + Transmitter ID Sniffer ModeTrouble Conditions To the InstallerSection 10 - Testing The System Power FailureContacting Technical Support VISTA-40Installation and Setup GuideTechnical Support ATLIS-FAXFAXBACK Automated Fax Retrieval SystemUL365 Police Station Connected Burglar Alarm UL Installation RequirementsRegulatory Agency Statements A P P E N D I X AVISTA-40Installation and Setup Guide UL611/UL1610 Central Station Burglary AlarmFor Grade A Service For Grade AA ServiceAppendix A - Regulatory Agency Statements IN THE EVENT OF TELEPHONE OPERATIONAL PROBLEMSFCC PART 68 NOTICE CANADIAN EMISSIONS STATEMENTS VISTA-40Installation and Setup GuideAVIS A P P E N D I X B Summary of System CommandsUser Code Commands Programming Commands Event Logging CommandsVISTA-40Installation and Setup Guide A P P E N D I X C SpecificationsInterface Wiring Interface WiringVISTA-40Installation and Setup Guide A P P E N D I X D Contact ID Event CodesTABLE OF CONTACT ID EVENT CODES CodeVISTA-40Installation and Setup Guide Index-1 IndexIndex-2 VISTA-40Installation and Setup GuideIndex-3 IndexIndex-4 VISTA-40Installation and Setup GuideTHE LIMITATIONS OF THIS ALARM SYSTEM LIMITED WARRANTY Page Page Page Page Page Page Page ¬19+l 165 Eileen Way, Syosset, New YorkN7001V5 5/04 Rev A