Honeywell ZyAIR G-3000 Installing the 4285/4286 VIP Module, VISTA-40Installation and Setup Guide

Page 30
Connecting the 4100SM to a Serial Printer

VISTA-40 Installation and Setup Guide

Connecting the 4100SM to a Serial Printer

To connect a serial printer using the 4100SM, refer to Figure 3-26and perform the following steps:

Step Action

1Connect terminal 1 on the 4100SM to the Violet wire on the 4142TR cable.

2Connect terminal 6 on the 4100SM to the Brown wire on the 4142TR cable.

3Connect the 4142TR cable to J8 on the control.

4Connect terminals 8 and 7 of the 4100SM to terminals 6 and 7 (aux. power (+) and (-)), respectively of the control.

5Connect the UL EDP Listed serial printer to the 4100SM Interface Module.

The 4100SM Module is supplied with a 10- foot RS232 cable. A longer cable can be used if the VISTA-40 is separated from the serial printer by more than 10 feet, but the total cable length should be less than 50 feet.

Installing the 4285/4286 VIP Module

The 4285/4286 VIP Module is an add-on accessory that permits the user to access the security system (and relays) via a TouchTone telephone. This may be done either from the premises or by calling the premises from a remote location. Only one VIP Module can be used in a security system. This module must be enabled as Device Address 4 in the Device Programming in #93 Menu Mode, and must be assigned to a partition.

UL

The 4285/4286 VIP Module is not permitted in

UL installations.

Detailed operating instructions for phone access to the security system are provided with the VIP Module.

The 4285/4286 is wired between the control panel and the premises’ handset(s) (see Figure 3-27). It listens for TouchTones on the phone line and reports them to the control panel. During on-premises phone access, it powers the premises phones. During off-premises phone access, it seizes the line from the premises phones and any answering machines.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

2

 

3

4

5

 

6

 

7

8

9

J8 CONNECTOR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NU

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

VIOLET

 

GREY

 

YELLOW

 

 

RED

 

GREEN

 

BROWN

BLUE

 

BLACK

 

 

 

 

 

 

 

 

2

PRINTER

DTR

 

3

 

GROUND

OUT

5

 

 

OUT

6

GROUND

GROUND

 

 

 

 

 

 

 

IN

 

 

 

IN

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4142TR CABLE (SUPPLIED WITH 4100SM)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

To TB6 Aux. Power (+)

4100SM SERIAL MODULE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

8

+ PWR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(25mA current draw)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

To TB7 Aux. Power (-)

 

 

7

- (GND)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6

RXD

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5

not used

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4

not used

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

TXD

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

not used

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

DTR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RED BLUE

WHITE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

USE GENDER CHANGER

3M

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SUPPLIED WITH 4100SM

Cable

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

IF PRINTER HAS DB25

Supplied with

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4100SM

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MALE CONNECTOR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4100SM JUMPERS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(CUT TO SET RESPECTIVE SIGNAL FLOATING)

 

 

 

 

 

 

V0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

COLOR

 

 

 

 

FUNCTION

 

 

 

 

 

PIN #

 

 

 

 

 

 

 

SERIAL PRINTER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SET FOR: 8 DATA BITS

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

011-

RED

 

 

 

 

 

CD

 

 

 

 

 

 

8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

EVEN PARITY

4100SM

BLUE

 

 

 

 

 

CTS

 

 

 

 

 

 

5

 

 

 

 

 

 

 

 

STOP BIT

WHITE

 

 

 

 

 

DSR

 

 

 

 

 

 

6

 

 

 

 

 

 

 

 

300/1200 BAUD

 

Figure 3-26: 4100SM Using a Serial Printer

NOTE: See the 4100SM Installation Instructions for details concerning the serial printer operation.

The 4285/4286 VIP Module features:

Allows the user to receive synthesized voice messages over the phone regarding the status of the security system.

Allows the user to arm and disarm the security system and perform most other commands using the telephone keypad.

Allows the user to control relays using the telephone keypad.

Provides voice annunciation over the phone to confirm any command that is entered.

Announces many of the same words that would normally be displayed on an alpha keypad under the same system conditions. Refer to the words in bold on the Alpha Vocabulary list found in the #93 Menu Mode in the Programming Guide.

Can be supervised for connection to control panel (annunciated and reported as Zone 804).

The VIP module will not operate until the device address (04) is enabled in the control’s Device Programming in #93 Menu Mode.

Do not mount the VIP Module on the cabinet

door or attempt to attach it to the PC board.

3-20

Image 30
Contents QVWDOODWLRQDQG6HWXS*XLGH $0&29,67$3DUWLWLRQHG6HFXULW\6\VWHP N7001V5 5/04 Rev APage Table of Contents Index List of Figures Conventions Used in This Manual PRODUCT MODEL NUMBERSS E C T I O N FeaturesGeneral Description About the VISTA-40VISTA-40Installation and Setup Guide Additional FeaturesEvent Log Theory of Partitioning Setting-Upa Partitioned SystemPartitioning S E C T I O NVISTA-40Installation and Setup Guide Mounting the Control Cabinet Installing the ControlInstalling the Cabinet Lock Grade A Mercantile Premises Listing GuidelinesInstalling the Control’s Circuit Board VISTA-40Installation and Setup GuideStep Action Wire Run Length/Gauge Table Installing the KeypadsSection 3 - Installing the Control Wire GaugeAlarm Output Supervision Installing External SoundersVISTA-40Installation and Setup Guide Wiring the Alarm OutputSupervising the Alarm Output Telephone Line ConnectionsSection 3 - Installing the Control Using a Siren DriverTERMINALS VISTA-40Installation and Setup GuideFigure 3-9 Wiring Connections for Zones ON CONTROLCompatible 2-WireSmoke Detectors Section 3 - Installing the ControlUsing 2-WireSmoke Detectors on Zone Using 4-WireSmoke Detectors on ZonesInstalling the 333PRM VISTA-40InstallationTOand Setup GuideUsing Smoke Power Reversal Module Smoke Detectors Compatible with the 333PRMFOUR-WIREDETECTOR CIRCUIT Section 3 - Installing the ControlFOUR-WIREDETECTOR CIRCUIT CONTROL PANELUsing 2-WireLatching Glassbreaks on Zone Installing RPM DevicesVISTA-40Installation and Setup Guide 3-10Step Action Section 3 - Installing the Control3-11 Figure 3-16 Polling Loop Connections to the3-12 VISTA-40Installation and Setup GuideUsing the 4297 Polling Loop Extender Polling Loop SupervisionRF System Installation Advisories Wireless Zone ExpansionSection 3 - Installing the Control Installation and Setup of the 5881 RF ReceiversStep Action VISTA-40Installation and Setup Guide3-14 StepThe 5800TM must not be installed within Section 3 - Installing the ControlInstalling the 5800TM Module 5800 Series Transmitter SetupTransmitter Battery Life Installing Relay DevicesVISTA-40Installation and Setup Guide Installing the 4204 Relay ModulesInstalling X10 Devices Installing the Ground Start ModuleSection 3 - Installing the Control The wire that reads + 50VDC is the RING sideKeyswitch Tamper Operation Installing a Remote KeyswitchVISTA-40Installation and Setup Guide Wiring for the Remote KeyswitchLong Range Radio Connected to the J7 Triggers Installing a 4100SMRemote Keypad Sounder Section 3 - Installing the ControlConnecting the 4100SM to a Serial Printer Installing the 4285/4286 VIP ModuleVISTA-40Installation and Setup Guide UL installationsStep Action Section 3 - Installing the Control3-21 Step ActionInstalling the Audio Alarm Verification Module VISTA-40Installation and Setup Guide3-22 3-23 Connecting the TransformerSection 3 - Installing the Control UVCM AND UVST SUMMARY OF CONNECTIONS3-24 VISTA-40Installation and Setup GuidePower Limiting Outputs OutputSection 3 - Installing the Control Determining the Control’s Power Supply LoadPanel Earth Ground Connections AC Power Outlet Ground Available fromTable 3 Alarm Output Current Load Determining the Size of the Standby BatteryVISTA-40Installation and Setup Guide AlarmRecommended Battery Section 3 - Installing the ControlTable 6 Battery Selection Table 3-27VISTA-40Installation and Setup Guide 3-28Entering and Exiting Programming Mode ProgrammingProgram Modes Data Field Programming ModeEntry Errors #93 Menu Mode ProgrammingVISTA-40Installation and Setup Guide 1Enter Program Mode Installer Code +MAIN MENU VISTA-40Installation and Setup Guide#93 Menu Mode Programming Commands OPTIONSZone Defaults Zone Number DesignationsVISTA-40Installation and Setup Guide Communication DefaultsType 05 Trouble by Day/Alarm by Night Zone Response Type DefinitionsCommunication Defaults for Zones Section 4 - ProgrammingType 06 24-HourSilent Alarm Zone Input Type DefinitionsVISTA-40Installation and Setup Guide Type 07 24-HourAudible AlarmSection 4 - Programming Programming for Access ControlProgramming for 4100SM StepVISTA-40Installation and Setup Guide Programming Data Fields Data Field DescriptionsAbout Data Field Programming Installer CodeKeyswitch Assignment VISTA-40Installation and Setup GuideAlarm Sounder Duration partition-specific Prevent Fire TimeoutPABX Access Code 24 25 26Power-Upin Previous State Section 5 - Data Field DescriptionsDownload Command Enables 38 39VISTA-40Installation and Setup Guide Enable Open/Close report for KeyswitchFIELD 45 46 47 48 49Section 5 - Data Field Descriptions TITLE and DATA ENTRIESAlarm Code for Zones 59 60 61 62VISTA-40Installation and Setup Guide Alarm Code for ZonesAlarm Code for Zones 74 75 76 77Supervisory and Restore Codes Alarm Code for ZonesNon-AlarmReport Codes Second Digit 82 83 84VISTA-40Installation and Setup Guide Restore Report Timing1*33 1*01 1*02 1*03 1*04 1*05 1*09 1*28 1*29 1*301*31 1*341*38 1*361*37 1*391*57 1*491*53 1*582*18 2*022*17 2*19Remote Downloading is not a UL Listed feature Downloading PrimerGeneral Information Access SecurityOn-LineControl Functions Getting On-Linewith a Control PanelVISTA-40Installation and Setup Guide Stage What HappensDirect-WireDownloading Telco HandoffSection 24 - Downloading Primer VISTA-40Installation and Setup Guide S E C T I O N Setting the Real-TimeClockSetting the Time and Date General InformationVISTA-40Installation and Setup Guide Level 0 Installer User 1 Code User Access CodesUser Codes & Levels of Authority S E C T I O NEXAMPLE OF MULTIPLE PARTITION ACCESS Multiple Partition AccessVISTA-40Installation and Setup Guide Level 6 Duress CodesAdding a Master, Manager, or Operator Code Section 9 - User Access CodesPROMPTEXPLANATION Deleting a Master, Manager, or Operator Code Changing a Master, Manager, or Operator CodeAdding an RF Key to an Existing User Exiting the User Edit ModeDialer Test Testing the SystemBattery Test Burglary Walk-TestCode + 5 TESTStep Action 1Enter Installer Code + Testing Wireless TransmittersVISTA-40Installation and Setup Guide Transmitter ID Sniffer ModeSection 10 - Testing The System To the InstallerTrouble Conditions Power FailureTechnical Support VISTA-40Installation and Setup GuideContacting Technical Support ATLIS-FAXFAXBACK Automated Fax Retrieval SystemRegulatory Agency Statements UL Installation RequirementsUL365 Police Station Connected Burglar Alarm A P P E N D I X AFor Grade A Service UL611/UL1610 Central Station Burglary AlarmVISTA-40Installation and Setup Guide For Grade AA ServiceIN THE EVENT OF TELEPHONE OPERATIONAL PROBLEMS Appendix A - Regulatory Agency StatementsFCC PART 68 NOTICE VISTA-40Installation and Setup Guide CANADIAN EMISSIONS STATEMENTSAVIS User Code Commands Programming Commands Summary of System CommandsA P P E N D I X B Event Logging CommandsVISTA-40Installation and Setup Guide Interface Wiring SpecificationsA P P E N D I X C Interface WiringVISTA-40Installation and Setup Guide TABLE OF CONTACT ID EVENT CODES Contact ID Event CodesA P P E N D I X D CodeVISTA-40Installation and Setup Guide Index Index-1VISTA-40Installation and Setup Guide Index-2Index Index-3VISTA-40Installation and Setup Guide Index-4THE LIMITATIONS OF THIS ALARM SYSTEM LIMITED WARRANTY Page Page Page Page Page Page Page 165 Eileen Way, Syosset, New York ¬19+lN7001V5 5/04 Rev A