Honeywell ZyAIR G-3000, 3.5 Installing Relay Devices, VISTA-40Installation and Setup Guide, 3-16

Page 26
Transmitter Battery Life

VISTA-40 Installation and Setup Guide

Transmitter Battery Life

Batteries in the wireless transmitters may last from 4 to 7 years, depending on the environment, usage, and the specific wireless device being used. Factors such as humidity, high or low temperatures, as well as large swings in temperature may all reduce the actual battery life in a given installation.

The wireless system can identify a true low battery situation, thus allowing the dealer or user of the system time to arrange a change of battery and maintain protection for that point within the system.

Some transmitters (e.g., 5802, 5802CP, and 5803) contain long-life but nonreplaceable batteries. At the end of their life, the complete unit must be replaced (and a new serial number enrolled at the control).

Button-type transmitters (e.g., 5801, 5802, 5802CP and 5803) should be periodically tested, as these transmitters do not send supervisory check-in signals.

To test the transmitters using the Transmitter ID Sniffer mode and the Go/NoGo Test Mode, see SECTION 10: Testing the System for the procedures.

Compatible 5800 Series Transmitters

Model

5801

5802

5802CP

5802MN

5802MN2

5804

5804BD

5804BDV

Product

Panic Transmitter

Pendant (Personal Emergency Transmitter)

Belt Clip (Personal Emergency Transmitter)

Miniature (Personal Emergency Transmitter)

Miniature (Personal Emergency Transmitter)

Wireless Key Transmitter

Wireless Key Bi-directional Transmitter

Wireless Key Bi-directional Transmitter with Voice

Input Type

UR or RF

BR Only

UR or RF

UR or RF

BR Only

BR Only

BR Only

Model

5806/5807/

5808

5816

5816MN

5816TEMP

5817

5818

5827

5827BD

5849

5850

5890

5890PI

Product

Wireless Photoelectric Smoke Detectors

Door/Window Transmitter

Miniature Door/Window Transmitter

Temperature Sensor Transmitter

Multi-Point Universal Transmitter

Recessed Transmitter

Wireless Keypad

Wireless Bi-directional Keypad

Glassbreak Detector

Glassbreak Detector

PIR Detector

PIR Detector with Pet Immunity

Input Type

RF

RF

RF

RF

House ID

House ID

RF

RF

RF

RF

Installing Relay Devices

The VISTA-40 support up to 8 relays. Each device must be programmed as to how to act (ACTION), when to activate (START), and when to deactivate (STOP). The 4204 and/or X-10 devices may be used as relay devices.

Installing the 4204 Relay Modules

Each 4204 module provides 4 relays with Form C (normally open and normally closed) contacts.

The relay module will not operate until the device address you have set the DIP switches for is enabled in the control’s Device Programming in the #93 Menu Mode.

To install the relay modules, see Figures 3-21and 3-22 and perform the following steps:

Step Action

1Set the 4204 or 4204CF’s DIP switches for a device address 01-15.

Do not use an address being used by another device (keypads, RF receivers, etc.).

2Mount the 4204 and 4204CF Modules per the instructions provided with them.

3Connect the module’s wire harness to the control (6, 7, 8, and 9). Plug the connector (other end of harness) to the module.

If you are mounting remotely, homerun each module to the control. The table below shows the maximum wire run lengths. Refer to the instructions provided with the 4204CF for its maximum permissible wire lengths.

Wire Gauge

Maximum Length

#22

125 feet

#20

200 feet

#18

300 feet

#16

500 feet

 

 

3-16

Image 26
Contents QVWDOODWLRQDQG6HWXS*XLGH $0&29,67$3DUWLWLRQHG6HFXULW\6\VWHP N7001V5 5/04 Rev APage Table of Contents Index List of Figures Conventions Used in This Manual PRODUCT MODEL NUMBERSS E C T I O N FeaturesGeneral Description About the VISTA-40Event Log VISTA-40Installation and Setup GuideAdditional Features Theory of Partitioning Setting-Upa Partitioned SystemPartitioning S E C T I O NVISTA-40Installation and Setup Guide Mounting the Control Cabinet Installing the ControlInstalling the Cabinet Lock Grade A Mercantile Premises Listing GuidelinesStep Action Installing the Control’s Circuit BoardVISTA-40Installation and Setup Guide Wire Run Length/Gauge Table Installing the KeypadsSection 3 - Installing the Control Wire GaugeAlarm Output Supervision Installing External SoundersVISTA-40Installation and Setup Guide Wiring the Alarm OutputSupervising the Alarm Output Telephone Line ConnectionsSection 3 - Installing the Control Using a Siren DriverTERMINALS VISTA-40Installation and Setup GuideFigure 3-9 Wiring Connections for Zones ON CONTROLCompatible 2-WireSmoke Detectors Section 3 - Installing the ControlUsing 2-WireSmoke Detectors on Zone Using 4-WireSmoke Detectors on ZonesInstalling the 333PRM VISTA-40InstallationTOand Setup GuideUsing Smoke Power Reversal Module Smoke Detectors Compatible with the 333PRMFOUR-WIREDETECTOR CIRCUIT Section 3 - Installing the ControlFOUR-WIREDETECTOR CIRCUIT CONTROL PANELUsing 2-WireLatching Glassbreaks on Zone Installing RPM DevicesVISTA-40Installation and Setup Guide 3-10Step Action Section 3 - Installing the Control3-11 Figure 3-16 Polling Loop Connections to the3-12 VISTA-40Installation and Setup GuideUsing the 4297 Polling Loop Extender Polling Loop SupervisionRF System Installation Advisories Wireless Zone ExpansionSection 3 - Installing the Control Installation and Setup of the 5881 RF ReceiversStep Action VISTA-40Installation and Setup Guide3-14 StepThe 5800TM must not be installed within Section 3 - Installing the ControlInstalling the 5800TM Module 5800 Series Transmitter SetupTransmitter Battery Life Installing Relay DevicesVISTA-40Installation and Setup Guide Installing the 4204 Relay ModulesInstalling X10 Devices Installing the Ground Start ModuleSection 3 - Installing the Control The wire that reads + 50VDC is the RING sideKeyswitch Tamper Operation Installing a Remote KeyswitchVISTA-40Installation and Setup Guide Wiring for the Remote KeyswitchLong Range Radio Connected to the J7 Triggers Installing a 4100SMRemote Keypad Sounder Section 3 - Installing the ControlConnecting the 4100SM to a Serial Printer Installing the 4285/4286 VIP ModuleVISTA-40Installation and Setup Guide UL installationsStep Action Section 3 - Installing the Control3-21 Step Action3-22 Installing the Audio Alarm Verification ModuleVISTA-40Installation and Setup Guide 3-23 Connecting the TransformerSection 3 - Installing the Control UVCM AND UVST SUMMARY OF CONNECTIONS3-24 VISTA-40Installation and Setup GuidePower Limiting Outputs OutputSection 3 - Installing the Control Determining the Control’s Power Supply LoadPanel Earth Ground Connections AC Power Outlet Ground Available fromTable 3 Alarm Output Current Load Determining the Size of the Standby BatteryVISTA-40Installation and Setup Guide AlarmRecommended Battery Section 3 - Installing the ControlTable 6 Battery Selection Table 3-27VISTA-40Installation and Setup Guide 3-28Entering and Exiting Programming Mode ProgrammingProgram Modes Data Field Programming ModeEntry Errors #93 Menu Mode ProgrammingVISTA-40Installation and Setup Guide 1Enter Program Mode Installer Code +MAIN MENU VISTA-40Installation and Setup Guide#93 Menu Mode Programming Commands OPTIONSZone Defaults Zone Number DesignationsVISTA-40Installation and Setup Guide Communication DefaultsType 05 Trouble by Day/Alarm by Night Zone Response Type DefinitionsCommunication Defaults for Zones Section 4 - ProgrammingType 06 24-HourSilent Alarm Zone Input Type DefinitionsVISTA-40Installation and Setup Guide Type 07 24-HourAudible AlarmSection 4 - Programming Programming for Access ControlProgramming for 4100SM StepVISTA-40Installation and Setup Guide Programming Data Fields Data Field DescriptionsAbout Data Field Programming Installer CodeKeyswitch Assignment VISTA-40Installation and Setup GuideAlarm Sounder Duration partition-specific Prevent Fire TimeoutPABX Access Code 24 25 26Power-Upin Previous State Section 5 - Data Field DescriptionsDownload Command Enables 38 39VISTA-40Installation and Setup Guide Enable Open/Close report for KeyswitchFIELD 45 46 47 48 49Section 5 - Data Field Descriptions TITLE and DATA ENTRIESAlarm Code for Zones 59 60 61 62VISTA-40Installation and Setup Guide Alarm Code for ZonesAlarm Code for Zones 74 75 76 77Supervisory and Restore Codes Alarm Code for ZonesNon-AlarmReport Codes Second Digit 82 83 84VISTA-40Installation and Setup Guide Restore Report Timing1*33 1*01 1*02 1*03 1*04 1*05 1*09 1*28 1*29 1*301*31 1*341*38 1*361*37 1*391*57 1*491*53 1*582*18 2*022*17 2*19Remote Downloading is not a UL Listed feature Downloading PrimerGeneral Information Access SecurityOn-LineControl Functions Getting On-Linewith a Control PanelVISTA-40Installation and Setup Guide Stage What HappensSection 24 - Downloading Primer Direct-WireDownloadingTelco Handoff VISTA-40Installation and Setup Guide S E C T I O N Setting the Real-TimeClockSetting the Time and Date General InformationVISTA-40Installation and Setup Guide Level 0 Installer User 1 Code User Access CodesUser Codes & Levels of Authority S E C T I O NEXAMPLE OF MULTIPLE PARTITION ACCESS Multiple Partition AccessVISTA-40Installation and Setup Guide Level 6 Duress CodesPROMPTEXPLANATION Adding a Master, Manager, or Operator CodeSection 9 - User Access Codes Deleting a Master, Manager, or Operator Code Changing a Master, Manager, or Operator CodeAdding an RF Key to an Existing User Exiting the User Edit ModeDialer Test Testing the SystemBattery Test Burglary Walk-TestCode + 5 TESTStep Action 1Enter Installer Code + Testing Wireless TransmittersVISTA-40Installation and Setup Guide Transmitter ID Sniffer ModeSection 10 - Testing The System To the InstallerTrouble Conditions Power FailureTechnical Support VISTA-40Installation and Setup GuideContacting Technical Support ATLIS-FAXFAXBACK Automated Fax Retrieval SystemRegulatory Agency Statements UL Installation RequirementsUL365 Police Station Connected Burglar Alarm A P P E N D I X AFor Grade A Service UL611/UL1610 Central Station Burglary AlarmVISTA-40Installation and Setup Guide For Grade AA ServiceFCC PART 68 NOTICE IN THE EVENT OF TELEPHONE OPERATIONAL PROBLEMSAppendix A - Regulatory Agency Statements AVIS VISTA-40Installation and Setup GuideCANADIAN EMISSIONS STATEMENTS User Code Commands Programming Commands Summary of System CommandsA P P E N D I X B Event Logging CommandsVISTA-40Installation and Setup Guide Interface Wiring SpecificationsA P P E N D I X C Interface WiringVISTA-40Installation and Setup Guide TABLE OF CONTACT ID EVENT CODES Contact ID Event CodesA P P E N D I X D CodeVISTA-40Installation and Setup Guide Index Index-1VISTA-40Installation and Setup Guide Index-2Index Index-3VISTA-40Installation and Setup Guide Index-4THE LIMITATIONS OF THIS ALARM SYSTEM LIMITED WARRANTY Page Page Page Page Page Page Page N7001V5 5/04 Rev A 165 Eileen Way, Syosset, New York¬19+l