Honeywell ZyAIR G-3000 Testing Wireless Transmitters, VISTA-40Installation and Setup Guide, Step

Page 70
Testing Wireless Transmitters

VISTA-40 Installation and Setup Guide

Step

6

7

8

Action

Check the keypad-initiated alarms, if programmed, by pressing the panic key pairs (and #, 1 and , and/or 3 and #).

The word ALARM and a descriptor “99” are displayed for and #. If [1] and [] are pressed, “95” is displayed; if [3] and [#] are pressed, “96” is displayed.

If the system has been programmed for audible emergency, the keypad emits a loud, steady alarm sound. Silence the alarm by entering the security code and pressing OFF. If the system has been programmed for silent panic, there are no audible alarms or displays. A report is sent to the central station, however.

Notify the central station that all tests are finished, and verify results with them.

Testing Wireless Transmitters

Transmitter ID Sniffer Mode

Use the Transmitter Sniffer Mode to test that transmitters have all been properly programmed.

If a transmitter does not have its serial number “enrolled,” it will not turn off its zone number.

To enter the Transmitter ID Sniffer Mode, proceed as follows:

Step Action

1Enter Installer Code + [#] + [3]. The keypad displays all zone numbers of wireless units programmed into the system.

2Fault each wireless zone, causing each device to transmit.

As the system receives a signal from each of the transmitters, the zone number of that transmitter disappears from the display.

3Enter Installer Code + OFF to exit the Sniffer Mode.

Go/No Go Test Mode

Checking the transmitters in this mode assists in determining good mounting locations, and verifies that the RF transmission has sufficient signal amplitude margin for the installed system.

All partitions containing wireless transmitters must be placed in the test mode for sensitivity reduction of the RF receiver (50% sensitivity). Otherwise, the RF receiver remains at full strength.

Make sure that all partitions are disarmed when performing this test, as the wireless receiver gain is reduced in half.

To enter the Go/No Go Test Mode, proceed as follows:

Step Action

1Enter Installer Code + [5].

2Fault each wireless transmitter, causing each device to transmit.

NOTE: If a single receiver is used, the keypad beeps three times to indicate signal reception. If two receivers are used, the keypad beeps once if the first receiver received the signal, twice if the second receiver received the signal, and three times if both receivers heard the signal.

3If the keypad does not beep, reorient or move the transmitter to another location. Usually a few inches in either direction is all that is required.

4Enter Installer Code + OFF to exit the Go/No Go Test Mode.

9-2

Image 70
Contents QVWDOODWLRQDQG6HWXS*XLGH $0&29,67$3DUWLWLRQHG6HFXULW\6\VWHP N7001V5 5/04 Rev APage Table of Contents Index List of Figures Conventions Used in This Manual PRODUCT MODEL NUMBERSS E C T I O N FeaturesGeneral Description About the VISTA-40Additional Features VISTA-40Installation and Setup GuideEvent Log Theory of Partitioning Setting-Upa Partitioned SystemPartitioning S E C T I O NVISTA-40Installation and Setup Guide Mounting the Control Cabinet Installing the ControlInstalling the Cabinet Lock Grade A Mercantile Premises Listing GuidelinesVISTA-40Installation and Setup Guide Installing the Control’s Circuit BoardStep Action Wire Run Length/Gauge Table Installing the KeypadsSection 3 - Installing the Control Wire GaugeAlarm Output Supervision Installing External SoundersVISTA-40Installation and Setup Guide Wiring the Alarm OutputSupervising the Alarm Output Telephone Line ConnectionsSection 3 - Installing the Control Using a Siren DriverTERMINALS VISTA-40Installation and Setup GuideFigure 3-9 Wiring Connections for Zones ON CONTROLCompatible 2-WireSmoke Detectors Section 3 - Installing the ControlUsing 2-WireSmoke Detectors on Zone Using 4-WireSmoke Detectors on ZonesInstalling the 333PRM VISTA-40InstallationTOand Setup GuideUsing Smoke Power Reversal Module Smoke Detectors Compatible with the 333PRMFOUR-WIREDETECTOR CIRCUIT Section 3 - Installing the ControlFOUR-WIREDETECTOR CIRCUIT CONTROL PANELUsing 2-WireLatching Glassbreaks on Zone Installing RPM DevicesVISTA-40Installation and Setup Guide 3-10Step Action Section 3 - Installing the Control3-11 Figure 3-16 Polling Loop Connections to the3-12 VISTA-40Installation and Setup GuideUsing the 4297 Polling Loop Extender Polling Loop SupervisionRF System Installation Advisories Wireless Zone ExpansionSection 3 - Installing the Control Installation and Setup of the 5881 RF ReceiversStep Action VISTA-40Installation and Setup Guide3-14 StepThe 5800TM must not be installed within Section 3 - Installing the ControlInstalling the 5800TM Module 5800 Series Transmitter SetupTransmitter Battery Life Installing Relay DevicesVISTA-40Installation and Setup Guide Installing the 4204 Relay ModulesInstalling X10 Devices Installing the Ground Start ModuleSection 3 - Installing the Control The wire that reads + 50VDC is the RING sideKeyswitch Tamper Operation Installing a Remote KeyswitchVISTA-40Installation and Setup Guide Wiring for the Remote KeyswitchLong Range Radio Connected to the J7 Triggers Installing a 4100SMRemote Keypad Sounder Section 3 - Installing the ControlConnecting the 4100SM to a Serial Printer Installing the 4285/4286 VIP ModuleVISTA-40Installation and Setup Guide UL installationsStep Action Section 3 - Installing the Control3-21 Step ActionVISTA-40Installation and Setup Guide Installing the Audio Alarm Verification Module3-22 3-23 Connecting the TransformerSection 3 - Installing the Control UVCM AND UVST SUMMARY OF CONNECTIONS3-24 VISTA-40Installation and Setup GuidePower Limiting Outputs OutputSection 3 - Installing the Control Determining the Control’s Power Supply LoadPanel Earth Ground Connections AC Power Outlet Ground Available fromTable 3 Alarm Output Current Load Determining the Size of the Standby BatteryVISTA-40Installation and Setup Guide AlarmRecommended Battery Section 3 - Installing the ControlTable 6 Battery Selection Table 3-27VISTA-40Installation and Setup Guide 3-28Entering and Exiting Programming Mode ProgrammingProgram Modes Data Field Programming ModeEntry Errors #93 Menu Mode ProgrammingVISTA-40Installation and Setup Guide 1Enter Program Mode Installer Code +MAIN MENU VISTA-40Installation and Setup Guide#93 Menu Mode Programming Commands OPTIONSZone Defaults Zone Number DesignationsVISTA-40Installation and Setup Guide Communication DefaultsType 05 Trouble by Day/Alarm by Night Zone Response Type DefinitionsCommunication Defaults for Zones Section 4 - ProgrammingType 06 24-HourSilent Alarm Zone Input Type DefinitionsVISTA-40Installation and Setup Guide Type 07 24-HourAudible AlarmSection 4 - Programming Programming for Access ControlProgramming for 4100SM StepVISTA-40Installation and Setup Guide Programming Data Fields Data Field DescriptionsAbout Data Field Programming Installer CodeKeyswitch Assignment VISTA-40Installation and Setup GuideAlarm Sounder Duration partition-specific Prevent Fire TimeoutPABX Access Code 24 25 26Power-Upin Previous State Section 5 - Data Field DescriptionsDownload Command Enables 38 39VISTA-40Installation and Setup Guide Enable Open/Close report for KeyswitchFIELD 45 46 47 48 49Section 5 - Data Field Descriptions TITLE and DATA ENTRIESAlarm Code for Zones 59 60 61 62VISTA-40Installation and Setup Guide Alarm Code for ZonesAlarm Code for Zones 74 75 76 77Supervisory and Restore Codes Alarm Code for ZonesNon-AlarmReport Codes Second Digit 82 83 84VISTA-40Installation and Setup Guide Restore Report Timing1*33 1*01 1*02 1*03 1*04 1*05 1*09 1*28 1*29 1*301*31 1*341*38 1*361*37 1*391*57 1*491*53 1*582*18 2*022*17 2*19Remote Downloading is not a UL Listed feature Downloading PrimerGeneral Information Access SecurityOn-LineControl Functions Getting On-Linewith a Control PanelVISTA-40Installation and Setup Guide Stage What HappensTelco Handoff Direct-WireDownloadingSection 24 - Downloading Primer VISTA-40Installation and Setup Guide S E C T I O N Setting the Real-TimeClockSetting the Time and Date General InformationVISTA-40Installation and Setup Guide Level 0 Installer User 1 Code User Access CodesUser Codes & Levels of Authority S E C T I O NEXAMPLE OF MULTIPLE PARTITION ACCESS Multiple Partition AccessVISTA-40Installation and Setup Guide Level 6 Duress CodesSection 9 - User Access Codes Adding a Master, Manager, or Operator CodePROMPTEXPLANATION Deleting a Master, Manager, or Operator Code Changing a Master, Manager, or Operator CodeAdding an RF Key to an Existing User Exiting the User Edit ModeDialer Test Testing the SystemBattery Test Burglary Walk-TestCode + 5 TESTStep Action 1Enter Installer Code + Testing Wireless TransmittersVISTA-40Installation and Setup Guide Transmitter ID Sniffer ModeSection 10 - Testing The System To the InstallerTrouble Conditions Power FailureTechnical Support VISTA-40Installation and Setup GuideContacting Technical Support ATLIS-FAXFAXBACK Automated Fax Retrieval SystemRegulatory Agency Statements UL Installation RequirementsUL365 Police Station Connected Burglar Alarm A P P E N D I X AFor Grade A Service UL611/UL1610 Central Station Burglary AlarmVISTA-40Installation and Setup Guide For Grade AA ServiceAppendix A - Regulatory Agency Statements IN THE EVENT OF TELEPHONE OPERATIONAL PROBLEMSFCC PART 68 NOTICE CANADIAN EMISSIONS STATEMENTS VISTA-40Installation and Setup GuideAVIS User Code Commands Programming Commands Summary of System CommandsA P P E N D I X B Event Logging CommandsVISTA-40Installation and Setup Guide Interface Wiring SpecificationsA P P E N D I X C Interface WiringVISTA-40Installation and Setup Guide TABLE OF CONTACT ID EVENT CODES Contact ID Event CodesA P P E N D I X D CodeVISTA-40Installation and Setup Guide Index Index-1VISTA-40Installation and Setup Guide Index-2Index Index-3VISTA-40Installation and Setup Guide Index-4THE LIMITATIONS OF THIS ALARM SYSTEM LIMITED WARRANTY Page Page Page Page Page Page Page ¬19+l 165 Eileen Way, Syosset, New YorkN7001V5 5/04 Rev A