Honeywell 3.5 manual 1*49, 1*53, 1*57, 1*58, 1*60, 1*70, 1*71, 1*74, 1*75, 1*76, 2*00, 2*01

Page 57
1*49

 

 

 

 

 

 

Section 5 – Data Field Descriptions

 

 

 

 

 

 

 

 

 

 

FIELD

 

TITLE and DATA ENTRIES

 

EXPLANATION

 

 

 

 

 

 

 

 

 

 

 

 

 

Suppress Transmitter

 

If enabled, no trouble soundings occur on the keypad for transmitter

 

 

1*49

 

 

 

 

Supervision Sound

 

check-in failures.

 

 

 

 

 

0 = disable

1 = enable

1*52

Send Cancel If Alarm + Off

(partition-specific)

 

Must be 0 for UL.

If enabled, Cancel reports are sent when the system is disarmed after an alarm, regardless of how much time has gone by.

0 = disable

1 = enable

 

1*53

 

Disable Download Callback

 

0

= callback required

 

 

 

 

1

= no callback required

 

 

 

 

 

 

 

Enable 5800 RF Button Global

 

1*57

 

 

 

Arm

 

 

 

 

 

0

= disable

 

 

1

= enable

 

 

 

 

 

 

 

Enable 5800 RF Button Force

 

1*58

 

 

 

Arm

 

 

 

 

 

0

= disable

 

 

1

= enable

If disabled, Cancel reports are sent within Bell Timeout period only.

NOTE: This option must be enabled so Cancel reports are always sent.

Select whether a callback from the control panel is required for downloading.

Must be 0 for UL installations.

If enabled, the system arms/disarms in accordance with the button’s user’s global arming settings.

If enabled, allows the RF button user to force a bypass of all faulted zones when arming the system.

NOTE: When attempting to arm the system, the keypad beeps once after the button is pressed if any faulted zones are present. The user should then press the button again within 4 seconds to force-bypass those zones and arm the system.

 

1*60

 

Zone 5 Audio Alarm Verification

 

0

= disable

 

 

 

 

1

= enable

 

 

 

 

 

 

 

Event Log Types

 

1*70

 

 

0

= disable

 

 

 

 

1

= enable

 

 

 

 

 

 

 

12/24 Hour Type Stamp Format

 

1*71

 

 

0

= 12-hour

 

 

 

 

1

= 24-hour

 

 

 

 

 

 

 

Relay Timeout XXX Minutes

 

1*74

 

 

 

Enter 000-127times 2 minutes (000-254).

 

 

 

 

 

 

 

 

 

 

Relay Timeout YYY Seconds

 

1*75

 

 

 

Enter 000-127seconds.

 

 

 

 

 

 

 

 

 

 

Access Control Relay (partition-

 

1*76

 

 

 

specific)

 

 

 

 

 

 

01-08= relay number

 

 

 

00 = relay not used.

 

 

 

 

 

 

 

Number of Partitions

 

2*00

 

 

 

Enter 1-2.

 

 

 

 

 

 

 

 

 

 

Daylight Saving Time Start/End

 

2*01

 

 

 

Month

 

 

 

 

 

0

= disable

 

 

1

= enable

 

 

 

 

 

If enabled, zone 5 is used for 2-way audio (AAV).

Must be 0 for UL installations.

NOTE: Zone 5 cannot be used as protection zone.

This field has five entries as follows: Alarm, Check, Bypass, Open/Close, and System. If enabled, the system logs those events into the event log.

Select the type of time stamping for the event log.

This is used for Relay Programming in the #93 Menu Mode Programming relay command “56.”

This is used for Relay Programming in the #93 Menu Mode Programming command “57.”

If enabled, the assigned relay closes for 2 seconds when the user enters his code and presses 0.

Must be 00 for UL installations.

Enter the number of partitions used in the system.

Enter the months (00-12)in which daylight saving time starts and ends.

Enter 00, 00 if daylight saving time does not apply to the user’s region. Standard setting for U.S. is 04,10.

5-11

Image 57
Contents 3DUWLWLRQHG6HFXULW\6\VWHP $0&29,67$QVWDOODWLRQDQG6HWXS*XLGH N7001V5 5/04 Rev APage Table of Contents Index List of Figures PRODUCT MODEL NUMBERS Conventions Used in This ManualGeneral Description FeaturesS E C T I O N About the VISTA-40VISTA-40Installation and Setup Guide Additional FeaturesEvent Log Partitioning Setting-Upa Partitioned SystemTheory of Partitioning S E C T I O NVISTA-40Installation and Setup Guide Installing the Cabinet Lock Installing the ControlMounting the Control Cabinet Grade A Mercantile Premises Listing GuidelinesInstalling the Control’s Circuit Board VISTA-40Installation and Setup GuideStep Action Section 3 - Installing the Control Installing the KeypadsWire Run Length/Gauge Table Wire GaugeVISTA-40Installation and Setup Guide Installing External SoundersAlarm Output Supervision Wiring the Alarm OutputSection 3 - Installing the Control Telephone Line ConnectionsSupervising the Alarm Output Using a Siren DriverFigure 3-9 Wiring Connections for Zones VISTA-40Installation and Setup GuideTERMINALS ON CONTROLUsing 2-WireSmoke Detectors on Zone Section 3 - Installing the ControlCompatible 2-WireSmoke Detectors Using 4-WireSmoke Detectors on ZonesUsing Smoke Power Reversal Module VISTA-40InstallationTOand Setup GuideInstalling the 333PRM Smoke Detectors Compatible with the 333PRMFOUR-WIREDETECTOR CIRCUIT Section 3 - Installing the ControlFOUR-WIREDETECTOR CIRCUIT CONTROL PANELVISTA-40Installation and Setup Guide Installing RPM DevicesUsing 2-WireLatching Glassbreaks on Zone 3-103-11 Section 3 - Installing the ControlStep Action Figure 3-16 Polling Loop Connections to theUsing the 4297 Polling Loop Extender VISTA-40Installation and Setup Guide3-12 Polling Loop SupervisionSection 3 - Installing the Control Wireless Zone ExpansionRF System Installation Advisories Installation and Setup of the 5881 RF Receivers3-14 VISTA-40Installation and Setup GuideStep Action StepInstalling the 5800TM Module Section 3 - Installing the ControlThe 5800TM must not be installed within 5800 Series Transmitter SetupVISTA-40Installation and Setup Guide Installing Relay DevicesTransmitter Battery Life Installing the 4204 Relay ModulesSection 3 - Installing the Control Installing the Ground Start ModuleInstalling X10 Devices The wire that reads + 50VDC is the RING sideVISTA-40Installation and Setup Guide Installing a Remote KeyswitchKeyswitch Tamper Operation Wiring for the Remote KeyswitchRemote Keypad Sounder Installing a 4100SMLong Range Radio Connected to the J7 Triggers Section 3 - Installing the ControlVISTA-40Installation and Setup Guide Installing the 4285/4286 VIP ModuleConnecting the 4100SM to a Serial Printer UL installations3-21 Section 3 - Installing the ControlStep Action Step ActionInstalling the Audio Alarm Verification Module VISTA-40Installation and Setup Guide3-22 Section 3 - Installing the Control Connecting the Transformer3-23 UVCM AND UVST SUMMARY OF CONNECTIONSPower Limiting Outputs VISTA-40Installation and Setup Guide3-24 OutputPanel Earth Ground Connections Determining the Control’s Power Supply LoadSection 3 - Installing the Control AC Power Outlet Ground Available fromVISTA-40Installation and Setup Guide Determining the Size of the Standby BatteryTable 3 Alarm Output Current Load AlarmTable 6 Battery Selection Table Section 3 - Installing the ControlRecommended Battery 3-273-28 VISTA-40Installation and Setup GuideProgram Modes ProgrammingEntering and Exiting Programming Mode Data Field Programming ModeVISTA-40Installation and Setup Guide #93 Menu Mode ProgrammingEntry Errors 1Enter Program Mode Installer Code +#93 Menu Mode Programming Commands VISTA-40Installation and Setup GuideMAIN MENU OPTIONSVISTA-40Installation and Setup Guide Zone Number DesignationsZone Defaults Communication DefaultsCommunication Defaults for Zones Zone Response Type DefinitionsType 05 Trouble by Day/Alarm by Night Section 4 - ProgrammingVISTA-40Installation and Setup Guide Zone Input Type DefinitionsType 06 24-HourSilent Alarm Type 07 24-HourAudible AlarmProgramming for 4100SM Programming for Access ControlSection 4 - Programming StepVISTA-40Installation and Setup Guide About Data Field Programming Data Field DescriptionsProgramming Data Fields Installer CodeAlarm Sounder Duration partition-specific VISTA-40Installation and Setup GuideKeyswitch Assignment Prevent Fire TimeoutPower-Upin Previous State 24 25 26PABX Access Code Section 5 - Data Field DescriptionsVISTA-40Installation and Setup Guide 38 39Download Command Enables Enable Open/Close report for KeyswitchSection 5 - Data Field Descriptions 45 46 47 48 49FIELD TITLE and DATA ENTRIESVISTA-40Installation and Setup Guide 59 60 61 62Alarm Code for Zones Alarm Code for ZonesSupervisory and Restore Codes 74 75 76 77Alarm Code for Zones Alarm Code for ZonesVISTA-40Installation and Setup Guide 82 83 84Non-AlarmReport Codes Second Digit Restore Report Timing1*31 1*01 1*02 1*03 1*04 1*05 1*09 1*28 1*29 1*301*33 1*341*37 1*361*38 1*391*53 1*491*57 1*582*17 2*022*18 2*19General Information Downloading PrimerRemote Downloading is not a UL Listed feature Access SecurityVISTA-40Installation and Setup Guide Getting On-Linewith a Control PanelOn-LineControl Functions Stage What HappensDirect-WireDownloading Telco HandoffSection 24 - Downloading Primer VISTA-40Installation and Setup Guide Setting the Time and Date Setting the Real-TimeClockS E C T I O N General InformationVISTA-40Installation and Setup Guide User Codes & Levels of Authority User Access CodesLevel 0 Installer User 1 Code S E C T I O NVISTA-40Installation and Setup Guide Multiple Partition AccessEXAMPLE OF MULTIPLE PARTITION ACCESS Level 6 Duress CodesAdding a Master, Manager, or Operator Code Section 9 - User Access CodesPROMPTEXPLANATION Adding an RF Key to an Existing User Changing a Master, Manager, or Operator CodeDeleting a Master, Manager, or Operator Code Exiting the User Edit ModeBattery Test Testing the SystemDialer Test Burglary Walk-TestCode + 5 TESTVISTA-40Installation and Setup Guide Testing Wireless TransmittersStep Action 1Enter Installer Code + Transmitter ID Sniffer ModeTrouble Conditions To the InstallerSection 10 - Testing The System Power FailureContacting Technical Support VISTA-40Installation and Setup GuideTechnical Support ATLIS-FAXFAXBACK Automated Fax Retrieval SystemUL365 Police Station Connected Burglar Alarm UL Installation RequirementsRegulatory Agency Statements A P P E N D I X AVISTA-40Installation and Setup Guide UL611/UL1610 Central Station Burglary AlarmFor Grade A Service For Grade AA ServiceIN THE EVENT OF TELEPHONE OPERATIONAL PROBLEMS Appendix A - Regulatory Agency StatementsFCC PART 68 NOTICE VISTA-40Installation and Setup Guide CANADIAN EMISSIONS STATEMENTSAVIS A P P E N D I X B Summary of System CommandsUser Code Commands Programming Commands Event Logging CommandsVISTA-40Installation and Setup Guide A P P E N D I X C SpecificationsInterface Wiring Interface WiringVISTA-40Installation and Setup Guide A P P E N D I X D Contact ID Event CodesTABLE OF CONTACT ID EVENT CODES CodeVISTA-40Installation and Setup Guide Index-1 IndexIndex-2 VISTA-40Installation and Setup GuideIndex-3 IndexIndex-4 VISTA-40Installation and Setup GuideTHE LIMITATIONS OF THIS ALARM SYSTEM LIMITED WARRANTY Page Page Page Page Page Page Page 165 Eileen Way, Syosset, New York ¬19+lN7001V5 5/04 Rev A