UL611/UL1610 Central Station Burglary Alarm
Follow the instructions for UL609 Local installations given above.
For Grade A Service:
•You must use the
•Connect the control’s burglary/audible panic alarm trigger (on J7 header) and the 659EN’s phone line monitor output to the 7720. The 7720 will send a report to the central station when a telephone line fault condition is detected.
•Also connect the 7720’s radio fault output to one of the
•Program the control’s dialer to send Burglary Alarm, Trouble, Opening/Closing, and Low Battery reports.
For Grade AA Service:
Follow the instructions for Grade A service, except use the 7920SE in place of the 7720.
California State Fire Marshal (CSFM) and UL Residential Fire Battery Backup Requirements
The California State Fire Marshal and UL have regulations that require all residential fire alarm control panels to have backup battery with sufficient capacity to operate the panel and its attached peripheral devices for 24 hours in the intended standby condition, followed by at least 4 minutes in the intended fire alarm signaling condition.
The
•Output current is limited to 750mA maximum total auxiliary power, polling loop, and bell output current.
•Maximum auxiliary current is 300mA (including polling loop current).
•A 14AH battery is used. (Yuasa model