Honeywell 3.5 Installing the Control, 3-21, Step Action, If you mount the VIP Module inside the

Page 31
If you mount the VIP Module inside the

Section 3 - Installing the Control

To install the VIP module, perform the following steps:

Step Action

1

Mount the module in the control cabinet if

 

space is available or, if this is not possible, on

 

the side of the cabinet or adjacent to it.

Step Action

4Connect the module to the phone line as shown below. See Figure 3-27.

If you mount the VIP Module inside the

control cabinet, attach it to the cabinet’s

interior surface with 2-faced adhesive tape.

You may leave the module’s cover off if it is

mounted within the cabinet.

If you mount the module outside the

cabinet, use the screw holes at the rear to

mount horizontally or vertically (2-faced

adhesive tape may be used, if preferred).

If you mount the module outside thecontrol cabinet’s door.￿

4285/4286 Terminal

1.Phone In (Tip)

2.Phone In (Ring)

3.Phone Out (Tip)

4.Phone Out (Ring)

5.No Connection

6.Audio Out 1

7.Audio Out 1

Connects to direct connect cord:

green wire

red wire

brown wire

gray wire

Speaker

Speaker

2

Affix the 4285/4286 connections label

 

(supplied separately) to the inside of the VIP

 

Module’s cover, if the cover is used.

 

Otherwise, affix the label to the inside of the

 

control cabinet’s door.

3

Make 12V (+) and (–) and data-in and data-

 

out connections from the VIP Module to the

 

control, using the connector cable supplied

 

with the VIP Module. These are the same

 

connections as for remote keypads.

Supported by the 4286 only

Use an RJ31X Jack with the phone cable supplied with the control to make connections to the VIP module. Make connections exactly as shown in Figure 3-27. This is essential, even if the system is not connected to a central station. The 4285/4286 will not function if this is not done.

If touch-tones are not present following phone access to the security system via an on- premises phone, try reversing the pair of wires connected to terminals 3 and 4 on the 4285/4286.

If the phone plug is disconnected from the control, the premise’s phones will not operate.

SPEAKER NOTE: IF CONNECTING SINGLE SPEAKER, USE 8-ohm SPEAKER ONLY.

 

 

 

 

 

IF CONNECTING 2 SPEAKERS, USE 4-ohm or 8-ohm SPEAKERS

 

 

 

 

 

AND CONNECT IN SERIES.

 

 

 

INCOMING TELCO LINE

 

 

 

 

 

 

 

4286 VIP MODULE

67

SEE SPEAKER NOTE

TIP

RING

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTE:

 

 

4 5

GREY

 

RJ31X

TIP

 

4286 DEVICE

SPEAKER

3

BROWN

 

RING

PREMISES

ADDRESS IS

VOLUME

2

 

 

JACK

FACTORY SET

CONTROL

1

GREEN

RED

 

 

 

ANSWERING

TO “4”

 

 

CALLER ID

 

MACHINE AND

 

 

NO

 

 

 

 

PHONES

 

 

 

 

 

UNIT

 

 

 

 

 

CONNECTION

KEYED

 

 

 

 

ANSWERING

 

 

 

HEADER

 

EARTH

 

 

 

MACHINE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GROUND

 

 

 

 

YELLOW

GREEN

 

TO CONTROL PANEL

TIP RING TIP RING

 

 

 

 

 

KEYPAD CONNECTIONS HANDSET INCOMING

 

 

 

 

4500

 

 

 

TELCO LINE

 

 

 

 

 

 

YELLOW

 

 

 

 

 

 

THERMOSTAT

 

 

 

 

 

 

 

 

NO CONNECTION

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RED

 

 

 

 

 

 

 

 

 

BLACK

 

 

 

 

 

 

 

 

 

GREEN

 

 

 

 

 

 

IMPORTANT NOTE FOR EXISTING INSTALLATIONS: EXISTING WIRES CONNECTED TO THE “HANDSET” TERMINALS ON CONTROL MUST BE MOVED FROM THERE TO TERMINALS 3 AND 4 ON THE 4286.

THIS DEVICE COMPLIES WITH FCC RULES, PART 68 FCC REGISTRATION No. AC3USA-74659-KX-N RINGER EQUIVALENCE: 1.0B

U.S. PATENT No. 4791658

FOR COMPLETE INFORMATION, SEE INSTALLATION

INSTRUCTIONS N6431-3 ACCOMPANYING 4286 VIP MODULE

4286_wiring-002-V1

Figure 3-27: VIP Module Connections

3-21

Image 31
Contents N7001V5 5/04 Rev A $0&29,67$3DUWLWLRQHG6HFXULW\6\VWHP QVWDOODWLRQDQG6HWXS*XLGHPage Table of Contents Index List of Figures PRODUCT MODEL NUMBERS Conventions Used in This ManualAbout the VISTA-40 FeaturesGeneral Description S E C T I O NAdditional Features VISTA-40Installation and Setup GuideEvent Log S E C T I O N Setting-Upa Partitioned SystemPartitioning Theory of PartitioningVISTA-40Installation and Setup Guide Grade A Mercantile Premises Listing Guidelines Installing the ControlInstalling the Cabinet Lock Mounting the Control CabinetVISTA-40Installation and Setup Guide Installing the Control’s Circuit BoardStep Action Wire Gauge Installing the KeypadsSection 3 - Installing the Control Wire Run Length/Gauge TableWiring the Alarm Output Installing External SoundersVISTA-40Installation and Setup Guide Alarm Output SupervisionUsing a Siren Driver Telephone Line ConnectionsSection 3 - Installing the Control Supervising the Alarm OutputON CONTROL VISTA-40Installation and Setup GuideFigure 3-9 Wiring Connections for Zones TERMINALSUsing 4-WireSmoke Detectors on Zones Section 3 - Installing the ControlUsing 2-WireSmoke Detectors on Zone Compatible 2-WireSmoke DetectorsSmoke Detectors Compatible with the 333PRM VISTA-40InstallationTOand Setup GuideUsing Smoke Power Reversal Module Installing the 333PRMCONTROL PANEL Section 3 - Installing the ControlFOUR-WIREDETECTOR CIRCUIT FOUR-WIREDETECTOR CIRCUIT3-10 Installing RPM DevicesVISTA-40Installation and Setup Guide Using 2-WireLatching Glassbreaks on ZoneFigure 3-16 Polling Loop Connections to the Section 3 - Installing the Control3-11 Step ActionPolling Loop Supervision VISTA-40Installation and Setup GuideUsing the 4297 Polling Loop Extender 3-12Installation and Setup of the 5881 RF Receivers Wireless Zone ExpansionSection 3 - Installing the Control RF System Installation AdvisoriesStep VISTA-40Installation and Setup Guide3-14 Step Action5800 Series Transmitter Setup Section 3 - Installing the ControlInstalling the 5800TM Module The 5800TM must not be installed withinInstalling the 4204 Relay Modules Installing Relay DevicesVISTA-40Installation and Setup Guide Transmitter Battery LifeThe wire that reads + 50VDC is the RING side Installing the Ground Start ModuleSection 3 - Installing the Control Installing X10 DevicesWiring for the Remote Keyswitch Installing a Remote KeyswitchVISTA-40Installation and Setup Guide Keyswitch Tamper OperationSection 3 - Installing the Control Installing a 4100SMRemote Keypad Sounder Long Range Radio Connected to the J7 TriggersUL installations Installing the 4285/4286 VIP ModuleVISTA-40Installation and Setup Guide Connecting the 4100SM to a Serial PrinterStep Action Section 3 - Installing the Control3-21 Step ActionVISTA-40Installation and Setup Guide Installing the Audio Alarm Verification Module3-22 UVCM AND UVST SUMMARY OF CONNECTIONS Connecting the TransformerSection 3 - Installing the Control 3-23Output VISTA-40Installation and Setup GuidePower Limiting Outputs 3-24AC Power Outlet Ground Available from Determining the Control’s Power Supply LoadPanel Earth Ground Connections Section 3 - Installing the ControlAlarm Determining the Size of the Standby BatteryVISTA-40Installation and Setup Guide Table 3 Alarm Output Current Load3-27 Section 3 - Installing the ControlTable 6 Battery Selection Table Recommended Battery3-28 VISTA-40Installation and Setup GuideData Field Programming Mode ProgrammingProgram Modes Entering and Exiting Programming Mode1Enter Program Mode Installer Code + #93 Menu Mode ProgrammingVISTA-40Installation and Setup Guide Entry ErrorsOPTIONS VISTA-40Installation and Setup Guide#93 Menu Mode Programming Commands MAIN MENUCommunication Defaults Zone Number DesignationsVISTA-40Installation and Setup Guide Zone DefaultsSection 4 - Programming Zone Response Type DefinitionsCommunication Defaults for Zones Type 05 Trouble by Day/Alarm by NightType 07 24-HourAudible Alarm Zone Input Type DefinitionsVISTA-40Installation and Setup Guide Type 06 24-HourSilent AlarmStep Programming for Access ControlProgramming for 4100SM Section 4 - ProgrammingVISTA-40Installation and Setup Guide Installer Code Data Field DescriptionsAbout Data Field Programming Programming Data FieldsPrevent Fire Timeout VISTA-40Installation and Setup GuideAlarm Sounder Duration partition-specific Keyswitch AssignmentSection 5 - Data Field Descriptions 24 25 26Power-Upin Previous State PABX Access CodeEnable Open/Close report for Keyswitch 38 39VISTA-40Installation and Setup Guide Download Command EnablesTITLE and DATA ENTRIES 45 46 47 48 49Section 5 - Data Field Descriptions FIELDAlarm Code for Zones 59 60 61 62VISTA-40Installation and Setup Guide Alarm Code for ZonesAlarm Code for Zones 74 75 76 77Supervisory and Restore Codes Alarm Code for ZonesRestore Report Timing 82 83 84VISTA-40Installation and Setup Guide Non-AlarmReport Codes Second Digit1*34 1*01 1*02 1*03 1*04 1*05 1*09 1*28 1*29 1*301*31 1*331*39 1*361*37 1*381*58 1*491*53 1*572*19 2*022*17 2*18Access Security Downloading PrimerGeneral Information Remote Downloading is not a UL Listed featureStage What Happens Getting On-Linewith a Control PanelVISTA-40Installation and Setup Guide On-LineControl FunctionsTelco Handoff Direct-WireDownloadingSection 24 - Downloading Primer VISTA-40Installation and Setup Guide General Information Setting the Real-TimeClockSetting the Time and Date S E C T I O NVISTA-40Installation and Setup Guide S E C T I O N User Access CodesUser Codes & Levels of Authority Level 0 Installer User 1 CodeLevel 6 Duress Codes Multiple Partition AccessVISTA-40Installation and Setup Guide EXAMPLE OF MULTIPLE PARTITION ACCESSSection 9 - User Access Codes Adding a Master, Manager, or Operator CodePROMPTEXPLANATION Exiting the User Edit Mode Changing a Master, Manager, or Operator CodeAdding an RF Key to an Existing User Deleting a Master, Manager, or Operator CodeBurglary Walk-TestCode + 5 TEST Testing the SystemBattery Test Dialer TestTransmitter ID Sniffer Mode Testing Wireless TransmittersVISTA-40Installation and Setup Guide Step Action 1Enter Installer Code +Power Failure To the InstallerTrouble Conditions Section 10 - Testing The SystemATLIS-FAXFAXBACK Automated Fax Retrieval System VISTA-40Installation and Setup GuideContacting Technical Support Technical SupportA P P E N D I X A UL Installation RequirementsUL365 Police Station Connected Burglar Alarm Regulatory Agency StatementsFor Grade AA Service UL611/UL1610 Central Station Burglary AlarmVISTA-40Installation and Setup Guide For Grade A ServiceAppendix A - Regulatory Agency Statements IN THE EVENT OF TELEPHONE OPERATIONAL PROBLEMSFCC PART 68 NOTICE CANADIAN EMISSIONS STATEMENTS VISTA-40Installation and Setup GuideAVIS Event Logging Commands Summary of System CommandsA P P E N D I X B User Code Commands Programming CommandsVISTA-40Installation and Setup Guide Interface Wiring SpecificationsA P P E N D I X C Interface WiringVISTA-40Installation and Setup Guide Code Contact ID Event CodesA P P E N D I X D TABLE OF CONTACT ID EVENT CODESVISTA-40Installation and Setup Guide Index-1 IndexIndex-2 VISTA-40Installation and Setup GuideIndex-3 IndexIndex-4 VISTA-40Installation and Setup GuideTHE LIMITATIONS OF THIS ALARM SYSTEM LIMITED WARRANTY Page Page Page Page Page Page Page ¬19+l 165 Eileen Way, Syosset, New YorkN7001V5 5/04 Rev A