Honeywell 3.5 manual Remote Keypad Sounder, Long Range Radio Connected to the J7 Triggers, 3-19

Page 29
Remote Keypad Sounder

Section 3 - Installing the Control

TO AUX POWER (TERMINAL 6)

YELLOWWHITE

REDGREEN

(ARMED) (READY)

820820

ohmsohms

REDBLACK

TO J7 / OUT 2 Remote Keypad Sounder Setup

TO J7 / OUT 4 Long Range Radio Connected to the J7 Triggers

2K ELOR

ZONE +

TAMPER SWITCH (CONTACTS CLOSE WHEN SWITCH DEPRESSED).

ZONE

LOCK SWITCH

(NORMALLY OPEN)

TO ZONE 7 (+) (TERMINAL 20)

2K ELOR

J7_keyswitch

Figure 3-24: Remote Keyswitch Wiring

Remote Keypad Sounder

An optional Amseco PAL 328N Piezo Sounder can be used to duplicate the sounds produced by the keypad’s built-in sounder. The panel will remote all sounds (e.g., alarm, trouble, chime, entry/exit, etc.) produced by the

To duplicate the keypad sounds for a particular partition, program that partition number in field 15. Program field 146 Auxiliary Output Enable with a [2].

keypad’s built-in sounder except for the short beeps associated with keypad key depression. One application of this feature might be to produce chime sounds at a distant location from the panel’s keypads.

Remote Keypad Sounder Setup

To setup for a remote keypad sounder, connect the piezo sounder to the panel’s positive auxiliary power output and to Output 1 on the J7 connector as shown in Figure 3-25.

IF USED.

1.OUT 1 IS NO LONGER USABLE FOR SMOKE DETECTOR RESET OR GROUND START (SEE FIELD 1*46).

2.OUT 2 & 4 CAN NO LONGER BE USED TO PROVIDE ALARM TRIGGERS.

TO AUX POWER +

RED

TERMINAL 6

 

 

10mA CURRENT DRAIN)

 

J7 CONNECTOR

 

4142TR CABLE

N/U

1

 

 

 

 

 

 

 

GRAY (GROUND)

 

2

 

 

 

YELLOW (OUT 1)

 

3

 

BLACK

 

 

 

 

 

WHITE (GROUND)

 

4

 

 

 

 

 

 

RED (OUT 2)

 

 

 

AMSECO PAL-328N

 

 

5

 

 

 

 

 

 

 

 

 

PIEZO SOUNDER

 

GREEN (GROUND)

 

 

 

 

 

 

6

 

+

 

 

 

 

 

 

 

BROWN (OUT 3)

 

7

 

 

 

 

 

 

 

 

BLUE (GROUND)

 

 

 

 

 

8

 

 

 

BLACK (OUT 4)

 

9

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

J7_trigcon-001-V1

Figure 3-25: Remote Keypad Sounder Wiring

Long Range Radio Connected to the J7 Triggers

These triggers may be used to trip auxiliary alarm signaling equipment such as the 7720, 7720ULF, and 7920SE Long Range Radios.

The triggers are common to all partitions and must be enabled for each partition (field 220).

The fire and burglary/audible panic alarm triggers are normally LOW and go HIGH until a User Code + OFF is entered in all enabled partition(s) that display these conditions.

The silent panic/duress trigger latches HIGH, except for duress, which is momentary.

Refer to the installation instructions that accompany your radio for the connections to the control panel.

Installing a 4100SM

The 4100SM is used to print event log reports to a serial printer.

NOTE: See SECTION 4: Programming for the programming details when using the 4100SM.

Printer Configurations

Configure the serial printer as follows:

8 data bits, no parity, 1 stop bit

1200 baud

Hardware handshaking using DTR.

3-19

Image 29
Contents 3DUWLWLRQHG6HFXULW\6\VWHP $0&29,67$QVWDOODWLRQDQG6HWXS*XLGH N7001V5 5/04 Rev APage Table of Contents Index List of Figures PRODUCT MODEL NUMBERS Conventions Used in This ManualGeneral Description FeaturesS E C T I O N About the VISTA-40Event Log VISTA-40Installation and Setup GuideAdditional Features Partitioning Setting-Upa Partitioned SystemTheory of Partitioning S E C T I O NVISTA-40Installation and Setup Guide Installing the Cabinet Lock Installing the ControlMounting the Control Cabinet Grade A Mercantile Premises Listing GuidelinesStep Action Installing the Control’s Circuit BoardVISTA-40Installation and Setup Guide Section 3 - Installing the Control Installing the KeypadsWire Run Length/Gauge Table Wire GaugeVISTA-40Installation and Setup Guide Installing External SoundersAlarm Output Supervision Wiring the Alarm OutputSection 3 - Installing the Control Telephone Line ConnectionsSupervising the Alarm Output Using a Siren DriverFigure 3-9 Wiring Connections for Zones VISTA-40Installation and Setup GuideTERMINALS ON CONTROLUsing 2-WireSmoke Detectors on Zone Section 3 - Installing the ControlCompatible 2-WireSmoke Detectors Using 4-WireSmoke Detectors on ZonesUsing Smoke Power Reversal Module VISTA-40InstallationTOand Setup GuideInstalling the 333PRM Smoke Detectors Compatible with the 333PRMFOUR-WIREDETECTOR CIRCUIT Section 3 - Installing the ControlFOUR-WIREDETECTOR CIRCUIT CONTROL PANELVISTA-40Installation and Setup Guide Installing RPM DevicesUsing 2-WireLatching Glassbreaks on Zone 3-103-11 Section 3 - Installing the ControlStep Action Figure 3-16 Polling Loop Connections to theUsing the 4297 Polling Loop Extender VISTA-40Installation and Setup Guide3-12 Polling Loop SupervisionSection 3 - Installing the Control Wireless Zone ExpansionRF System Installation Advisories Installation and Setup of the 5881 RF Receivers3-14 VISTA-40Installation and Setup GuideStep Action StepInstalling the 5800TM Module Section 3 - Installing the ControlThe 5800TM must not be installed within 5800 Series Transmitter SetupVISTA-40Installation and Setup Guide Installing Relay DevicesTransmitter Battery Life Installing the 4204 Relay ModulesSection 3 - Installing the Control Installing the Ground Start ModuleInstalling X10 Devices The wire that reads + 50VDC is the RING sideVISTA-40Installation and Setup Guide Installing a Remote KeyswitchKeyswitch Tamper Operation Wiring for the Remote KeyswitchRemote Keypad Sounder Installing a 4100SMLong Range Radio Connected to the J7 Triggers Section 3 - Installing the ControlVISTA-40Installation and Setup Guide Installing the 4285/4286 VIP ModuleConnecting the 4100SM to a Serial Printer UL installations3-21 Section 3 - Installing the ControlStep Action Step Action3-22 Installing the Audio Alarm Verification ModuleVISTA-40Installation and Setup Guide Section 3 - Installing the Control Connecting the Transformer3-23 UVCM AND UVST SUMMARY OF CONNECTIONSPower Limiting Outputs VISTA-40Installation and Setup Guide3-24 OutputPanel Earth Ground Connections Determining the Control’s Power Supply LoadSection 3 - Installing the Control AC Power Outlet Ground Available fromVISTA-40Installation and Setup Guide Determining the Size of the Standby BatteryTable 3 Alarm Output Current Load AlarmTable 6 Battery Selection Table Section 3 - Installing the ControlRecommended Battery 3-273-28 VISTA-40Installation and Setup GuideProgram Modes ProgrammingEntering and Exiting Programming Mode Data Field Programming ModeVISTA-40Installation and Setup Guide #93 Menu Mode ProgrammingEntry Errors 1Enter Program Mode Installer Code +#93 Menu Mode Programming Commands VISTA-40Installation and Setup GuideMAIN MENU OPTIONSVISTA-40Installation and Setup Guide Zone Number DesignationsZone Defaults Communication DefaultsCommunication Defaults for Zones Zone Response Type DefinitionsType 05 Trouble by Day/Alarm by Night Section 4 - ProgrammingVISTA-40Installation and Setup Guide Zone Input Type DefinitionsType 06 24-HourSilent Alarm Type 07 24-HourAudible AlarmProgramming for 4100SM Programming for Access ControlSection 4 - Programming StepVISTA-40Installation and Setup Guide About Data Field Programming Data Field DescriptionsProgramming Data Fields Installer CodeAlarm Sounder Duration partition-specific VISTA-40Installation and Setup GuideKeyswitch Assignment Prevent Fire TimeoutPower-Upin Previous State 24 25 26PABX Access Code Section 5 - Data Field DescriptionsVISTA-40Installation and Setup Guide 38 39Download Command Enables Enable Open/Close report for KeyswitchSection 5 - Data Field Descriptions 45 46 47 48 49FIELD TITLE and DATA ENTRIESVISTA-40Installation and Setup Guide 59 60 61 62Alarm Code for Zones Alarm Code for ZonesSupervisory and Restore Codes 74 75 76 77Alarm Code for Zones Alarm Code for ZonesVISTA-40Installation and Setup Guide 82 83 84Non-AlarmReport Codes Second Digit Restore Report Timing1*31 1*01 1*02 1*03 1*04 1*05 1*09 1*28 1*29 1*301*33 1*341*37 1*361*38 1*391*53 1*491*57 1*582*17 2*022*18 2*19General Information Downloading PrimerRemote Downloading is not a UL Listed feature Access SecurityVISTA-40Installation and Setup Guide Getting On-Linewith a Control PanelOn-LineControl Functions Stage What HappensSection 24 - Downloading Primer Direct-WireDownloadingTelco Handoff VISTA-40Installation and Setup Guide Setting the Time and Date Setting the Real-TimeClockS E C T I O N General InformationVISTA-40Installation and Setup Guide User Codes & Levels of Authority User Access CodesLevel 0 Installer User 1 Code S E C T I O NVISTA-40Installation and Setup Guide Multiple Partition AccessEXAMPLE OF MULTIPLE PARTITION ACCESS Level 6 Duress CodesPROMPTEXPLANATION Adding a Master, Manager, or Operator CodeSection 9 - User Access Codes Adding an RF Key to an Existing User Changing a Master, Manager, or Operator CodeDeleting a Master, Manager, or Operator Code Exiting the User Edit ModeBattery Test Testing the SystemDialer Test Burglary Walk-TestCode + 5 TESTVISTA-40Installation and Setup Guide Testing Wireless TransmittersStep Action 1Enter Installer Code + Transmitter ID Sniffer ModeTrouble Conditions To the InstallerSection 10 - Testing The System Power FailureContacting Technical Support VISTA-40Installation and Setup GuideTechnical Support ATLIS-FAXFAXBACK Automated Fax Retrieval SystemUL365 Police Station Connected Burglar Alarm UL Installation RequirementsRegulatory Agency Statements A P P E N D I X AVISTA-40Installation and Setup Guide UL611/UL1610 Central Station Burglary AlarmFor Grade A Service For Grade AA ServiceFCC PART 68 NOTICE IN THE EVENT OF TELEPHONE OPERATIONAL PROBLEMSAppendix A - Regulatory Agency Statements AVIS VISTA-40Installation and Setup GuideCANADIAN EMISSIONS STATEMENTS A P P E N D I X B Summary of System CommandsUser Code Commands Programming Commands Event Logging CommandsVISTA-40Installation and Setup Guide A P P E N D I X C SpecificationsInterface Wiring Interface WiringVISTA-40Installation and Setup Guide A P P E N D I X D Contact ID Event CodesTABLE OF CONTACT ID EVENT CODES CodeVISTA-40Installation and Setup Guide Index-1 IndexIndex-2 VISTA-40Installation and Setup GuideIndex-3 IndexIndex-4 VISTA-40Installation and Setup GuideTHE LIMITATIONS OF THIS ALARM SYSTEM LIMITED WARRANTY Page Page Page Page Page Page Page N7001V5 5/04 Rev A 165 Eileen Way, Syosset, New York¬19+l